Low Ice Making Capacity - Remote Air CooledProblem Likely Cause Probable Solution Dirty condenser Clean condenser Hot ambient Check condenser inlet temp Water leak Check purge valve, check curtain Water inlet valve leaks through Check inlet valve Low on refrigerant Add refrigerant, if cycle time drops, check for leak Incorrect superheat Check evaporator superheat, if significantly low or high, replace TXVLong Harvest Cycle Dirty evaporator De-scale water systemFalse bin full signal No harvest assist Check harvest assist solenoid Bridge thickness too big Check and adjust bridge thickness Machine in very cool ambient Increase room temperature Ice jammed in between curtain and sump Clear ice away Curtain does not close correctly Check curtain for proper swingMakes Excessive Noise - Air cooled Probable Solution Replace fan bladeProblem Likely Cause Replace motor mountFan blade vibrates Blade is bent Tighten bolts Fan motor mount is broken Replace pumpCompressor vibrates Mounting bolts loose Tighten screwsWater pump vibrates Pump bearings wornPanels vibrate Mounting screws loose January 2015 Page 51
Test Procedures - SensorsAll electrical components in this ice machine can be diagnosed with a volt-ohmmeter.Curtain Switch:1. Test using the controller’s indicator lights. Observe SW1 and SW2. Open and close the curtain in question.When the curtain is opened, the SW light will be ON. When the curtain gets to within a half inch of closing (atthe switch) the SW light will go OUT.2. Test with an ohmmeter. Disconnect electrical power. Open the control box cover. Unplug the curtain switchlead from the controller. Connect an ohmmeter to the leads of the switch. Open and close the curtain. Whenthe curtain is closed, the switch is closed and there will be continuity. When the curtain is open, the switch isopen and the circuit will be open.3. Test the controller’s curtain switch circuit by jumping the connectors on J1 or J2 together. Reconnectelectrical power. When jumped, the matching SW light will go out. When unplugged or open, the SW light willbe ON. Curtain Switch Indicator Lights Light is ON when curtain is OPEN Single curtain models have one indicator light ON all the time. January 2015 Page 52
Ice Thickness Sensor1. Test using the controller’s indicator light. Observe the Ready To Harvest light. Shut the machine off. Usea wire to connect the metal part of the Ice Thickness sensor to the evaporator or simply remove the IceThickness Sensor and touch its metal surface to the metal control box wall. The Ready for Harvest light shouldgo ON.2. Test with an Ohmmeter. Disconnect electrical power. Open the control box cover. Unplug the ice thicknesssensor lead from the controller. Connect an ohmmeter lead to the ice thickness sensor lead, touch the otherohmmeter lead to the ice machine chassis. There must be an open circuit. If there is continuity, the sensormust be replaced. If there is no continuity, touch the ohmmeter lead to the metal part of the ice thicknesssensor. There should be continuity. If open, check the ice thickness sensor for scale build up. Clean andrecheck. If still open, replace the ice thickness sensor.3. Test the controller’s ice thickness sensor circuit by connecting a wire from J10 to ground. Reconnectelectrical power. The Ready for Harvest light should go ON.Ready To Harvest light is Ice Thickness SensorON when water contacts icethickness sensor. January 2015 Page 53
Water Level Sensor1. Test using the controller’s indicator lights (sump empty and sump full). Unit must be powered up and theremust be water in the sump. Add some manually if needed. Locate water level sensor. Release from sumpcover and slowly lift up until the mid-length probe is out of the water. The sump empty light should come on,and if the unit is on the inlet water solenoid valve will open to fill the reservoir. Return the water level sensor toits normal position. If the unit is on and calling for ice the water will fill until the top probe is in contact with it, atthat time the sump full light will switch ON.2. Test with an ohmmeter. Disconnect electrical power. Open the control box cover. Unplug the connector at J9.Locate water level sensor and remove it from the sump cover. Test 1: Place one lead of the ohmmeter on thelongest probe and the other on the controller end of the red wire, there should be continuity. Test 2: Place onelead on the controller end of the white wire and the other on the mid-length probe, there should be continuity.Test 3: Place on lead on the controller end of the black wire and the other on the shortest probe, there shouldbe continuity.If not, clean the probes and recheck.3. Test the controller’s water level sensor circuit.Reconnect electrical power. Unplug harness fromwater level sensor, the sump empty light should beON. Jump harness wires white and black. The sumpfull light should be ON. Jump harness wires white andred, the sump full and sump empty lights will be OFF.Check harness wire by wire for continuity if there is noreaction from the controller during this test. Sump Empty Light Sump Full Light January 2015 Page 54
Temperature Sensors1. Check controller. If the sensor calibration is completely out of range, the code display will read either 5 or 7.2. Check with an ohmmeter.• Open control box cover, unplug sensor from J6. Water temperature probe:• Measure the temperature of the water.• Push and release the clean button.• Wait one minute.• Measure the resistance of the water probe (two leads next to the open socket) and compare to the resistance in the chart for that temperature. Any reading within 1000 ohms is acceptable.Discharge sensor:• Measure the temperature of the discharge line as close to the sensor as possible.• Measure the resistance of the discharge temperature sensor (two leads farthest away from the open socket on the harness connector) and compare to the resistance in the chart for that temperature. Any reading within 1000 ohms is acceptable.3. Alternate procedure: Remove both water and discharge sensors from their places on the ice machine. Putboth into a container of ice water. Put a thermometer in the water. When the thermometer is at 32 degrees F.,check the resistance of each sensor. The resistance should be within 1000 ohms of 32649. Water Temperature Set Discharge Temperature Set January 2015 Page 55
