Most electrical and electronic equipment are designed to tolerate a range of ±10 percent of rated voltage and still operate satisfactorily. However, pan- elboard voltages in the range of 115/200 or 265/460 V will probably translate into unacceptably low voltages at receptacles or utilization equipment, due to addi- tional voltage drop on the branch circuit conductors. Common causes of low voltage at the panel are low tap settings at transformers, feeder conductors that are too long or too small, and loose connections. The first condition results in lower supply voltage; the latter two result in higher impedance that increases voltage drop. Voltage Stability Voltage sags can be caused by either loads on branch circuits, or elsewhere in the distribution system, includ- ing utility-generated sags and brownouts. This is most easily analyzed using an instrument such as a power quality analyzer that measures both voltage and cur- rent simultaneously. Take measurements at each branch circuit in the panelboard. Voltage sag occurring simultaneously with a current surge usually indicates a problem downstream of the measurement point. This would be a load-related distur- bance on the branch circuit. Voltage sag occurring simultaneously with a current sag usually indicates a problem upstream of the mea- surement point, originating elsewhere in the distribu- tion system. Typical source-related disturbances include large three-phase motors coming on line (starting) or sags in the utility network. 196
Current Loading Measure the current on each feeder phase and branch circuit (Figure 9-5). It is important to make these mea- surements using a true-RMS ammeter or digital multi- meter (DMM). Because the combination of fundamental and harmonic currents results in a distorted waveform, a lower-cost average-sensing meter will tend to read low, leading you to assume that circuits are more lightly loaded than they actually are. Loading on the three phases should be as balanced as possible. Unbalanced current will return on the neu- tral conductor, which may already be carrying a high load due to harmonics caused by nonlinear loads. In an ideal, balanced, three-phase electrical distribution sys- tem, there is little or no load on the neutral. Neither the panel feeder nor branch circuits should be loaded to the maximum allowable limit (80 percent of the overcurrent device rating, for continuous loads). There should be some spare capacity to allow for har- monic currents. Harmonics Harmonics are frequencies that are multiples of the fundamental frequency (120 Hz, 180 Hz, 240 Hz, and so on). High-frequency harmonic currents caused by non- linear loads such as computers, adjustable speed motor drives, programmable controllers, and fluorescent fix- tures with electronic ballasts can cause significant heating in power distribution systems, particularly in grounded (neutral) conductors. Harmonics affect the operation or 197
9-5 Branch-circuit panelboard. (Courtesy of Schneider Electric Company.) 198
equipment such as motors, transformers, and overheat- ing of neutral conductors. Triplen Harmonics Triplen harmonics are the following multiples of the fundamental frequency: 3, 6, 9, 12, and so on. They are very harmful for power quality because triplen harmonic currents can add up in the neutrals of the three-phase power systems, as shown in Figure 9-6. Nonlinear loads include such common electrical equipment as switched-mode power supplies used in computers and their peripherals, and fluorescent or HID fixture ballasts. Overloaded neutrals are a potential fire hazard because, unlike phase conductors, they are not pro- tected by an overcurrent device. Third harmonics can overload system neutral conductors even when loads have been balanced among the three phases. For this reason, National Electrical Code 310.15(B) (4)(c) requires that “On a four-wire, three-phase, wye L1 L2 A1 100 Amps A2 100 100 A 100 A Nonlinear Amps Nonlinear 200 A0 100 A Nonlinear Amps L3 100 A3 Up to 200% of the phase current for harmonic Amps neutral current. 9-6 Effect of harmonics due to nonlinear loads. 199
circuit where the major portion of the load consists of nonlinear loads, harmonic currents are present in the neutral conductor; the neutral shall therefore be con- sidered a current-carrying conductor.” In effect, this requires that neutral conductors of such three-phase, four-wire systems be at least the same size as the phase conductors. In practice, neu- trals of systems serving a high proportion of nonlin- ear loads (such as office areas with multiple computers and fluorescent lighting) are sometimes even larger, up to double the size of the associated phase conduc- tors (Figure 9-6). Multiwire Branch Circuits Common neutrals shared by either two or three single- phase branch circuits are subject to the same over- loading as neutrals of three-phase panel feeders, due to asymmetrical loading and third harmonics. Harmonic currents in feeder or branch circuit grounded (neutral) conductors can be measured using a DMM, or by using a probe-type meter to measure the potential from neutral to ground (Figure 9-7). Grounding The neutral and grounding electrode conductor should be bonded together only once, at the service entrance or distribution point of a separately derived system. Other neutral-ground connections elsewhere in the system, such as subpanels or receptacle outlets, are a violation of the National Electrical Code. Unfortunately, improper downstream connections between neutral and grounding conductors are also 200
Ground bus PLUKE 87 III RANGE HOLD ⍀ V mV mA V A V OFF A A mA A COM V⍀ Neutral bus 9-7 Measuring neutral current. very common, and they are frequently a source of power quality problems. When the neutral and grounding electrode con- ductors are bonded at a subpanel or other location, the ground path becomes a parallel return path for normal load current, and there will be measurable current on the ground. To determine whether improper connections exist, measure the current on the grounded (neutral) con- ductor and then on the grounding electrode conduc- tor and look at the ratio between them. For example, if the neutral current is 70 A and the ground current is 2 A, the small ground current probably represents 201
