SIGNAL CONVERTERS Signal converters change the signal from one form to another. Where ever possible, these are the standard inputs and output ranges. Normally we show them on a block diagram as a box with an input and output with a label to say what it does. Here are some examples. All these examples have opposite versions i.e. I/P, P/M and so on.
Flapper Nozzle Mechanism If the flapper moves away from the nozzle then the transmitted or output pressure will fall to a low value. If the flapper moves towards the nozzle then the transmitted pressure will rise to almost the supply pressure. The transmitted pressure is approximately proportional to the movement of the flapper and thus the change in the measured variable.
Pneumatic transducers The flapper-nozzle displacement sensor forms the basis of all pneumatic transducers. It consists of a fixed restrictor (orifice) in series with a variable restrictor (flapper and nozzle). Varying the separation x of the flapper and nozzle alters the resistance to air flow. The output is taken to be the pressure p. An increase in x reduces the nozzle resistance and the output pressure.
FLAPPER-NOZZLE MECHANISM and D. P. CELLS
Description The nozzle – flapper system is widely used in D.P. cells. The form shown converts differential pressure (e.g. from a differential pressure flow meter) into a standard pneumatic signal. This is widely used in the control of air operated pipeline valves. The bellows respond to the differential pressure and moves the lever. This moves the flapper towards or away from the nozzle. The air supply passes through a restrictor and leaks out of the nozzle. The output pressure hence depends on how close the flapper is to the end of the nozzle. The range of the instrument is adjusted by moving the pivot and the zero position is adjusted by moving the relative position of the flapper and nozzle. This system is used in a variety of forms. Instead of bellows, a bourdon tube might be used and this is operated by an expansion type temperature sensor to produce a temperature - pneumatic signal converter.
Electrical DP Cells These provide the same functions as the pneumatic versions but given an output of 4 – 20 mA using electrical pressure transducers. They are typically used with D.P. flow meters.
Converters The pictures below show typical units for converting 4 – 20 mA into 0.2 – 1 bar and vice versa. They contain adjustments for range and zero. They are widely used for converting the standard pneumatic and electric signals back and forth. They can also be adjusted to work with non standard inputs to convert them into a standard form. Current to Pressure Converter (I/P) Pressure to Current Converter (P/I)
Controllers The devices that receive the measured value signals and compare them with the desired value signals (set points) and process their differences if any, to produce correction signals in response to any system disturbances. However, there are various time lags or delays that the controller must compensate for and ensure a steady output as near to the desired value as possible.
Controller Actions – Time Lags or Delays Measurement Lag - The actual value in time that it takes a measuring unit to indicate or transmit a signal equal in value to the variable being measured after a disturbance has occurred. Process Lag - The value in time that it takes the process being controlled to change by the required amount after the correcting (regulating) unit has been adjusted to effect the change, i.e. if water is being heated in a tank by a steam coil, the process lag is the time taken for the water to attain a new value after the regulating valve has been adjusted. Transfer Lag - A process will contain a transfer lag if, for example, the process liquid is heated indirectly by causing steam to heat a transfer medium in an inner tank. Distance Velocity Lag - The time delay between a change in process condition at the correcting element and the arrival of this changed condition at the detecting element.
Effects of Process Lags on the Response of the Controlled Condition The function of the controller (a) Distance velocity lag Position of correcting is to overcome and (b) (L) element compensate for the effects (c) of the system lag. (d) (L) Perfect process with no (e) lags Change in controlled (f) condition Process with ideal distance velocity lag Figure showing the effects of process lags on controlled Process with single condition response. capacity lag Process with single capacity and distance velocity lag Process with two capacity and transfer lags Time
Controller Action – Two-Step or On/Off Control In this, the simplest of controller actions, two extreme positions of the controller are possible, either on or off. If the controller were, for example, a valve it would be either open or closed. A heating system is considered with the control valve regulating the supply of heating steam. The controller action and system response is shown in the figure below. As the measured value rises above its desired value the valve will close. System lags will result in a continuing temperature rise which eventually peaks and then falls below the desired value. The valve will then open again and the temperature will cease to fall and will rise again. This form of control is acceptable where a considerable deviation from the desired value is allowed.
Two-Step or On/Off Control
Controller Action – Proportional Action This is a form of continuous control where any change in controller output is proportional to the deviation between the controlled condition and the desired value. The proportional band is the amount by which the input signal value must change to move the correcting unit between its extreme positions. The desired value is usually located at the centre of the proportional band. Offset is a sustained deviation as a result of a load change in the process. It is an inherent characteristic of proportional control action. Consider, for example, a proportional controller operating a feedwater valve supplying a boiler drum. If the steam demand, i.e. load, increases then the drum level will fall. When the level has dropped the feedwater valve will open. An equilibrium position will be reached when the feedwater valve has opened enough to match the new steam demand. The drum level, however, will have fallen to a new value below the desired value, i.e. offset.