Test Procedures - CompressorFailure to start.Single phase models. All have resistance start, capacitor run type motors. Check voltage to compressor at thecontactor. Compare the idle voltage (compressor off) to the active voltage (compressor starting). The supplyvoltage must not be less than the lowest rated voltage for the ice machine. If the voltage is correct, proceed tothe next step.Check starting components. Most models use a PTCR to cut power to the start winding after the compressorhas started. Check the PTCR for resistance. The resistance check must be when the PTCR is at roomtemperature – any temperature between 50 and 100.At that temperature resistance should be very low between 25 and 50 ohms. Also check resistance to ground,it should be infinite. If the PTCR is good, check the compressor windings.Measure resistance from Common to ground. It should be infinite. Measure resistance from Common to Run –compare to the chart. Measure resistance from Common to Start – compare to the chart.Compressor check for high amp draw. Measure amp draw of starting circuit. If it does not drop off immediatelyafter start up, the PTCR should be replaced. It is not practical to check a PTCR for resistance at hightemperatures as the resistance drops very fast as the PTCR’s temperature falls. If the compressor is drawingexcessive amps but is operating, the run capacitor may be open. Disconnect electrical power, discharge thecapacitor and measure its resistance. If open, replace it. If shorted to ground, replace it.Any time the compressor is replaced, the PTCR and run capacitor should also be replaced, or if the modelwas equipped with a potential relay, start capacitor and run capacitor, those should be replaced with thecompressor. Most Scotsman service compressors include those parts.Some systems use a potential start relay and start capacitor in place of the PTCR.Potential relay. If the compressor will not start, check the amp draw of the starting circuit. If very low, thepotential relay contacts or start capacitor may be open. Measure the resistance of the potential relay contactsand the start capacitor. If either is open it should be replaced. If the compressor starts but draws very highamps from the starting circuit, the potential relay may not switch off. In that case the relay should be replaced. January 2015 Page 56
Test Procedures - Fan motor1. Test using the controller’s indicator lights.Note: Fan pressure control connection must be jumped to perform this test.Put the controller into test mode (depress Off for 3 seconds then depress Clean for 3 seconds). At the end ofthe test cycle, the fan motor will be powered and the Condenser Fan motor indicator light will be on. The fanmotor should start and run at that time. If it does not, repeat the test but check the voltage to the fan motor,it must receive full voltage at the fan motor lead connection at the end of the test. If there is voltage and themotor does not operate, replace the motor. If there is no voltage, check the controller high voltage harnessconnection.The fan motor lead is the top wire. Check voltage from it to ground, at the end of the test, when the fan motorindicator light is On, there must be voltage from this pin to ground.Note: high voltage power is supplied to the bottom pin from the contactor line. Refer to the machinewiring diagram as needed.2. Test using an ohmmeter. Disconnect electrical power. Unplug fan motor from harness. Measure fan motorwinding resistance. If open, replace the fan motor.This light is ON when the fan motor Brown 8 - Fan Motorshould be operating. Red 7 - Inlet Water Sol White 6 - Water Pump 5 - Hot Gas Valve Blue 4 - Compressor 3 - Purge Valve Brown White Yellow Red Black 1 - Line InFan Pressure Control, must CLOSE tooperate fan motor. January 2015 Page 57
Test Procedures - Water Pump1. Test using the controller’s indicator lights. Check the indicator light during the freeze cycle. The light willbe On for all but the 30 second anti-slush period, so observe the light for one minute. When it is On, checkthe water pump, it should be operating. If not, check voltage to the pump. If low check the voltage from thecontroller to ground. The water pump pin is number 6. If there is voltage at that pin to ground, but very lowvoltage at the pump motor, there must be a broken wire in the harness. If the voltage is low at pin 6, thecontroller should be replaced.2. Test using an ohmmeter. Disconnect electrical power. Unplug the water pump motor leads from the harness.Measure the resistance of the motor windings. If open, replace the pump. Measure resistance to ground. Ifthere is any, replace the pump. Brown 8 - Fan Motor Red 7 - Inlet Water Sol White 6 - Water Pump 5 - Hot Gas Valve Blue 4 - Compressor 3 - Purge Valve Brown White Yellow RedWater Pump light is Black 1 - Line InON when pump isoperating. January 2015 Page 58
Test Procedure - Purge valve1. Test using the controller’s indicator lights.• Shut unit off by holding the Off button for 3 seconds. Wait four minutes.• Push and release the On button, observe the Purge Valve indicator light. As the unit drains the reservoir, the purge valve will be powered. When it gets power, the indicator light will be ON.• If the purge valve does not open to drain the reservoir when its indicator light is on, do a voltage check. Shut the unit down by holding the Off button in for 3 seconds. Unplug the harness connection from the purge valve.• Wait four minutes. Push and release the On button to restart the machine.• As the unit drains the reservoir, the purge valve connection should receive full voltage. If it does, the purge valve should be replaced. If there is no voltage, check voltage from the controller to ground. The purge valve pin is 3 (dump valve on wiring diagram). If there is voltage from that pin to ground, but low voltage at the valve harness connection, the harness has a broken wire or poor connection and must be replaced.• If the voltage to ground is low, the controller should be replaced.Note: The coil of this valve is internally rectified, and will normally show infinite resistance whentested with an ohmmeter Brown 8 - Fan Motor Red 7 - Inlet Water Sol White 6 - Water Pump 5 - Hot Gas Valve Blue 4 - Compressor 3 - Purge Valve BrownThis light will be ON Whitewhen the Purge Valve Yellowis powered. Red Black 1 - Line In January 2015 Page 59