normal leakage. But if the neutral measures 40 A and the green ground measures 20 A, this probably indi- cates that there are improper neutral-ground connec- tions. The smaller the ratio of neutral-to-ground current, the more likely it is that neutral-ground binds exist. All neutral-to-ground connections not permitted by the National Electrical Code should be removed. This will improve both safety and power quality. Overheated Terminals and Connections Poor connections and loose terminations increase cir- cuit impedance and thus voltage drop. They can also cause hard-to-diagnose intermittent problems, such as circuits that cycle on and off unpredictably (a loose connection may open when it heats up, and then close again when it cools down). “Hot spots” indicating possible poor connections and terminations can often be found using thermal scanning, which is discussed further in Chapter 10. Visual inspection may also be useful. A preventive maintenance program of checking and tightening conductor connections on a regular basis can help prevent this type of problem before it occurs. Circuit Breakers Although molded-case circuit breakers typically have long service lives, contacts and springs can wear out, particularly when the device has tripped frequently or been used as a switch to turn equipment or circuits on 202
and off. As with other poor connections, marginal breakers increase circuit impedance and voltage drop. Overheating due to their poor internal connections may also lead to “nuisance tripping.” Measure voltage drop across the circuit breaker, from line side to load side, to determine the condition of internal components (see Figure 9-8). If voltage drop exceeds 100 millivolts (mV), the branch circuit breaker should be replaced. Readings in the 35 to 0.5 0.5 Ohm Ohm B AC 1.0 Ohm 9-8 Measuring voltage drop across circuit breaker. 203
100 mV range should be noted and those breakers rechecked at regular intervals. Power Factor Power factor is a key element of power quality; it is computed as real power (volt-amperes) divided by apparent power (watts). Both electric utilities and facility engineers typically try to maintain power fac- tor as close to unity (1.0) as possible. However, many types of equipment and devices attached to modern electric supply systems cause either a leading or lag- ging power factor, because impedance causes a phase shift between the voltage and current waveforms. Power factor is a measure of how efficiently a load uses electricity or how much energy is consumed by the load versus how much the utility must provide. Electric utilities frequently levy high penalties on large electricity users (industrial plants, office campuses) that fail to keep power factor above some minimum such as 0.95 power factor. Impedance Impedance is at the heart of power factor. Typically, there should be an impedance value of less than 0.5 Ω between the phase and grounded (neutral) conductor, and between the neutral conductor and equipment grounding conductor. Figure 9-9 summarizes power quality troubleshoot- ing recommendations. 204
Symptoms Probab Low voltage levels at Utility suppl panelboard or service too low. entrance equipment. Transforme too low. 205 Loose conn feeder serv conductors. Voltage sag coincides Downstream with current surge, when high inrush measured at panelboard. as motor(s) incandesce Voltage surge coincides Upstream s with current decrease, disturbance when measured at panelboard. 9-9 Troubleshooting char
ble Cause Action or Items to Check ly voltage Consult utility. er tap settings Use higher voltage taps. nection in Check connections. vice . m load with Consider feeding sensitive current, such loads from other circuits ) or or panelboards. ent lighting. source-related Consult utility. e. rt for power quality problems.
Symptoms Probab Significant neutral Unbalanced current on three-phase different ph feeder. panelboard Current on neutral of Harmonics three-phase feeder nonlinear lo equals or exceeds phase currents. 206 Current on shared neutral Harmonics of multiwire branch of nonlinear lo circuit equals or exceeds phase currents. Neutral-to-ground Neutral-to-g potential exceeds connections 0.5 V. other than s entrance eq 9-9 Troubleshooting chart for p
ble Cause Action or Items to Check d loading on Balance panelboard. hases of d. generated by Increase size of feeder oads. neutral conductor. generated by Use individual two-wire oads. branch circuits. ground Remove improper s at panels neutral-to-ground service connections. quipment. power quality problems. (Continued)
Symptoms Probab Long branc Low voltage levels at receptacles or Loose conn utilizations equipment. branch circ 207 Voltage drop across Worn circui circuit breaker exceeds contacts an 100 mV, from load to line side. 9-9 Troubleshooting chart for p
ble Cause Action or Items to Check ch circuit runs. Install oversized conductors to compensate for voltage drops. nections in Check and tighten cuits. connections. it breaker Replace circuit breaker. nd springs. power quality problems. (Continued)
This page intentionally left blank
CHAPTER 10 Troubleshooting With Infrared Thermography Infrared thermography (also called thermal scanning) is an important diagnostic tool for troubleshooting electrical equipment and systems. Overheating can be a symptom of many different kinds of problems, and equipment typically goes through a stage where it gives off heat before an actual physical failure occurs. This heat is infrared radiation, in energy wavelengths (invisible to the human eye). Infrared thermography uses infrared cameras to “see” and measure the thermal energy being emitted by overheated electrical equipment. This information is used to pinpoint electrical problems before failures occur. Infrared cameras, in effect, take photographs of electrical equipment by detecting heat energy rather than visible light. Infrared thermography is used to detect the following general types of electrical main- tenance problems: Poor Connections: Vibration and thermal cycling can cause electrical connections to loosen. Mois- ture and contamination can corrode connections. 209 Copyright © 2007, 2000, 1996 by The McGraw-Hill Companies, Inc. Click here for terms of use.