System response to proportional controller action
Proportional Band and Gain Proportional Band = the input change required to change the output 100%.
Wide, Narrow, Low & High
Percentage Valve Opening Open 100% Proportional 20% Proportional 100 Band Band 80 20% Proportional • Band 60 20 40 60 80 100 40 Percentage of Scale Range 20 0 Closed
Proportional Band Is the amount the measured value of a controlled condition must change in order that the control valve may be moved from fully closed to fully open position. The proportional band setting required for any given application will depend on plant characteristics and the various lags in the control loop. There is an optimum value which will give stable control. If the p.b. is made too narrow (high controller sensitivity), the process will become unstable, while if it is made too wide ( low controller sensitivity), the process will be sluggish.
Response Versus P.B., Proportional Control only.
Controller Action – Integral Action This type of controller action is used in conjunction with proportional control in order to remove offset. Integral or reset action occurs when the controller output varies at a rate proportional to the deviation between the desired value and the measured value. The integral action of a controller can usually be varied to achieve the required response in a particular system.
Controller Action – Derivative Action Where a plant or system has long time delays between changes in the measured value and their correction, derivative action may be applied. This will be in addition to proportional and integral action. Derivative or rate action is where the output signal change is proportional to the rate of change of deviation. A considerable corrective action can therefore take place for a small deviation which occurs suddenly. Derivative action can also be adjusted within the controller.
Controller Action – Multiple Term Controller Action The various controller actions in response to a process change are shown in the figure below. The improvement in response associated with the addition of integral and derivative action can clearly be seen. Reference is often made to the number of terms of a controller. This means the various actions: proportional (P), integral (I), and derivative (D). A three-term controller would therefore mean P+I+D, and two-term usually P+I.
System Recovery Time Response to Controller Actions
Controllers – Basic Construction Flapper Nozzle Air Supply Output, p Comparator Set Point Measured bellows Value Signal Correcting Unit
Description of the Basic Construction The diagram shows the same flapper nozzle arrangement seen earlier. One end is connected to comparator bellows. The movement of this end of the flapper is thus dependent upon the relative values of the measured value and set point signals. Any difference between the two values brings about movement of the flapper which, in turn, changes the separation between the flapper and the nozzle thereby changing the value of the generated pneumatic pressure signal. It should be noted, however, that the total pressure change of 0.2 to 1.0 bar is brought about by change in separation of 40 um. That means, in this form, this device is a very high gain device and as such of not much practical use.
Proportional Controller Flapper Nozzle Comparator Set Point Air Supply Measured bellows Relay Valve Value Signal Correcting Unit
Proportional Controller Description. The diagram shows addition of a negative feedback bellows or proportional bellows being supplied with the output signal and actuating the other end of the flapper. The separation between the flapper and nozzle is thus under the combined influence of the opposite movements brought by the two ends of the flapper. By a suitable selection of relative bellows coefficients, it is possible to arrange to have any desired change in separation between flapper and nozzle for a specified change in the value of the measured variable, and thus control the gain or sensitivity of the device. This then forms the basis of a pure proportional controller.
Summary (P) Proportional control: action of a controller whose output signal is proportional to the deviation. i.e. Correction signal ∞ deviation (I) Integral control: action of a controller whose output signal changes at a rate which is proportional to the deviation. i.e. Velocity of correction signal ∞ deviation Objective: To reduce offset to zero. (D) Derivative control: action of a controller whose output signal is proportional to the rate at which the deviation is changing. i.e. Correction signal ∞ velocity of deviation Objective: Gives quicker response and better damping.
Correcting Unit / Regulating Unit The controller output signal is fed to the correcting unit which then alters some variable in order to return the system to its desired value. This correcting unit may be a valve, a motor, a damper or louvre for a fan or an electric contactor. Most marine control applications will involve the actuation or operation of valves in order to regulate liquid flow.
Adjusting valves: Do you believe in automation? Central control room • Overview of entire process • Make immediate adjustment anywhere • Safe location • History of past operation Process pictures courtesy of Petro-Canada Products
Pneumatic Control Valves It can be considered as made up of two parts — the actuator and the valve. • In the arrangement shown a flexible diaphragm forms a pressure tight chamber in the upper half of the actuator and the controller signal is fed in. • Movement of the diaphragm results in a movement of the valve spindle and the valve. • The diaphragm movement is opposed by a spring and is usually arranged so that the variation of controller output corresponds to full travel of the valve.
The valve body is arranged to fit into the particular pipeline and houses the valve and seat assembly. Valve operation may be direct acting where increasing pressure on the diaphragm closes the valve. A reverse acting valve opens as pressure on the diaphragm increases. The diaphragm movement is opposed by a spring which will close or open the valve in the event of air supply failure depending upon the action of the valve.