Test Procedure - Compressor contactor1. Test using the controller’s indicator lights. When the unit is in ice making mode (continuous F in the display)the compressor contactor will have power.• Check the Compressor indicator light, when it is on the compressor contactor will have pulled in. If it is not, do a voltage check.• Place voltmeter leads on the coil of the contactor. There should be full voltage.• If there is full voltage present and the contactor has not pulled in, replace the contactor.• If there is no voltage check if the high pressure cut out is open. If the high pressure cut out is closed, check for voltage from the controller to ground. The contactor pin is 4. Check from 4 to ground, or on 220 volt models, to the other power leg (usually L2) when the compressor indicator light is on. There should be voltage. If not, replace the controller.• If there is voltage at the controller but not at the contactor coil, the harness wires or connectors are damaged and must be replaced.2. Test using an ohmmeter. Test the coil of the contactor for continuity or shorts to ground. Replace if open orshorted.3. Check connections and contacts. Be sure connections are tight and that the contacts are not burnt. Replaceany contactor with burnt contacts. Brown 8 - Fan Motor Red 7 - Inlet Water Sol White 6 - Water Pump 5 - Hot Gas Valve Blue 4 - Compressor 3 - Purge Valve Brown White Yellow RedThis light is ON when the compressor isoperating. Black 1 - Line In January 2015 Page 60
Test Procedures - Pressure switchesThere are two pressure switches: Fan and High Pressure cut out.Fan. The fan pressure switch will open to shut the fan motor off at a certain pressure and re-close at a presethigher pressure.High pressure cut out. The high pressure cut out switch will open at a preset pressure, shutting off power tothe compressor contactor. After the pressure has fallen to another preset level, the switch will re-close and thecontactor coil will be engergized.To Test Fan Pressure Switch:A. Attach refrigeration gauge set to high side port.B. Unplug both wires from fan pressure control. Be SURE the wire's terminals are wrapped in electrical tape toprevent short circuits to ground during the test.C. Connect ohmmeter to terminals of fan pressure control..D. Switch ice machine on, observe pressure that the pressure control closes at, compare to spec. Switch unitoff, allow system to equalize, observe pressure the pressure control opens at, compare to spec.To Test High Pressure Switch:A. Attach refrigeration gauge set to high side port.B. Unplug fan motor or shut water off if water cooled.C. Measure voltage between contactor side terminal of high pressure control and ground.D. Switch ice machine on, observe pressure that the pressure control opens at, compare to spec. Allow systemto equalize, observe the pressure that the pressure control closes at, compare to spec.TransformerCheck secondary voltage, it must be between 10 and 15.5 AC volts. Replace if no voltage is output or if aboveor below the acceptable voltage..ControllerThe controller’s software operation is confirmed if it is functioning. Execute the test to confirm its operation ofthe loads. Illumination of a diagnostic code (other than E) is not an indication of controller failure. Each coderequires its own diagnosis. January 2015 Page 61
Test Procedures - Liquid Line Solenoid1. Test using the controller’s indicator lights. Put the controller into test mode (depress Off for 3 secondsthen depress Clean for 3 seconds). At the end of the test cycle, the liquid line valve will be powered and theCondenser Fan motor indicator light will be on. The liquid line valve should be open at that time.If it is not, repeat the test but check the voltage to the liquid line valve coil, it must receive full voltage at theliquid line lead connection at the end of the test. If there is voltage and the valve does not operate, replace thevalve coil.If there is no voltage, check the controller high voltage harness connection. The liquid line solenoid lead is thetop wire. Check voltage from it to ground, at the end of the test, when the Condenser Fan indicator light is On,there must be voltage from this pin to ground or, on 220 volt models, to the other power leg.Note: high voltage power is supplied to the bottom pin from the contactor line. Refer to the machinewiring diagram as needed.2. Test using an ohmmeter. Disconnect electrical power. Unplug liquid line coil from harness. Measure liquidline coil resistance. If open, replace the liquid line valve coil. Brown 8 - Fan Motor Red 7 - Inlet Water Sol White 6 - Water Pump 5 - Hot Gas Valve Blue 4 - Compressor 3 - Purge Valve Brown White Yellow RedIndicator light for Liquid Line Coil Black 1 - Line In January 2015 Page 62
Test Procedure - Inlet Water Solenoid Valve1. Test using the controller’s indicator lights.Shut unit off by holding the Off button for 3 seconds. Wait four minutes.Push and release the On button, observe the Water Solenoid indicator light. After the unit drains the reservoir,the inlet water valve will be powered to refill the reservoir. When it gets power, the indicator light will be ON.If the water valve does not open to fill the reservoir when its indicator light is on, do a voltage check. Shut theunit down by holding the Off button in for 3 seconds. Unplug the harness connection from the inlet water valve.Wait four minutes.Push and release the On button to restart the machine. After the unit drains the reservoir, the inlet water valveconnection should receive full voltage. If it does, the inlet water valve should be replaced.If there is no voltage, check voltage from the controller. The inlet water solenoid valve pin is 7. If there isvoltage from that pin to ground, or on 220 volt models to the other power leg, but low voltage at the valveharness connection, the harness has a broken wire or poor connection and must be replaced. If the voltage toground or other leg is low, the controller should be replaced.2. Test using an ohmmeter. Disconnect electrical power. Unplug coil from harness. Measure coil resistance. Ifopen, replace the inlet water solenoid.Light is ON when inlet water Brown 8 - Fan Motorsolenoid is in operation. Red 7 - Inlet Water Sol January 2015 Page 63 White 6 - Water Pump 5 - Hot Gas Valve Blue 4 - Compressor 3 - Purge Valve Brown White Yellow Red Black 1 - Line In