Poor connections cause hot spots that are easily detected using infrared cameras. Overloaded Conductors: Overloaded electrical conductors typically cause protective devices such as circuit breakers and fuses to operate. When they dont’, the overloaded conductors run hotter than usual. Short Circuits and Ground Faults: Short circuits and ground faults (a short circuit involving an equipment ground) also should cause protective devices to operate. But sometimes the current, while not sufficient operate a circuit breaker or ground fault relay, is sufficient to damage con- ductor insulation and cause overheating that can ignite a fire. Harmonics: High-frequency harmonic currents caused by electronic loads such as computers, adjustable speed motor drives, and fluorescent fixtures with electronic ballasts can cause signif- icant heating in power distribution systems, par- ticularly in grounded (neutral) conductors. Mechanical problems: Problems such as loose cou- plings and misalignment of motor shafts cause overheating that can be detected by thermal scanning. The troubleshooting chart in Figure 10-1 lists typi- cal operational problems of electrical equipment that 210
211 Symptoms Probable Overheated terminal Loose or corrod or connection. Damaged condu Transformer Insulation failure overheats. Shorted turns in Transformer bushing core. overheats. Loose connectio Motor overheats. Internal fault. Misaligned shaf High or low volta Shorted stator c Faulty connectio 10-1 Troubleshooting chart for pro
e Cause Action or Items to Check ded terminal. Tighten or replace terminal. uctor. Replace conductor. e. See Chapter 8. n transformer See Chapter 8. on. Tighten or repair connector. See Chapter 8. ft. See Chapter 10. age. See Chapter 10. coil. See Chapter 10. on. See Chapter 10. oblems identified with thermal scanning.
can be identified using thermal scanning (infrared thermography). Safety Considerations Infrared thermography is a noncontact troubleshoot- ing technique. It is typically performed on energized systems operating at full load. However, while its’ not necessary for an infrared camera or electronic thermometer to contact the equip- ment, in many cases thermal scanning is still hazardous work. This is because it is often performed on energized equipment such as panelboards and switchboards, with the covers removed. A mistake can result in accidental contact with “live” parts and possible electrocution, burns, or arc-flash injuries to the technicians. For this reason, all thermal scanning work around exposed conductors and equipment must be per- formed in accordance with NFPA 70E-2004, Standard for Electrical Safety in the Workplace—particularly min- imum approach distances and proper use of personal protective equipment (PPE). 212
Index AC circuits, voltmeters for, 7 Analog test instruments AC motors testing, 16 (analog meters) (Cont.): Acceleration issues, of motors, phase-sequence indicator, 22 151–152 power factor meter, 19 Accessories, for DMMs, 29 power quality analyzers, 23–24 Accuracy: single-function, 1–2 tachometers, 20 of ammeters, 3–4 types of, 1–2 with clamp-on ammeters, 3–4 usefulness of, 1 of digital multimeters, 25, 26 voltmeters, 6–13 Air gap feeler gauges, 94 Angular-contact ball bearings, Alignment, of bearings, 101–102 Alternating-current motors, 159 162 Ammeters, 2–6 Apparent power, 204 accuracy of, 3–4 Arc streams, 71–72 applications of, 4–5 Arc tubes, of HID luminaires, clamp-on, 2–4, 93 in electric baseboard heater, 87–88 Arc-blasts, 44 4–5 Armatures, heat of, 131–132 recording, 5–6 Audible indicators (ammeter), in three-phase motor, 4 volt-ohm-ammeters, 12, 13 12, 13 Analog test instruments (analog Backlighting switch (DMMs), 27 meters), 1–24 Ball bearings: ammeters, 2–6 cable-length meters, 22 angular-contact, 162 electrical thermometers, double-row, deep-groove, 162 failure of, 159 21–22 heat of, 172 footcandle meters, 21 self-aligning, 160 frequency meters, 19 single-row, deep-groove, megohmmeters, 13–19 161–162 213 Copyright © 2007, 2000, 1996 by The McGraw-Hill Companies, Inc. Click here for terms of use.