Some Typical C. Valves
Pneumatic Control Valves Diaphragm Motor Valve Body Or Actuator Containing Inner Valve or Plug Required to Varies the Area Convert a Change Thro Which the of Pressure into a Fluid Passes Stroke
Valves: What are the two main features? Sampson Valves The actuator provides the ability to change the flow resistance, i.e., the size of the opening for flow. The most common actuator is a pneumatic diaphragm. The body of the valve defines the flow path and is selected to achieve the desired fluid flow behavior.
Valve Body: We match the valve body to the fluid type and process needs? http://www.tycoflowcontrol-pc.com/products_results.asp?Selection=Double+Flanged+Butterfly+Valve&m=1 Fluids: water, nitrogen, tree pulp and water, blood, sewage, food products (yogurt), highly pure pharma products, hazards (isocyanates), polymer melts, and just about anything else that flows! http://images.google.ca/imgres?imgurl=http://www.ckit.co.za/Secure/Catalogues/mac%2520steel/fluid%2520control/MS%2520image%2520 24%2520- 2520thumb.jpg&imgrefurl=http://www.ckit.co.za/Secure/Catalogues/Mac%2520steel/Fluid%2520control/MS%2520fluid%2520control.htm &h=150&w=113&sz=5&hl=en&start=83&tbnid=3ZKYixrpLJ5wTM:&tbnh=96&tbnw=72&prev=/images%3Fq%3Dball%2Bvalves,%2Bpr ocess%2Bcontrol%26start%3D80%26ndsp%3D20%26svnum%3D10%26hl%3Den%26sa%3DN
Trim Trim generally refers to the removable internal parts of a valve which come in contact with the flowing fluid. The components included in trim are different depending on the type of valve, but they usually include packing follower, lantern ring, packing retaining ring, stem, stem lock pin, guide bushing, valve plug and seat ring (cage).
Bonnets Bonnets functionally connect or join the actuator to the valve body and serve as a housing for the stem seal or packing. Four types of bonnets are provided for various operating temperatures and corrosive conditions: i) Plain iii) Extension Column ii)Radiation Fin iv) Bellows Seal
Packings
Plain Bonnet Used for fluids having temperatures between 0 and 200 C. With grafoil packing can be used upto 450 C. Extension Column Bonnet Used for low temperature service between 0 to -270 C. Low temp frosting can cause packing damage. The extension bonnet removes the packing from the frosting area. Radiation Fin Bonnet High temperature tends to dry out packing and decompose lubricants. For temperatures >200 C an extension bonnet with radiating fins can be used. Bellows Seal Bonnet Used to provide an absolutely tight seal when a highly explosive, toxic, costly or volatile fluid is flowing thru the valve. Bellows material is usually stainless steel or monel depending on pressure. Additional packing is provided for emergency use in case of damaged bellows.
Valve Packing
Inner Valve Single Seated Double Seated Tight Shut-Off ie. Balanced Forces ie Very Low leakage More Accurate Rate. Positioning of the Valve. Unbalanced Forces Requiring Large Difficult to Prevent Diaphragm Motor. Leakage. In order to achieve accurate valve disc positioning and overcome the effects of friction and unbalanced forces a valve positioner may be used.
Valve Positioner
Function of Valve Positioner To position the valve stem more accurately than is possible using only the controller output. To provide extra power to operate the valve, so increasing the speed of valve movement.
Valve Positioner Description The controller signal acts on a bellows which will move the flapper in relation to the nozzle. This movement will alter the air pressure on the diaphragm which is supplied via an orifice from a constant pressure supply. The diaphragm movement will move the valve spindle and also the flapper. An equilibrium position will be set up when the valve disc is correctly positioned. This arrangement enables the use of a separate power source to actuate the valve. Actuator Operation The control signal to a correcting unit may be pneumatic, electric or hydraulic.
Search
Read the Text Version
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- 41
- 42
- 43
- 44
- 45
- 46
- 47
- 48
- 49
- 50
- 51
- 52
- 53
- 54
- 55
- 56
- 57
- 58
- 59
- 60
- 61
- 62
- 63
- 64
- 65
- 66
- 67
- 68
- 69
- 70
- 71
- 72
- 73
- 74
- 75
- 76
- 77
- 78
- 79
- 80
- 81
- 82
- 83
- 84
- 85
- 86
- 87
- 88
- 89
- 90
- 91
- 92
- 93
- 94
- 95
- 96
- 97
- 98
- 99
- 100
- 101
- 102
- 103
- 104
- 105
- 106
- 107
- 108
- 109
- 110
- 111
- 112
- 113
- 114
- 115
- 116
- 117
- 118
- 119
- 120
- 121
- 122
- 123
- 124
- 125
- 126
- 127
- 128
- 129
- 130
- 131
- 132
- 133
- 134
- 135
- 136
- 137
- 138
- 139
- 140
- 141
- 142
- 143
- 144
- 145
- 146
- 147