Test Procedure - Harvest Assist1. Test using the controller’s indicator lights. Push and release the Harvest button. The Hot Gas indicator lightwill be on. At the same time the Harvest Assist Solenoid or Motor will be powered. If the ice on the evaporatoris thin, the ejection pin will extend. If the ice is nearly full sized, the pin will press against the ice until it releasesfrom the evaporator, then the pin will extend. If the pin extends, the solenoid or motor is good. If not, do avoltage check.Unplug the high voltage harness from the harvest assist solenoid. Attach a voltmeter to the harness connector.Push and release the Harvest button. There should be full voltage at the connector.If there is and the solenoid does not extend, replace the solenoid. If full voltage is not present, check voltageat the controller. If there is no voltage, check voltage from the controller to ground. The hot gas / harvest assistpin is 5.If there is voltage from that pin to ground, but low voltage at the solenoid harness connection, the harness hasa broken wire or poor connection and must be replaced. If the voltage to ground is low, the controller should bereplaced.Note: The coil of this valve is internally rectified, will normally show infinite resistance when testedwith an ohmmeter.Hot Gas or Vapor Valve1. Test using the controller’s indicator lights. If the unit is running, or has been off for more than 4 minutes, pushand release the Harvest button. The Hot Gas indicator light will be on and the hot gas valve will be energized.The compressor will force discharge gas into the evaporator inlet, warming it.If the evaporator inlet does not warm up, do a voltage check. Shut the unit off by holding the Off button infor 3 seconds. Unplug the high voltage harness from the hot gas solenoid. Attach a voltmeter to the harnessconnector. Wait 4 minutes.Push and release the Harvest button. There should be full voltage at the connector. If there is and the solenoiddoes not open, replace the solenoid coil. If full voltage is not present, check voltage at the controller. If thereis no voltage, check voltage from the controller to ground or on 220 volt models to the other power leg. Thehot gas pin is 5. If there is voltage from that pin to ground, but low voltage at the solenoid harness connection,the harness has a broken wire or poor connection and must be replaced. If the voltage to ground is low, thecontroller should be replaced.2. Test with an ohmmeter. Disconnect electrical power. Unplug high voltage harness from hot gas or vaporvalve. Measure resistance of hot gas or vapor valve coil. If open, replace the coil. This light will be ON during harvest. Both the Hot Gas Valve coil and the Harvest Assist will have power when this light is ON. January 2015 Page 64
Performance Data - C0322Model C0322A 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 2.4 to 2.6 lb. 80Cycle Time 10-12(minutes) Water Temp 11-12 12-13 13-14 12-13 13-14 14-16Suction Pressure 50 13-14 14+ 15-16(PSIG) 26 14-15 16-17Discharge 70 105 32Pressure (PSIG) 235 130 80 150 250 200 90 End of Freeze Harvest End of Freeze HarvestModel C0322W 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 2.4 to 2.6 lb 80Cycle Time 9-11(minutes) Water Temp 11+ 11+ 10-11 12+ 12+ 10-12Suction Pressure 50 12-13 13+ 12-13(PSIG) 32 13-14 13+Discharge 70 95-100 32Pressure (PSIG) 245 100-110 80 140 245 150 90 End of Freeze Harvest End of Freeze HarvestSuction Pressure Graph C0322A 70/50 PSIG120100 80 60 40 20 014:02:00 14:02:38 14:03:23 14:04:08 14:04:53 14:05:39 14:06:24 14:07:08 14:07:54 14:08:38 14:09:24 14:10:10 14:10:54 14:11:39 14:12:24 14:13:10 January 2015 Page 65
Performance Data - C0522Model C0522A 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 4.5 to 5 lb. 80Cycle Time 11-13(minutes) Water Temp 13 13 16 14 14 16-18Suction Pressure 50 15 15 18(PSIG) 32 16 19Discharge 70 105Pressure (PSIG) 228 34 80 180 120 270 90 210 End of Freeze Harvest End of Freeze HarvestModel C0522W 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 4.5 to 5 lb. 80Cycle Time 13-15(minutes) Water Temp 15 15 14 16 16 14-15Suction Pressure 50 16-17 17 15(PSIG) 23 17 16Discharge 70 85Pressure (PSIG) 235 36 80 115 110 245 90 200 End of Freeze Harvest End of Freeze HarvestSuction Pressure Graph C0522A-1 70/50 PSIG120100 80 60 40 20 013:14:58 13:15:33 13:16:19 13:17:04 13:17:49 13:18:35 13:19:20 13:20:05 13:20:50 13:21:35 13:22:20 13:23:05 13:23:50 13:24:35 13:25:20 13:26:05 13:26:51 January 2015 Page 66
Performance Data - C0722Model C0722A 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 7.3 to 7.5 lb. 80Cycle Time 13(minutes) Water Temp 13-14 13-14 17 14-15 14 17-18Suction Pressure 50 15-16 15 19-20(PSIG) 30 17 21-22Discharge 70 92-94 33Pressure (PSIG) 240-250 150-120 80 150-155 310-330 190-200 90 End of Freeze Harvest End of Freeze HarvestSuction Pressure Graph PSIG C0722A 70/50 100 90 80 70 60 50 40 30 20 10 02:04:13 PM 2:04:53 PM 2:05:33 PM 2:06:13 PM 2:06:53 PM 2:07:33 PM 2:08:13 PM 2:08:53 PM 2:09:33 PM 2:10:13 PM 2:10:53 PM 2:11:33 PM 2:12:13 PM 2:12:53 PM 2:13:33 PM 2:14:13 PM 2:14:53 PM 2:15:23 PM 2:16:03 PM January 2015 Page 67
Performance Data - C0330Model C0330A 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 2.4 to 2.6 lb. 80Cycle Time 9-10(minutes) Water Temp 10-11 10-11 11-12 11-12 11-12 12-13Suction Pressure 50 12-13 12-13 13-14(PSIG) 28 13-14 14-15Discharge 70 110Pressure (PSIG) 200 80 150 90 End of Freeze Harvest End of Freeze HarvestModel C0330W 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 2.4 to 2.6 lb. 80Cycle Time 11-12(minutes) Water Temp 12-13 10 10 13-14 11 10-11Suction Pressure 50 14-15 11 11(PSIG) 33 11 12Discharge 70 95Pressure (PSIG) 235 35 80 130 110 235 90 150 End of Freeze Harvest End of Freeze HarvestSuction Pressure Graph C0330A-1A 70/50 PSIG120100 80 60 40 20 010:04:53 10:05:21 10:05:51 10:06:22 10:06:51 10:07:22 10:07:51 10:08:22 10:08:51 10:09:22 10:09:51 10:10:22 10:10:52 10:11:22 10:11:52 10:12:21 10:12:52 10:13:22 10:13:52 January 2015 Page 68
Performance Data - C0530Model C0530A 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 4.5 to 5 lb. 80Cycle Time 13(minutes) Water Temp 14 14 16 15 15 17Suction Pressure 50 16 16 18(PSIG) 33 17 19Discharge 70 95Pressure (PSIG) 230 32 80 130 105 260 90 190 End of Freeze Harvest End of Freeze HarvestModel C0530W 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 4.5 to 5 lb. 80Cycle Time 10(minutes) Water Temp 11 12 12 12 13 13Suction Pressure 50 13 13 13(PSIG) 33 13 14Discharge 70 100Pressure (PSIG) 235 34 80 140 110 235 90 150 End of Freeze Harvest End of Freeze HarvestSuction Pressure Graph C0530A-1A 70/50120100 80 60 40 PSIG 20 014:46:35 14:47:06 14:47:51 14:48:36 14:49:22 14:50:07 14:50:53 14:51:38 14:52:24 14:53:09 14:53:54 14:54:40 14:55:25 14:56:10 14:56:56 14:57:41 14:58:26 14:59:13 January 2015 Page 69