Ballasts: Button, of incandescent lamp, 75 in fluorescent luminaires, 58 Button rod, of incandescent noise in, 84–85 two-lamp, 61 lamp, 75 Ball-thrust bearings, 162–163 Cable insulation testing, 13–14 Base: Cable-length meters (time- of HID luminaires, 89 domain reflectometers, of incandescent lamp, 75 TDRs), 22 loose, 89 Calibration, 51 Bearings (see Motor bearings) Cameras, infrared (see Infrared Bent shafts, in split-phase cameras) Canvas strips, 95 motors, 101 Capacitance measurements, Binoculars, 95 with DMMs, 32, 34, 38 Blackening, of ends of lamps: Capacitors, 38 Capture (hold, freeze) mode within 1 inch of ends, 67 (DMM), 27 in brownish ring, 70 CAT I, 37 with dark streaks, 70 CAT II, 37 dense, 66–67, 69 CAT III, 36, 37 early in life, 68–69 CAT IV, 36 extending 2–3 inches from Cathodes, in fluorescent luminaires, 58 base, 66–67 Centrifugal switches, defective, of HID luminaires, 89 102 of inner arc tube, in HID Chatter, in contactors and relays, 187–189 luminaires, 89 Circuit(s): short lamp life and, 63–66 AC, 7 spot, 69 DC, 6, 7 Blinking, of fluorescent harmonics and, 200, 201 multiwire branch, 200, 201 luminaires, 60–61 open, 49–53, 98 Branch circuit(s): short, 103–104, 210 Circuit breakers: harmonics and, 200, 201 power quality problems in, multiwire, 200, 201 panelboards, 198 202–204 Brightness, unequal (fluorescent testing, with megohmmeters, luminaires), 73–74 17 Brownouts, 196 tripped, 40–41 Brushes: voltage drop across, 203, 207 sparks at, 137–141 wear of, 141–144 Bulbs, of incandescent lamp, 75 Burned insulation, in dry-type transformers, 56 214
Circuit grounded (neutral) Conductor(s) (Cont.): conductors, 200 neutral electrode, 200, 201 overloading of, 210 Clamp-on ammeters, 2 accuracy with, 3–4 Connections: currency measurements with, corroded, 209 2–3 delta connections, 100 for electric motor downstream connections, maintenance, 93 200, 201 in electric motors, 98–99 Clamp-on power factor meters, neutral-to-ground 93 connections, 202, 206 overheated, 202, 211 Cleaning solvents, 94 reversed, 98–99, 102–103 Closed contactors, 181 Wye connections, 100, Clothing hazards, 45 106, 109 Coil(s): Contactors, 175, 177–189 distortion of, 55 chatter in, 187–189 in dry-type transformers, 55 closed, 181 in electric motors, 92, 96–97 coil temperature and, 189 grounded, 92, 96 defined, 175 shorted, 96–97 discolored, 186–187 temperature of, 189 drop out failure in, 182–185 Coil connections: fast operation of, 185 in electric motors, 98–99 hum in, 187–189 reversed, 98–99, 102–103 noise in, excessive, 187–189 Color, abnormal (see pitted, 186–187 pull in failure of, 178–181 Discoloration) starter issues of, 181 Common or return (COM) Contamination, 209 input, 28 Continuity, 52 Commutators: digital multimeters and, heat of, 133–134 31, 33 issues with, in motors, noise in, 31 137–141 testing, 31, 33 Complete shorts, in dry-type Continuity Capture mode transformers, 53–54 (DMM), 42 Computerized (digital) meters, Core loss, in dry-type 1–2 transformers, 56 Concentric coils, wye Core-and-coil fluorescent connections with, 100 luminaires, 58 Conductor(s): Corroded connections, 209 circuit grounded, 200 loss, in dry-type transformers, 55 215
Current: Digital multimeters (DMMs) in DMMs, 28 (Cont.): in fluorescent luminaires, 58 instantaneous, 5 capture mode of, 27 category number of, 37 Current decrease, 205 construction features of, Current loading, 197 Current measurements: 27–28 for continuity testing, 31, 33 with clamp-on ammeters, 2–3 convenience features of, with digital multimeters, 27–28 30, 31 for current measurements, 30, digital multimeters for, 197 Current sag, 196 31, 197 Current surges, 196, 205 for diode testing, 33, 35 Cycling, thermal, 209 display of, 26–27, 43 Cylindrical-roller bearings, 162 features of, 27–28 freeze mode of, 27 DC circuits, 6, 7 for frequency measurements, DC motors and generators 32, 34 testing, 14–15 function selection in, 28 Decreased light output: hold mode of, 27 inputs for, 28–29 of fluorescent luminaires, modes of, 27 73–74 for motor leads testing, 114 power quality analyzers vs., 23 of incandescent luminaires, for resistance measurements, 77, 79–81 30–32, 38 De-energized systems: safety features of, 36–37 lockout/tagout in, 46–47 safety precautions for, 37–38 open-circuited transformer, 49 safety ratings of, 36 test leads for, 28–29 Defective centrifugal switches, Underwriters Laboratories, 102 Inc. and, 36 Delta connections, 100 using, 29–35 Delta-wound motors: for voltage measurements, three-phase, 110–115 29–30 Dielectric testers, portable oil, 94 Dim light (see Decreased light Digital (computerized) meters, output) 1–2 Diode testing: Digital multimeters (DMMs), with digital multimeters, 33, 1–2, 25–38 35, 38 accessories for, 29 accuracy of, 25, 26 safety with, 38 for capacitance measurements, Direct (two-terminal) test, 17 32, 34, 38 216