Performance Data - C0630Model C0630A 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 4.5 to 5 lb. 80Cycle Time 9-10(minutes) Water Temp 10-11 10-11 10-11 11-12 11-12 11-12Suction Pressure 50 12-13 12-13 12-13(PSIG) 21 13-14 13-14Discharge 70 85 27Pressure (PSIG) 200 115 80 160 255 200 90 End of Freeze Harvest End of Freeze HarvestModel C0630W 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 4.52 to 5 lb. 80Cycle Time 9(minutes) Water Temp 10 10 10 11 11 11Suction Pressure 50 11 11 12(PSIG) 25 11 13Discharge 70 75Pressure (PSIG) 235 22 80 140 80 235 90 155 End of Freeze Harvest End of Freeze HarvestSuction Pressure Graph C0630A 70/50100 90 80 70 60 50 40 PSIG 30 20 10 08:11:25 8:11:40 8:12:11 8:12:41 8:13:11 8:13:41 8:14:11 8:14:41 8:15:11 8:15:41 8:16:11 8:16:41 8:17:11 8:17:41 8:18:11 8:18:41 8:19:12 8:19:41 8:20:12 8:20:41 January 2015 Page 70
Performance Data - C0830Model C0830A 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 7 -7.3 lb 80Cycle Time 11(minutes) Water Temp 12 12 13 13 13 14Suction Pressure 50 14 14 15(PSIG) 26 15 16Discharge 70 80Pressure (PSIG) 204 30 80 160 100 260 90 195 End of Freeze Harvest End of Freeze HarvestModel C0830W 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 7 - 7.3 lb. 80Cycle Time 11(minutes) Water Temp 12 12-13 13 13 13-14 13Suction Pressure 50 14 13-14 14(PSIG) 30 14 15Discharge 70 85 31Pressure (PSIG) 235 90 80 175 237 178 90 End of Freeze Harvest End of Freeze HarvestSuction Pressure Graph C0830A 70/5090807060504030 PSIG2010 07:50:50 7:51:29 7:52:14 7:52:59 7:53:44 7:54:29 7:55:14 7:56:00 7:56:44 7:57:29 7:58:14 7:59:00 7:59:45 8:00:30 8:01:14 8:02:00 January 2015 Page 71
Performance Data - C1030Model C1030A 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 7 - 7.3 lb 80Cycle Time 9-10(minutes) Water Temp 10-11 10-11 11-12 11-12 11-12 12-13Suction Pressure 50 10-13 12-13 13(PSIG) 26 13-14 14-15Discharge 70 80 30Pressure (PSIG) 210 90 80 165 260 190 90 End of Freeze Harvest End of Freeze HarvestModel C1030W 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 7 -7.3 lb. 80Cycle Time 10(minutes) Water Temp 11 11 11 11-12 11-12 11Suction Pressure 50 12 12 12(PSIG) 26 12-13 13Discharge 70 70 30Pressure (PSIG) 240 75 80 145 240 155 90 End of Freeze Harvest End of Freeze HarvestSuction Pressure Graph PSIG C1030R-32A 70/50 120 100 80 60 40 20 0 January 2015 Page 72
Performance Data - C1448Model C1448A 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 14 lb. 80Cycle Time 12-13(minutes) Water Temp 13-14 13-14 14-15 14-15 14-15 15-16Suction Pressure 50 15-16 15-16 16-17(PSIG) 38 16-17 17-18Discharge 70 100 40Pressure (PSIG) 250 100 80 150 270 160 90 End of Freeze Harvest End of Freeze HarvestModel C1448W 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 14 lb. 80Cycle Time 13-14(minutes) Water Temp 14-15 14-15 15-16 15-16 15-16 15-16Suction Pressure 50 15-16 15-16 16-17(PSIG) 36 15-16 17-18Discharge 70 105 35Pressure (PSIG) 235 100 80 170 235 185 90 End of Freeze Harvest End of Freeze HarvestSuction Pressure Graph C1448R-32 90/70140120100 80 60 40 PSIG 20 014:37:22 14:38:07 14:38:53 14:39:38 14:40:23 14:41:08 14:41:53 14:42:37 14:43:23 14:44:08 14:44:53 14:45:38 14:46:23 14:47:09 14:47:54 14:48:39 14:49:24 14:50:09 14:50:54 14:51:38 January 2015 Page 73
Performance Data - C1848Model C1848A 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 14 lb. 80Cycle Time 10-11(minutes) Water Temp 11-12 11-12 12-13 12-13 12-13 13-14Suction Pressure 50 13-14 13-14 14-15(PSIG) 30 14-15 15-16Discharge 70 90 32Pressure (PSIG) 227 100 80 170 285 195 90 End of Freeze Harvest End of Freeze HarvestModel C1848W 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 14 lb. 80Cycle Time 10-11(minutes) Water Temp 11-12 11-12 11-12 12-13 12-13 11-12Suction Pressure 50 12-13 12-13 12-13(PSIG) 30 12-13 13-14Discharge 70 80 30Pressure (PSIG) 240 85 80 155 240 165 90 End of Freeze Harvest End of Freeze HarvestSuction Pressure Graph PSIG C1848A-32 90/70 120 100 80 60 40 20 09:51:16 9:51:50 9:52:36 9:53:20 9:54:06 9:54:51 9:55:35 9:56:21 9:57:06 9:57:51 9:58:36 9:59:21 10:00:06 10:00:52 10:01:37 10:02:22 10:03:07 10:03:52 January 2015 Page 74
Performance Data - C2148Model C2148R -20 Ambient Air Temp., Degrees F. 120Ice weight / cycle 14.2 lb. 9 70 80 90 18-19Cycle Time peak 410(minutes) Water Temp 10 10 11 9-10 10 12Suction Pressure 50 11-12 11 13(PSIG) 12-13 14 15-16Discharge 70 24 24Pressure (PSIG) 80 95 80 240 250 190 220 90 End of Freeze Harvest End of Freeze HarvestModel C2148W 70 Ambient Air Temp., Degrees F. 90Ice weight / cycle 14.2 lb 80Cycle Time 9-10(minutes) Water Temp 10-11 10-11 11 11-12 11-12 11Suction Pressure 50 11-12 11-12 12(PSIG) 27 11-12 13Discharge 70 75 27Pressure (PSIG) 235 75 80 160 240 160 90 End of Freeze Harvest End of Freeze HarvestSuction Pressure Graph C2148R 70/5090807060504030 PSIG2010 08:56:50 8:57:15 8:57:46 8:58:16 8:58:47 8:59:16 8:59:46 9:00:16 9:00:46 9:01:16 9:01:46 9:02:17 9:02:46 9:03:16 9:03:47 9:04:16 9:04:47 9:05:17 9:05:47 January 2015 Page 75
Performance Data Remote - C0522, C0530Model C0522R -20 Ambient Air Temp., Degrees F. 120Ice weight / cycle 4.4 to 4.6 lb. 10 70 80 90 23Cycle Time peak 360(minutes) Water Temp 12-13 13-14 14 13-14 13-14 14-15Suction Pressure 50 14-15 14-15 15-16(PSIG) 15-16 17-18 18-19Discharge 70 35 24Pressure (PSIG) 85 95 80 230 245 215 225 90 End of Freeze Harvest End of Freeze HarvestModel C0530R -20 Ambient Air Temp., Degrees F. 120Ice weight / cycle 4.4 to 4.6 lb. 10 70 80 90 27Cycle Time Peak 350(minutes) Water Temp 11-13 13-14 13-14 14 14-15 14Suction Pressure 50 15 15-16 15-16(PSIG) 16 17-18 17-18Discharge 70 30 35Pressure (PSIG) 145 100 80 230 245 200 220 90 End of Freeze Harvest End of Freeze Harvest January 2015 Page 76