Dirty motors, 116–117 Electric motors, 91–158 Disassembly, of electrical grounded coils in, 92, 96 identifying, 104–110 equipment, 41 open circuit in, 98 Discharging capacitors, 38 recordkeeping, 110–115 Discoloration: reversed coil connections in, 98–99 of contactors and relays, reversed phase in, 99 186–187 shorted coils in, 96–97 split-phase motors, 101–104 of HID luminaires, 83 three-phase delta-wound Displays: motors, 110–115 troubleshooting chart for, of digital multimeters, 26–28, 115–158 38, 43 Electric tachometers, 20 in grounded coil, 96 Electrical failure, 41 infinity in, 96 Electrical hazards, 43, 44 liquid-crystal diode, 27, 28 Electrical thermometers, 21–22 overlimit, 38 Electromagnetic induction, 91 of power quality analyzers, 23 Electromotive force (EMF), 6 Distribution equipment Excess secondary voltages, 55 Exciting currents, 56 monitoring, 193 Exhaust tubes, of incandescent DMM (see Digital multimeters) Double-row, deep-groove ball lamp, 75 bearings, 162 Faults, intermittent, 42–43 Double-shielded bearings, 160 “Feel” test, 168 Downstream connections, Fields, heat of, 134–135 Filament, of incandescent lamp, 200, 201 Drop out failure, 182–185 75 Dry-type transformers, 49–56 Fire-rated (FR) clothing, 46 Fixtures, lighting complete short in, 53–54 ground fault in, 53 (see Luminaires) grounded windings in, 54–56 Fluorescent luminaires, 58–74 noise in, 56 open circuit in, 49–53 cathodes in, 58 overheating, 55 noise in, 73 smoke, 56 preheat, 58 smoke in, 56 radio interference in, 72 vibrations in, 56 short lamp life of, 63–66 starting issues of, 62, 63 Earth-resistance testing, direct Footcandle meters, 21 method of, 18 Electric ballasts, in fluorescent luminaires, 58 Electric baseboard heaters, 4–5 217
FR (fire-rated) clothing, 46 Harmonics: Freeze (hold, capture) mode defined, 197 grounding, 200–202 (DMM), 27 infrared thermography and, Frequency, 19 210 Frequency measurements, with multiwire branch circuits and, 200, 201 DMM, 32, 34 power quality problems, 197, Frequency meters, 19 199–202 “Frozen” (tight) bearings, triplen, 199–200 101 Hazards, 43, 44 Function selection (DMM), 28 High-intensity discharge (HID) Fuses: luminaires, 76, 79–89 of DMM, 36 blackening of, 89 in dry-type transformers, 56 lamp breakage in, 86–87 of incandescent lamp, 75 lamp breakage of, 86 open, 56 noise in, 84–85 testing, with voltmeters, 12 radio interference in, 84 starting issues of, 79–80 Gas, in lamps, 75 High-voltage transients, DMMs Generators, 14–15 Grinding rigs, 95 and, 36 Ground(s), 92 Hold (freeze, capture) mode defined, 92 (DMM), 27 reversed, 102–103 “Hot spots,” 202, 210 Ground faults: Humidity, 63 in dry-type transformers, 53 Humming: infrared thermography and, in contactors and relays, 210 187–189 voltmeters and, 9–13 Ground resistance testing, in fluorescent luminaires, 73 17–19 Impedance, 204–207 Grounded coils, 92, 96 Incandescent luminaires, 59, Grounded windings: 75–78 in dry-type transformers, components of, 75 54–56 lamp breakage in, 78 quartz-halogen lamps, 59 megohmmeters and, 54 quartz-iodide lamps, 59 Grounding, 200–202 short lamp life of, 77–78 Grounding electrode traditional types of, 59 tungsten-halogen lamps, 59 conductors, 200, 201 Induction, electromagnetic, 91 Hand-held test meters, 36 Hard stones, 95 218
Industrial electric service, Lamp(s) (Cont.): small, 10 quartz-iodide, 59 tungsten-halogen, 59 Inert gas, in tungsten-halogen (See also Luminaires) lamp, 75 Lamp breakage: Infinity, in grounded coil in HID luminaires, 86–87 display, 96 in incandescent luminaires, 78 in outer bulb, of HID Infrared cameras, 209, luminaires, 86 210, 212 Lamp life, short: Infrared thermography, blackening and, 63–66 209–212 blackening at, 68–69 of fluorescent luminaires, harmonics and, 210 63–66 overheating, 209 of incandescent luminaires, poor connections in, 209–210 77–78 safety considerations for, 212 short circuits and, 210 Lamp-within-a-lamp design, vibrations in, 209 59, 75 Inner arc tubes, blackening of, LCD displays (see Liquid-crystal 89 diode displays) Inputs, for DMMs, 28–29 Instant start lamps, 58 Lead-in wires, of incandescent Instantaneous current, 5 lamp, 75 Insulation: Lighting fixtures (see luminaires) burned, 56 Liquid-crystal diode (LCD) failure of, in dry-type displays (DMMs), 27, 28 transformers, 56 “Live” (see Working “live”) Insulation breakdown: “Lo Bat” warning (DMMs), 28 Load: shorted coils and, 96 in transformers, 54 monitoring at, 193 Insulation resistance tester, 94 motors under, 152–154 Intermittent faults, 42–43 Lockout/tagout, 46–47 Iodine vapor, in tungsten- Long-term monitoring, 192 Low-voltage, 195, 196 halogen lamp, 75 causes of, 196 at panelboard, 205 Jewelry, and safety, 45 at receptacles, 207 at service entrance equipment, Lamp(s): blackening on ends of, 63–69 205 fitting, to fixture, 85–86 testing, 9 fixture not fitting to, 85–86 at utilization equipment, 207 instant start, 58 voltmeters, for testing, 9 quartz-halogen, 59 219