Performance Data Remote - C0630, C0830, C1030Model C0630R -20 Ambient Air Temp., Degrees F. 120Ice weight / cycle 4.4 to 4.6 lb. 7-8 70 80 90 16-17Cycle Time Peak 370(minutes) Water Temp 9 9 9-10 9-10 9-10 10Suction Pressure 50 10-11 11-12 11(PSIG) 12 14 13-14Discharge 70 30 30Pressure (PSIG) 110 120 80 240 245 200 220 90 End of Freeze Harvest End of Freeze HarvestModel C0830R -20 Ambient Air Temp., Degrees F. 120Ice weight / cycle 7 -7.3 lb 8-9 70 80 90 21-22Cycle Time Peak 360(minutes) Water Temp 9-11 10-11 12 11 11-12 13Suction Pressure 50 12-13 12-13 13-14(PSIG) 13-14 15 16-17Discharge 70 32 32Pressure (PSIG) 100 110 80 240 245 200 210 90 End of Freeze Harvest End of Freeze HarvestModel C1030R -20 Ambient Air Temp., Degrees F. 120Ice weight / cycle 7 -7.3 lb 9 70 80 90 20-21Cycle Time Peak 380(minutes) Water Temp 10-11 11 12-13 11 11-12 12-13Suction Pressure 50 12-13 12-13 14(PSIG) 13-14 15-16 16-17Discharge 70 28 27Pressure (PSIG) 95 100 80 230 240 200 215 90 End of Freeze Harvest End of Freeze Harvest January 2015 Page 77
Performance Data Remote - C1448, C1848Model C1448R -20 Ambient Air Temp., Degrees F. 120Ice weight / cycle 14 lb. 9 70 80 90 22Cycle Time Peak 405(minutes) Water Temp 11 11-12 14-15 11-12 11-12 14-15Suction Pressure 50 13 13 16(PSIG) 14 15-16 18-19Discharge 70 40 40Pressure (PSIG) 100 125 80 240 270 150 200 90 End of Freeze Harvest End of Freeze HarvestModel C1848R -20 Ambient Air Temp., Degrees F. 120Ice weight / cycle 14 lb. 9 70 80 90 19Cycle Time Peak 370(minutes) Water Temp 10-11 11-12 13 11-12 12 13Suction Pressure 50 13 13-14 14-15(PSIG) 14 16 17Discharge 70 32 33Pressure (PSIG) 85 105 80 240 245 170 2005 90 End of Freeze Harvest End of Freeze Harvest January 2015 Page 78
Wiring Diagrams USE COPPER CONDUCTORS ONLY 1 DASHED LINES INDICATE FIELD WIRING WHICH MUST BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL (AIR COOLED ONLY) CAUTION: PTCR WILL BE HOT. CODE AND ALL STATE AND LOCAL CODES. COMPRESSOR MAY NOT START IF17-3053-01 MOT MOT (WHEN 2ND PTCR IS NOT ALLOWED TO COOL 2 WIRE COLOR FOR 208-230/60/1 AND 115/60/1 UNITS: BLACK FAN FAN FAN IS PRESENT) WATER 3 WIRE COLOR FOR 115/60/1 UNITS: WHITE SOLENOID W BN/W WIRE COLOR FOR 208-230/60/1 UNITS: BLACK W/WHITE STRIPE BN W 4 HIGH PRESSURE CONTROL USED ON WC UNITS & AC C0222, C0422, BN/W C0230, C0530, C0630 MOT HOT GAS HARV ASSIST PUMP SOLENOID SOLENOID BN W L1 N BU W LINE OR L2DUMP R/W LOADVALVE O W LINER W TRANSFORMER TRANSFORMER HARVEST ASSIST W 12V SOLENOID 1 W BK BK HOT GAS VALVE WATER VALVEFAN CYCLING PRESSURE V L1 T1 HIGH CONTACTOR CONTROL SWITCH Y CONTACTOR PRESSURE COIL (AIR COOLED ONLY) CONTROL L2 T2 SEE NOTE 4 BN W WATER R RUN ELECTRONIC CONTROL LEVEL BK CAP SENSOR W GN/YICE BKTHICKNESSPROBE J10 12 3 J9 W/R WATER SUMP Y W/Y W/R LEVEL TEMP. SENSOR CURTAIN 1234 J1 DISCHARGE ICE SWITCH 1 TEMP. THICKNESSSUMP TEMP. ELECTRONIC HIGH PRESSURE PTCR PROBE CURTAINSENSOR CONTROL CONTROL GN/Y EARTH GROUND SWITCH 2 SEE NOTE 4 CONTACTOR T1 (2 PLATE UNITS ONLY)DISCHARGE 1234 BK Y R DUMP FANTEMP. J6 VALVE MOTORSENSOR J2 (AC ONLY) WATER 12345678 2 3 PROTECTOR TERMINAL BOX PUMP FAN FAN CYCLING INTERNAL R MOTOR PRESSURE JUNCTION GROUND C1 S2 (WHEN APPLICABLE) SWITCH J7 J8 BOX SCREW (AC ONLY) (A/C ONLY) 12 12 BK 1 EARTH GROUND R3 1 CURTAIN SWITCH SEE NAMEPLATE FOR POWER SUPPLY W PTCR COMPRESSOR CAUTION: PROPER VOLTAGE REQUIREMENTS RUN CAP. AND MAXIMUM FUSE SIZETHIS UNIT MUST MORE THAN ONE DISCONNECT MEANS MAY BEBE GROUNDED. REQUIRED TO DISCONNECT ALL POWER TO THIS UNIT. COMPRESSORC0322, C0522, C0722, C0330, C0530, C0630, C0830, C1030 - Single Phase A - B SeriesC0322, C0522, C0722, C0630, C0830, C1030 - Single Phase D Series January 2015 Page 79
Wiring Diagrams17-3358-01 (AIR COOLED ONLY) (WHEN 2ND USE COPPER CONDUCTORS ONLY 1 DASHED LINES INDICATE FIELD WIRING WHICH MUST BE MOT MOT FAN IS PRESENT) INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL WATER FAN FAN CODE AND ALL STATE AND LOCAL CODES. SOLENOID 2 WIRE COLOR FOR 208-230/60/1 AND 115/60/1 UNITS: BLACK MOT W HOT GAS BN/W HARV ASSIST CAUTION: PTCRWILL BE HOT. PUMP BN SOLENOID W SOLENOID COMPRESSOR MAY NOT START IF 3 WIRE COLOR FOR 115/60/1 UNITS: WHITE PTCR IS NOT ALLOWEDTO COOL WIRE COLOR FOR 208-230/60/1 UNITS: BLACK W/WHITE STRIPE BU BN/W DUMP L1 N VALVE W R/W BN W LINE OR W L2 LOAD TRANSFORMER RW W O LINE 12V HARVEST ASSIST TRANSFORMER SOLENOID 1 BK W HOT GAS VALVE BK WATER VALVEFAN CYCLING PRESSURE V L1 T1 CONTACTOR CONTROL SWITCH CONTACTOR COIL (AIR COOLED ONLY) L2 T2 BN W WATER R BK W RUN ELECTRONIC CONTROL LEVEL BK CAP SENSOR GN/YICETHICKNESS J10 W/RPROBE 12 3 Y W/Y W/R J9 WATER SUMP LEVEL TEMP. SENSOR CURTAIN 1234 ICE SWITCH 1 J1 DISCHARGE THICKNESS TEMP. PROBE CURTAINSUMP TEMP. PTCRSENSOR ELECTRONIC GN/Y EARTH GROUND SWITCH 2 DISCHARGE CONTROL (2 PLATE UNITS ONLY) TEMP. CONTACTOR T1 SENSOR 1234 BK Y DUMP J6 R VALVE FAN J2 MOTOR 23 PROTECTOR TERMINAL BOX (AC ONLY) FAN CYCLING 12345678 INTERNAL R PRESSURE SWITCH J7 J8 JUNCTION GROUND BK C1 S2 WATER FAN (A/C ONLY) 12 12 BOX SCREW R3 PUMP MOTOR (WHEN APPLICABLE) (AC ONLY) 1 EARTH GROUND 1 CURTAIN SWITCH CAUTION: SEE NAMEPLATE FOR POWER SUPPLY W PTCR COMPRESSOR RUN THIS UNIT MUST PROPER VOLTAGE REQUIREMENTS CAP. BE GROUNDED. AND MAXIMUM FUSE SIZEC0330 and C0530 C Series MORETHAN ONE DISCONNECT MEANS MAY BE REQUIREDTO DISCONNECT ALL POWERTOTHIS UNIT. COMPRESSORC0330 and C0530 D Series January 2015 Page 80
Wiring Diagrams17-3070-01 (AIR COOLED ONLY) (WHEN 2ND USE COPPER CONDUCTORS ONLY 1 DASHED LINES INDICATE FIELD WIRING WHICH MUST BE FAN IS PRESENT) INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL MOT MOT CODE AND ALL STATE AND LOCAL CODES. FAN FAN W BN/W CAUTION: PTCR WILL BE HOT. W COMPRESSOR MAY NOT START IF WATER BN HOT GAS HARV ASSIST PTCR IS NOT ALLOWED TO COOL SOLENOID SOLENOID SOLENOID MOT PUMP BN/W DUMP W L1 N L3 VALVE BN LINE OR L2 W LOAD WW R/W O BU LINE TRANSFORMER RW W TRANSFORMER BK 12V HARVEST ASSIST SOLENOID 1FAN CYCLING PRESSURE V HOT GAS VALVE CONTACTOR CONTROL SWITCH COIL (AIR COOLED ONLY) Y WATER VALVE HIGH PRESSURE BK L1 L2 L3 W BN CONTROL HIGH PRESSURE (WATER COOLED ONLY) CONTROL (WC ONLY) T1 T2 T3 WATER R W ELECTRONIC CONTROL LEVEL BK SENSOR BKICETHICKNESS J10 CONTACTORPROBE GN/Y 12 3 J9 Y WATER SUMP LEVEL TEMP. SENSOR CURTAIN 1234 J1 DISCHARGE ICE SWITCH 1 TEMP. THICKNESSSUMP TEMP. PROBE CURTAINSENSOR ELECTRONIC EARTH GROUND SWITCH 2 DISCHARGE CONTROL GN/Y TEMP. (2 PLATE UNITS ONLY) SENSOR 1234 BK BK BK RR R DUMP FAN J6 VALVE MOTOR J2 JUNCTION PROTECTOR TERMINAL BOX (AC ONLY) FAN CYCLING BOX INTERNAL R WATER PRESSURE 12345678 PUMP FAN SWITCH J7 J8 GROUND BK MOTOR (A/C ONLY) 12 12 SCREW (WHEN APPLICABLE) (AC ONLY) C1 S2 R3 CURTAIN SWITCH W CONTACTOR CONTACTOR CONTACTOR COMPRESSOR CAUTION: POWER SUPPLYTHIS UNIT MUST MORE THAN ONE DISCONNECT MEANS MAY BE SEE NAMEPLATE FORBE GROUNDED. REQUIRED TO DISCONNECT ALL POWER TO THIS UNIT. PROPER VOLTAGE REQUIREMENTS AND MAXIMUM FUSE SIZE COMPRESSORC0830, C1030 Three Phase A - B SeriesC0830, C1030 Three Phase D Series January 2015 Page 81