Lubrication: Monitoring: frequency, of motor bearings, at distribution equipment, 163, 167 193 of motor bearings, 163, at load, 193 167–168 long-term, 192 of motors, 163, 167–168 power quality problems, procedure for, 167–168 192–194 at service, 193 Luminaires (lighting fixtures), 57–89 Monitors, recording, 192 Motor(s): defined, by NEC, 57 fitting lamps to, 85–86 AC, 16 fluorescent, 58–74 acceleration issues of, high-intensity discharge, 76, 151–152 79–89 alternating-current, 159 incandescent, 59, 75–78 ammeters in, 4 armature, heat of, 131–132 mA (milliampere), 29 brush wear of, 141–144 Magnifying glass, 95 commutate issues of, 137–141 Main distribution panel, 194 commutator, heat of, MCC (motor control center), 133–134 193 DC, 14–15 Mechanical problems, 210 delta-wound, 110–115 Megger (see Megohmmeters) dirty, 116–117 Megohmmeters (meggers), 1, electric, 91–158 fast, 124–126 13–19 fields, heat of, 134–135 for AC motors testing, 16 under load, 152–154 cable insulation testing with, lubrication of, 163, 167–168 magnetic noise of, 158 13–14 megohmmeters and, 14–16 for circuit breakers testing, 17 noisy, 144–146, 158 for DC motors and generators overheated, 129–130, testing, 14–15 152–154, 211 for ground resistance testing, reverse direction of, 120 rotation of, 152 17–19 scraping noise of, 158 grounded windings and, 54 slow, 127–129 for power cable testing, 13–14 sparks at brush and, 137–141 for safety switches testing, 17 speed issues with, 121–129, for switchgears testing, 17 Metal, and safety, 45 149–151 Microampere (µA), 29 split-phase, 101–104 Milliampere (mA), 29 Moisture, 209 220
Motor(s) (Cont.): Motor control center (MCC), 193 stalling, 147–148 Motor leads testing, 114 start failure of, 119–120, 148 Motor rotation testers, 95 three-phase, 4, 110–115 µA (microampere), 29 unbalanced, 135–137 Multimeters, 93 unbalanced line current of, Multirange one-scale 157 vibrations in, 135–137, voltmeters, 8 155–156 Multiwire branch circuits: wet, 118 harmonics and, 200, 201 Motor bearings, 159–173 neutral electrode conductors alignment of, 101–102 angular-contact ball bearings, of, 206 162 ball-thrust bearings, 162–163 Nameplates: cylindrical-roller bearings, 162 of electric baseboard heater, 4 double-row, deep-groove ball for motor identification, 104 bearings, 162 double-shielded, 160 National Electric Code frozen, 101 (Article 100): heat of, 169–171 lubrication frequency, 163, 167 on grounding, 200 lubrication procedure, on luminaires, 57 167–168 on neutral-to-ground open bearings, 159–160 replacement of, 160 connections, 202 self-aligning ball bearings, on qualified persons, 44 160 on triplen harmonics, single-row, deep-groove ball bearings, 161–162 199, 200 single-shielded bearings, 160 Needles (indicator), 1 spherical-roller bearings, 162 NEMA size 1 contactor, 177 spherical-roller thrust NEMA Standards: bearings, 163 in split-phase motors, for lead markings for dual- 101–102 voltage, delta-wound tapered-roller bearings, 163 motors, 111 testing, 168–173 tight, 101 for lead markings for dual- types of, 159–167 voltage, wye-wound worn bearings, 101 motors, 109 for motor identification, 104 Neutral electrode conductors, 200, 201 of multiwire branch, 206 on three-phase feeder, 206 Neutrals, overloading of, 199 Neutral-to-ground connections, 202, 206 221
NFPA 70E-2004 (Standard for Open breakers, in dry-type Electrical Safety in the transformers, 56 Workplace), 44 Open circuits, 92 on electrical testing, 45 defined, 92 on infrared thermography, in dry-type transformers, 49–53 212 in electric motors, 98 on personal protective in split-phase motors, 102 equipment, 45 Open fuses, in dry-type on qualified persons, 44 transformers, 56 Noise (sounds, tones): of ballast, 84–85 Optical pyrometers, 21–22 in contactors and relays, Optical time-domain 187–189 reflectometers in continuity tests with (ODTRs), 22 Outer bulb, lamp breakage of, DMMs, 31 86 in dry-type transformers, 56 Overcurrent devices, opening of, in fluorescent luminaires, 86 Overflow plugs, oil leakage 73 from, 116 of HID luminaires, 84–85 Overheating: humming, in fluorescent checking for, with voltmeters, luminaires, 73 53 magnetic, 158 of connections, 202, 211 of motors, 144–146, 158 in dry-type transformers, 55 scraping, 158 infrared thermography and, Noncontact troubleshooting, 209 212 of motors, 129–130, 152–154, Nonlinear loads, 199 “Nuisance tripping,” 203 211 of terminals, 202, 211 Odor, from insulation melting, of transformer bushing, 53 211 ODTRs (optical time-domain of transformers, 53, 211 reflectometers), 22 Overlimit display (DMM), 38 Overloading: Ohmmeters, 93 of conductors, 210 Oil dielectric testers, portable, of neutrals, 199 of transformers, 54 94 Overvoltages, 36, 195 Oil filters, portable, 94 Oxidized parts, of HID Oil leakage, from overflow luminaires, 83 plugs, 116 125-VAC duplex receptacle, 7 Open bearings, 159–160 222