Wiring Diagrams USE COPPER CONDUCTORS ONLY 1 DASHED LINES INDICATE FIELD WIRING WHICH MUST BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL 17-3055-01 CODE AND ALL STATE AND LOCAL CODES.LIQUID WATER MOT HOT GAS BN/W HARV ASSIST 2 WIRE COLOR FOR 208-230/60/1 AND 115/60/1 UNITS: BLACK N LINE SOLENOID PUMP SOLENOID W SOLENOID OR 3 WIRE COLOR FOR 115/60/1 UNITS: WHITE L2SOLENOID W BN/W WIRE COLOR FOR 208-230/60/1 UNITS: BLACK W/WHITE STRIPE L1 CRANKCASE HEATER DUMP W R/W W LOAD LINE HARVEST ASSIST VALVE W SOLENOID 1 BU O TRANSFORMER R W LINE 12V HOT GAS VALVE TRANSFORMER WATER VALVE W HIGH CONTACTOR BK PRESSURE COIL BK CONTROL (WC ONLY) V L1 T1 BN Y CONTACTOR WATER L2 T2 LEVEL SENSOR W ELECTRONIC CONTROLICE R W RUNTHICKNESS BK CAPPROBE BK W/R J10 GN/Y WATER SUMP LEVEL TEMP. GN/Y 12 3 SENSOR J9 CURTAIN Y W/Y W/R DISCHARGE ICE SWITCH 1 TEMP. THICKNESS PROBE CURTAIN 1234 SWITCH 2 J1 (2 PLATE UNITS ONLY) CONTACTOR T1 HIGH PRESSURE PTCR EARTHSUMP TEMP. ELECTRONIC CONTROL BK GROUND DUMPSENSOR CONTROL 2 3 BU BU BK BK VALVE GN/YDISCHARGETEMP. 1234 CRANKCASE HEATER Y R LIQUID LINESENSOR J6 SOLENOID J2 C1 S2 JUNCTION PROTECTOR R3 WATER 12345678 BOX INTERNAL PUMP J7 J8 GROUND TERMINAL BOX 12 12 SCREW R EARTH GROUND BK POWER SUPPLY PTCR SEE NAMEPLATE FORTHIS UNIT MUST CURTAIN SWITCH PROPER VOLTAGE REQUIREMENTS 1 W RUNBE GROUNDED. AND MAXIMUM FUSE SIZE REMOTE COMPRESSOR CAP. CONDENSER MORE THAN ONE DISCONNECT MEANS MAY BE COMPRESSOR FAN REQUIRED TO DISCONNECT ALL POWER TO THIS UNIT. REMOTE CONDENSER FANC0522R, C0530R, C0630R, C0830R, C1030R - Single Phase A - B SeriesC0630R, C0830R, C1030R - Single Phase D Series January 2015 Page 82
Wiring Diagrams USE COPPER CONDUCTORS ONLY 1 DASHED LINES INDICATE FIELD WIRING WHICH MUST BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL 17-3359-01 CODE AND ALL STATE AND LOCAL CODES. 2 WIRE COLOR FOR 208-230/60/1 AND 115/60/1 UNITS: BLACKLIQUID WATER MOT HOT GAS BN/W HARV ASSIST 3 WIRE COLOR FOR 115/60/1 UNITS: WHITE N LINE SOLENOID PUMP BN/W SOLENOID W SOLENOID WIRE COLOR FOR 208-230/60/1 UNITS: BLACK W/WHITE STRIPE ORSOLENOID L2 W L1 CRANKCASE HEATER DUMP W LOAD LINE VALVE W R/W RW BU O LINE TRANSFORMER HARVEST ASSIST TRANSFORMER SOLENOID 1 12V HOT GAS VALVE W WATER VALVE BK CONTACTOR BK COIL BN V L1 T1 ELECTRONIC CONTROL WATER CONTACTOR LEVEL R BK W L2 T2 SENSOR BKICE WTHICKNESS J10 12 3 WATER SUMPPROBE J9 RUN LEVEL TEMP. GN/Y CAP GN/Y SENSOR W/R CURTAIN ICE SWITCH 1 Y W/Y W/R DISCHARGE THICKNESS TEMP. PROBE CURTAIN 1234 SWITCH 2 J1 (2 PLATE UNITS ONLY) CONTACTOR T1SUMP TEMP. PTCR EARTHSENSOR ELECTRONIC BK GROUND DUMPDISCHARGE CONTROL GN/Y BK BK VALVETEMP.SENSOR 1234 2 3 BU BU CRANKCASE HEATER Y R LIQUID LINE J6 SOLENOID J2 C1 S2 WATER JUNCTION PROTECTOR R3 PUMP 12345678 BOX INTERNAL J7 J8 TERMINAL BOX 12 12 GROUND R SCREW EARTH GROUND BK THIS UNIT MUST CURTAIN SWITCH POWER SUPPLY 1 W COMPRESSOR PTCR BE GROUNDED. SEE NAMEPLATE FOR REMOTE COMPRESSOR RUN PROPER VOLTAGE REQUIREMENTS CONDENSER CAP.C0530R - C Series AND MAXIMUM FUSE SIZE MORETHAN ONE DISCONNECT MEANS MAY BE FAN REQUIREDTO DISCONNECT ALL POWERTOTHIS UNIT. REMOTE CONDENSER FANC0530R - D Series January 2015 Page 83
Wiring Diagrams USE COPPER CONDUCTORS ONLY 1 DASHED LINES INDICATE FIELD WIRING WHICH MUST BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL 17-3054-01 CODE AND ALL STATE AND LOCAL CODES.LIQUID WATER MOT HOT GAS BN/W HARV ASSIST L1 L2 L3 LINE SOLENOID PUMP BN/W SOLENOID W SOLENOIDSOLENOID W W CRANKCASE HEATER DUMP W LOAD LINE VALVE R/W HARVEST ASSIST W TRANSFORMER SOLENOID 1 BU O 12V LINE RW W TRANSFORMER BK HOT GAS VALVE WATER VALVE HIGH CONTACTOR PRESSURE COIL CONTROL V (WC ONLY) L1 L2 L3 W BN T1 T2 T3 ELECTRONIC CONTROL WATER R W LEVEL BK SENSOR BK CONTACTORICE BK Y YTHICKNESSPROBE J10 12 3 GN/Y WATER SUMP J9 BK LEVEL TEMP.SUMP TEMP. GN/Y SENSORSENSOR CURTAINDISCHARGE ICE SWITCH 1TEMP. DISCHARGE THICKNESSSENSOR TEMP. PROBE CURTAIN 1234 SWITCH 2 J1 (2 PLATE UNITS ONLY) ELECTRONIC HIGH PRESSURE EARTH BK R DUMP CONTROL CONTROL GROUND VALVE 1234 GN/Y CRANKCASE HEATER R R LIQUID LINE J6 SOLENOID J2 BK BK BK BU BU C1 S2 WATER JUNCTION PROTECTOR R3 PUMP 12345678 BOX INTERNAL J7 J8 TERMINAL BOX 12 12 GROUND R SCREW BK CONTACTOR CONTACTOR CONTACTORTHIS UNIT MUST CURTAIN SWITCH 1 W COMPRESSORBE GROUNDED. REMOTE COMPRESSOR POWER SUPPLY CONDENSER SEE NAMEPLATE FOR MORETHAN ONE DISCONNECT MEANS MAY BE PROPER VOLTAGE REQUIREMENTS FAN REQUIREDTO DISCONNECT ALL POWERTOTHIS UNIT. AND MAXIMUM FUSE SIZE REMOTE CONDENSER FANC0830R, C1030R Three Phase, A-B SeriesC0830R, C1030R Three Phase, D Series January 2015 Page 84
Wiring Diagrams17-3071-01 (AIR COOLED ONLY) (WHEN 2ND USE COPPER CONDUCTORS ONLY 1 DASHED LINES INDICATE FIELD WIRING WHICH MUST BE MOT MOT FAN IS PRESENT) INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL FAN FAN CODE AND ALL STATE AND LOCAL CODES. 2 WIRE COLOR FOR 208-230/60/1 UNITS: BLACK W BN/W HOT GAS BN/W HARV ASSIST BN/W SOLENOID W SOLENOID 3 WIRE COLOR FOR 208-230/60/1 UNITS: BLACK W/WHITE STRIPE BN WATER MOT HOT GAS W HARV ASSIST SOLENOID PUMP BN/W SOLENOID W SOLENOID L1 L2 LINE BN W HARVEST ASSIST DUMP W BU W LOAD SOLENOID 2 VALVE R/W O HOT GAS HARVEST ASSIST LINE VALVE 2 SOLENOID 1 TRANSFORMER TRANSFORMER HOT GAS RW W 12V VALVE 1 BK BK WATER VALVEFAN CYCLING PRESSURE V W L1 T1 HIGH CONTACTOR CONTROL SWITCH Y CONTACTOR PRESSURE COIL (AIR COOLED ONLY) L2 T2 CONTROL (WC ONLY) BN W WATER R W RUN ELECTRONIC CONTROL LEVEL BK CAP SENSOR GN/YICE BKTHICKNESSPROBE J10 12 3 J9 W/R WATER SUMP Y W/Y W/R LEVEL TEMP. SENSOR CURTAIN 1234 DISCHARGE ICE SWITCH 2 J1 TEMP. THICKNESS CONTACTOR T1 PROBE CURTAIN SUMP TEMP. ELECTRONIC HIGH PRESSURE PTCR EARTH GROUND SENSOR CONTROL CONTROL GN/Y SWITCH 1 DISCHARGE (WATER COOLED ONLY) TEMP. SENSOR 1234 BK Y R DUMP FAN J6 VALVE MOTORTHIS UNIT MUST J2 23 PROTECTOR TERMINAL BOX (AC ONLY) FAN CYCLINGBE GROUNDED. INTERNAL R WATER PRESSURE 12345678 PUMP FAN SWITCH J7 J8 JUNCTION GROUND BK MOTOR (A/C ONLY) 12 12 BOX SCREW C1 S2 (AC ONLY) R3 1 EARTH GROUND 1 CURTAIN CURTAIN SEE NAMEPLATE FOR POWER SUPPLY W PTCR SWITCH 1 SWITCH 2 COMPRESSOR RUN CAUTION: PROPER VOLTAGE REQUIREMENTS CAP. AND MAXIMUM FUSE SIZE CAUTION: PTCRWILL BE HOT. COMPRESSOR MAY NOT START IF MORETHAN ONE DISCONNECT MEANS MAY BE PTCR IS NOT ALLOWEDTO COOL REQUIREDTO DISCONNECT ALL POWERTOTHIS UNIT. COMPRESSORC1448, C1848, C2148 Single Phase, A-B SeriesC1448, C1848 Single Phase, D Series January 2015 Page 85