Panelboards: Power quality problems (Cont.): branch-circuit, 198 power factor of, 204 current surges at, 205 voltage levels and, 193, low-voltage at, 205 195–196 safety at, 45 safety with, 45 PPE (see Personal protective voltage measurement equipment) technique at, 195 voltage sags at, 205 Preheat fluorescent lamps, 58 voltage surges at, 205 Psychrometers, 94 Pull-in failure, of contactors Personal protective equipment (PPE): and relays, 178–181 Pyrometers, optical, 21–22 for infrared thermography, 212 safety with, 45–46 Qualified persons, 44 Phase, reversed (see Reversed Quartz tube, in tungsten- phase) halogen lamp, 75 Phase-sequence indicator, 22 Quartz-halogen lamps (see Phosphor, in fluorescent Tungsten-halogen lamps) lamps, 58 Quartz-iodide lamps (see Photo tachometers, 20 Pitted contactors, 186–187 Tungsten-halogen lamps) Pointers (indicator), 1 Polyphase motors, unbalanced Radiation pyrometers, 21–22 Radio interference: line current of, 157 Portable oil dielectric testers, 94 in fluorescent luminaires, 72 Portable oil filters, 94 of HID luminaires, 84 Power, 204 Rapid start lamps, 58, 63 Power cable testing, 13–14 Rattling, of HID luminaires, 89 Power factor, 204 Real power, 204 Power factor meters, 19, 93 Receptacles, low-voltage at, 207 Power quality analyzers, Recording: ammeters, 5–6 23–24 meters, 94 Power quality problems, Recording mode, 42–43 Recording monitors, 192 191–207 Recordkeeping, 110–115 in circuit breakers, 202–204 Relays, 175–176, 178–189 current loading and, 197 chatter in, 187–189 harmonics and, 197, 199–202 coil temperature and, 189 impedance and, 204–207 defined, 175 monitoring, 192–194 discolored contacts and, overheated terminals and 186–187 connections, 202 drop out failure in, 182–185 223
Relays (Cont.): Safety equipment, 45 fast operation of, 185 Safety features, of DMM, 36–37 hum in, 187–189 Safety precautions, for DMM, noise in, excessive, 187–189 pitted contacts and, 186–187 37–38 pull in failure of, 178–181 Safety switches testing, 17 single-pole, single-throw, 176 Scanning, thermal (see Infrared starter issues of, 181 time delay, 185 thermography) Scraping noise, 158 Resistance measurements: Self-aligning ball bearings, 160 with digital multimeters, Service, monitoring at, 193 30–32, 38 Service entrance equipment, safety with, 38 205 Resistance thermometers, 21 Shimmering, of fluorescent Reverse direction of motors, 120 Reversed coil connections: luminaires, 60 Short(s), 53–54, 92 in electric motors, 98–99 Short circuits: in split-phase motors, infrared thermography and, 102–103 210 Reversed grounds, 102–103 Reversed phase, 99 in split-phase motors, Rotating equipment speed, 20 103–104 Rotation, of motors, 95, 152 Shorted coils: Safety: in electric motors, 96–97 with capacitors, 38 insulation breakdown and, 96 with diode testing, 38 dress for, 45 Sine waveform, 192 with infrared thermography, Single-function analog meters, 212 with lockout/tagout, 46–47 1–2 metal and, 45 Single-pole, single-throw (SPST) at panelboards, 45 with panelboards, 45 relay, 176 with personal protective Single-row, deep-groove ball equipment, 45–46 qualified persons and, 44 bearings, 161–162 with resistance measurements, Single-shielded bearings, 160 38 Sleeve bearings: troubleshooting tips for, 43–46 working “live” and, 46 failure of, 159 heat of, 170–171 Smoke, in dry-type transformers, 56 “Soft keys” (DMMs), 28 “Sound” test, 168 Sounds (see Noise) Speed issues, 121–129, 149–151 Spherical-roller bearings, 162 224
Spherical-roller thrust bearings, Tachometers, 20, 93 163 Tagout (see Lockout/tagout) Tapered-roller bearings, 163 Split-phase motors, 101–104 TDRs (time-domain reversed coil connections in, 102–103 reflectometers, cable-length short circuits in, 103–104 meters), 22 tight bearings in, 101 Terminals, overheated, 202, 211 Test instruments, analog (see Spot blackening, 69 Analog test instruments) Spring tension scales, 95 Test leads: SPST (single-pole, single-throw) for digital multimeters, relay, 176 28–29, 38 Stalling, of motors, 147–148 removal of, 38 Starter (fluorescent lamps), 58 Thermal cycling, 209 Starter issues: Thermal scanning (see Infrared of contactors and relays, thermography) 181 Thermocouples, 21 Thermography, infrared (see of fluorescent luminaires, 62 of HID luminaires, 79–80 Infrared thermography) lack of, in fluorescent Thermometers: luminaires, 62, 63 electrical, 21–22, 94 of motors, 119–120, 148 resistance, 21 Stationary (stator) windings, 91 Three-phase delta-wound Stem press, of incandescent motors, 110–115 lamp, 75 Three-phase feeder, 206 Stethoscopes, transistorized, 93 Three-phase motors, 4 Streaks, dark (in lamps), 70 Three-phase power factor Stroboscopic effect, of HID meters, 19 luminaires, 83 Thrust bearings, 162–163 Sunburn (suntan), of HID Tight (“frozen”) bearings, luminaires, 85 101 Support wires, of incandescent Time-domain reflectometers, lamp, 75 optical (OTDR), 22 Switchboards, three-phase Time-domain reflectometers power factor meters in, 19 (TDRs, cable-length Switches: meters), 22 Tones (see Noise) centrifugal, 102 Transformers: defective centrifugal, 102 dry-type, 49–56 safety, 17 insulation breakdown in, 54 Switchgears testing, 17 overheating, 53, 211 “Switching operations” safety, 45–46 225
Transformers (Cont.): Vibrations: overheating of bushing of, in dry-type transformers, 56 211 infrared thermography, overloading of, 54 209 winding, 53–54 of motor, 135–137, 155–156 Transistorized stethoscopes, 93 Triplen harmonics, 199–200 Volt (V), 6 Tripped circuit breakers, 40–41 Voltage: Troubleshooting, 39–47 in DMMs, 28 with continuity capture drop in, across circuit breakers, mode, 42 203, 207 correcting cause of trouble, in dry-type transformers, 55 41–42 excess secondary, 55 levels of, 193, 195–196 with disassembly, 41 low, 195, 196, 205, 207 finding cause of trouble, at 125-VAC duplex receptacle, 41–42 7 for intermittent faults, 42–43 power quality problems and, noncontact, 212 with recording mode, 42–43 193, 195–196 for safety, 43–46 range of, in voltmeters, thinking before acting, 40–41 (See also specific topics, e.g., 7, 8 in voltmeters, 7, 8 Dry-type transformers) Voltage measurements: Tungsten-halogen (quartz- with digital multimeters, halogen, quartz-iodide) 29–30 lamps, 59, 75 at panelboards, 195 25-kVA three-phase unit, 50 Voltage sags, 196, 205 Two-terminal (direct) test, 17 Voltage surges, 205 Voltage to ground, 56 UL categories, 37 Voltmeters (analog), 6–13 UL Standard 3111-1, 36 for AC circuits, 7 Unbalanced motors, 135–137 applications of, 8 Underwriters Laboratories common types of, 12, 13 connecting, to circuit, 6 Inc., 36 for DC circuits, 6, 7 Unequal brightness, 73–74 for electric motor Utility-generated sags, 196 Utilizations equipment, low- maintenance, 93 fuse testing with, 12 voltage at, 207 ground faults and, 9–13 for low-voltage test, 9 V (volt), 6 multirange one-scale, 8 Vibrating-reed tachometers, 20 226
Voltmeters (analog) (Cont.): Windings (Cont.): for overheating checks, 53 stationary, 91 voltage ranges of, 7, 8 testing of, 92 transformers and, Volt-ohm-ammeters, 12, 13 53–54 Wattmeters, 93 Working “live,” 44, 46, 212 Wet motors, 118 Worn bearings, 101 Windings: Wye connections, 100, 106 in dry-type transformers, with concentric coils, 100 54–56 lead markings for grounded, 54–56 dual-voltage, 109 227
Search
Read the Text Version
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- 41
- 42
- 43
- 44
- 45
- 46
- 47
- 48
- 49
- 50
- 51
- 52
- 53
- 54
- 55
- 56
- 57
- 58
- 59
- 60
- 61
- 62
- 63
- 64
- 65
- 66
- 67
- 68
- 69
- 70
- 71
- 72
- 73
- 74
- 75
- 76
- 77
- 78
- 79
- 80
- 81
- 82
- 83
- 84
- 85
- 86
- 87
- 88
- 89
- 90
- 91
- 92
- 93
- 94
- 95
- 96
- 97
- 98
- 99
- 100
- 101
- 102
- 103
- 104
- 105
- 106
- 107
- 108
- 109
- 110
- 111
- 112
- 113
- 114
- 115
- 116
- 117
- 118
- 119
- 120
- 121
- 122
- 123
- 124
- 125
- 126
- 127
- 128
- 129
- 130
- 131
- 132
- 133
- 134
- 135
- 136
- 137
- 138
- 139
- 140
- 141
- 142
- 143
- 144
- 145
- 146
- 147
- 148
- 149
- 150
- 151
- 152
- 153
- 154
- 155
- 156
- 157
- 158
- 159
- 160
- 161
- 162
- 163
- 164
- 165
- 166
- 167
- 168
- 169
- 170
- 171
- 172
- 173
- 174
- 175
- 176
- 177
- 178
- 179
- 180
- 181
- 182
- 183
- 184
- 185
- 186
- 187
- 188
- 189
- 190
- 191
- 192
- 193
- 194
- 195
- 196
- 197
- 198
- 199
- 200
- 201
- 202
- 203
- 204
- 205
- 206
- 207
- 208
- 209
- 210
- 211
- 212
- 213
- 214
- 215
- 216
- 217
- 218
- 219
- 220
- 221
- 222
- 223
- 224
- 225
- 226
- 227
- 228
- 229
- 230
- 231
- 232
- 233
- 234
- 235
- 236
- 237
- 238
- 239
- 240
- 241
- 242
- 243
- 244
- 245
- 246
- 247
- 248
- 249
- 250
- 251
- 252
- 253
- 254
- 255
- 256
- 257
- 258
- 259
- 260
- 261
- 262
- 263
- 264
- 265
- 266
- 267
- 268
- 269
- 270
- 271
- 272
- 273
- 274
- 275
- 276
- 277
- 278
- 279
- 280
- 281
- 282
- 283
- 284
- 285
- 286
- 287
- 288
- 289
- 290
- 291
- 292
- 293
- 294
- 295
- 296
- 297
- 298
- 299
- 300
- 301
- 302
- 303
- 304
- 305
- 306
- 307
- 308
- 309
- 310
- 311
- 312
- 313
- 314
- 315
- 316
- 317
- 318
- 319
- 320
- 321
- 322
- 323
- 324
- 325
- 326
- 327
- 328
- 329
- 330
- 331
- 332
- 333
- 334
- 335
- 336
- 337