Wiring Diagrams17-3167-01 (AIR COOLED ONLY) (WHEN 2ND USE COPPER CONDUCTORS ONLY 1 DASHED LINES INDICATE FIELD WIRING WHICH MUST BE FAN IS PRESENT) INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL MOT MOT CODE AND ALL STATE AND LOCAL CODES. FAN FAN W BN/W HOT GAS BN/W HARV ASSIST BN/W SOLENOID W SOLENOID BN WATER HOT GAS W HARV ASSIST SOLENOID MOT BN/W SOLENOID SOLENOID W PUMP L1 L2 L3 LINE BN W HARVEST ASSIST DUMP W BU W LOAD SOLENOID 2 VALVE W R/W HOT GAS HARVEST ASSIST R VALVE 2 SOLENOID 1 O TRANSFORMER LINE HOT GAS 12V VALVE 1 TRANSFORMER BK W W WATER VALVEFAN CYCLING PRESSURE V HIGH CONTACTOR CONTROL SWITCH PRESSURE COIL (AIR COOLED ONLY) Y CONTROL HIGH PRESSURE BK L1 L2 L3 W (WC ONLY) BN CONTROL T1 T2 T3 (WATER COOLED ONLY) WATER R W ELECTRONIC CONTROL LEVEL BK SENSOR BKICETHICKNESS J10 CONTACTORPROBE GN/Y 12 3 J9 Y WATER SUMP LEVEL TEMP. SENSOR CURTAIN 1234 DISCHARGE ICE SWITCH 2 J1 TEMP. THICKNESS PROBE CURTAINSUMP TEMP. ELECTRONIC EARTH GROUNDSENSOR CONTROL GN/Y SWITCH 1 DISCHARGE 1234 BK BK BK RR R DUMP FAN TEMP. J6 VALVE MOTOR SENSOR J2 JUNCTION (AC ONLY) BOX WATER 12345678 PROTECTOR TERMINAL BOX PUMP FAN FAN CYCLING GROUND INTERNAL R MOTOR PRESSURE SCREW (AC ONLY) SWITCH J7 J8 BK (A/C ONLY) 12 12 C1 S2 R3 CURTAIN CURTAIN W CONTACTOR CONTACTOR CONTACTOR SWITCH 1 COMPRESSOR SWITCH2 CAUTION: POWER SUPPLYTHIS UNIT MUST CAUTION: PTCR WILL BE HOT.BE GROUNDED. MORE THAN ONE DISCONNECT MEANS MAY BE SEE NAMEPLATE FOR COMPRESSOR MAY NOT START IF REQUIRED TO DISCONNECT ALL POWER TO THIS UNIT. PROPER VOLTAGE REQUIREMENTS PTCR IS NOT ALLOWED TO COOL AND MAXIMUM FUSE SIZE COMPRESSORC1448, C1848, C2148 Three Phase, A-B SeriesC1448 Three Phase, D Series January 2015 Page 86
Wiring Diagrams USE COPPER CONDUCTORS ONLY 1 DASHED LINES INDICATE FIELD WIRING WHICH MUST BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL 17-3072-01 CODE AND ALL STATE AND LOCAL CODES.LIQUID BN/W HOT GAS BN/W HARV ASSIST 2 WIRE COLOR FOR 208-230/60/1 UNITS: BLACK LINE BN/W SOLENOID W SOLENOID 3 WIRE COLOR FOR 115/60/1 UNITS: WHITESOLENOID WATER MOT BN/W HOT GAS W HARV ASSIST WIRE COLOR FOR 208-230/60/1 UNITS: BLACK W/WHITE STRIPE L2 PUMP SOLENOID SOLENOID SOLENOID L1 W CRANKCASE HEATER W W W LOAD LINE HARVEST ASSIST R/W SOLENOID 2 TRANSFORMER HOT GAS DUMP BU O 12V VALVE 2 HARVEST ASSIST VALVE LINE SOLENOID 1 HOT GAS RW W TRANSFORMER VALVE 1 W BK BK WATER VALVE V L1 T1 HIGH CONTACTOR CONTACTOR PRESSURE COIL L2 T2 CONTROL BN (WC ONLY) W WATER LEVEL R W RUN ELECTRONIC CONTROL SENSOR BK CAP GN/YICE BKTHICKNESSPROBE J10 12 3 W/R J9 Y GN/Y BK WATER SUMP Y 2 3 BU BU W/Y W/R LEVEL TEMP. SENSOR HIGH PRESSURE CURTAIN 1234 CONTROL DISCHARGE ICE SWITCH 2 J1 GN/Y TEMP. THICKNESS PROBE CURTAINSUMP TEMP. ELECTRONIC PTCR EARTH CONTACTOR T1SENSOR CONTROL GROUND SWITCH 1 BK BKDISCHARGETEMP. 1234 CRANKCASE HEATER Y R DUMPSENSOR J6 VALVE J2 C1 S2 JUNCTION PROTECTOR R3 WATER LIQUID LINE 12345678 BOX INTERNAL PUMP SOLENOID J7 J8 GROUND TERMINAL BOX 12 12 SCREW R BK EARTH GROUND PTCRTHIS UNIT MUST CURTAIN CURTAIN 1 W RUNBE GROUNDED. SWITCH 1 SWITCH 2 REMOTE COMPRESSOR CAP. CONDENSER MORE THAN ONE DISCONNECT MEANS MAY BE COMPRESSOR FAN REQUIRED TO DISCONNECT ALL POWER TO THIS UNIT. POWER SUPPLY SEE NAMEPLATE FOR REMOTE CONDENSER FAN PROPER VOLTAGE REQUIREMENTS AND MAXIMUM FUSE SIZEC1448R, C1848R, C2148R Single Phase, A - B SeriesC1448R, C1848R, C2148R, Single Phase, D Series January 2015 Page 87
Wiring Diagrams USE COPPER CONDUCTORS ONLY 1 DASHED LINES INDICATE FIELD WIRING WHICH MUST BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL 17-3074-01 CODE AND ALL STATE AND LOCAL CODES.LIQUID BN/W HOT GAS BN/W HARV ASSIST LINE BN/W SOLENOID W SOLENOIDSOLENOID WATER MOT HOT GAS W HARV ASSIST L2 L3 PUMP BN/W SOLENOID L1 SOLENOID W W SOLENOID CRANKCASE HEATER W W LOAD LINE HARVEST ASSIST DUMP SOLENOID 2 VALVE R/W BU O TRANSFORMER HOT GAS RW W LINE VALVE 2 HARVEST ASSIST 12V SOLENOID 1 TRANSFORMER HOT GAS W VALVE 1 BK WATER VALVE V HIGH CONTACTOR PRESSURE COIL CONTROL L1 L2 L3 W (WC ONLY) BN T1 T2 T3 WATER R W ELECTRONIC CONTROL LEVEL BK SENSOR BK CONTACTORICE BK Y YTHICKNESSPROBE J10 GN/YSUMP TEMP. GN/Y 12 3 BKSENSOR J9DISCHARGETEMP. WATER SUMPSENSOR LEVEL TEMP. SENSOR CURTAIN 1234 DISCHARGE ICE SWITCH 2 J1 TEMP. THICKNESS PROBE CURTAIN ELECTRONIC HIGH PRESSURE EARTH BK R CONTROL CONTROL GROUND SWITCH 1 1234 GN/Y CRANKCASE HEATER R R DUMP J6 VALVE J2 BK BK BK BU BU C1 S2 JUNCTION PROTECTOR R3 WATER LIQUID LINE 12345678 BOX INTERNAL PUMP SOLENOID J7 J8 GROUND TERMINAL BOX 12 12 SCREW R BK CONTACTOR CONTACTOR CONTACTORTHIS UNIT MUST CURTAIN CURTAIN POWER SUPPLY 1 W COMPRESSORBE GROUNDED. SWITCH 1 SWITCH 2 SEE NAMEPLATE FOR REMOTE COMPRESSOR PROPER VOLTAGE REQUIREMENTS CONDENSER AND MAXIMUM FUSE SIZE MORETHAN ONE DISCONNECT MEANS MAY BE FAN REQUIREDTO DISCONNECT ALL POWERTOTHIS UNIT. REMOTE CONDENSER FANC1448R, C1848R, C2148R Three Phase, A - B SeriesC1448R, C1848R, C2148R, Three Phase, D Series January 2015 Page 88
Wiring Diagrams USE COPPER CONDUCTORS ONLY 1 DASHED LINES INDICATE FIELD WIRING WHICH MUST BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL 17-3250-01 CODE AND ALL STATE AND LOCAL CODES. BN/W HOT GAS BN/W HARV ASSIST N L3 L2 BN/W SOLENOID W SOLENOIDLIQUID WATER HOT GAS W HARV ASSIST LO1 L1 LINE BN/W SOLENOID LO2 SOLENOID MOT CRANKCASESOLENOID W PUMP SOLENOID HEATER W FUSE (3A) BK .33 HARVEST ASSIST uF SOLENOID 2 W 6 7 9 10 LOAD LINE 12V HOT GAS HARVEST ASSIST W LO4 LO3 VALVE 2 SOLENOID 1 R/W TRANSFORMER 230V LO5 TRANSFORMER DUMP W 5 42 1 LINE HOT GAS VALVE BU O W BK 12V VALVE 1 R BK RW FUSE (3A) WATER VALVE WW HIGH CONTACTOR V A1 A2 PRESSURE COIL CONTROL L1 L2 L3 NO (WC ONLY) BN T1 T2 T3 NO WATER R W BK ELECTRONIC CONTROL LEVEL BK Y SENSOR BK CONTACTORICETHICKNESS J10 BKPROBE GN/Y 12 3 J9 GN/Y WATER SUMP Y LEVEL TEMP. SENSOR CURTAIN 1234 DISCHARGE ICE SWITCH 2 J1 TEMP. THICKNESS PROBE CURTAINSUMP TEMP. ELECTRONIC HIGH PRESSURE EARTH BK RSENSOR CONTROL CONTROL GROUND SWITCH 1DISCHARGE 1234 GN/Y W Y BN BN BU BU CRANKCASE HEATER BK Y DUMPTEMP. J6 VALVESENSOR J2 JUNCTION C1 S2 BOX R3 12345678 PROTECTOR WATER LIQUID LINE GROUND INTERNAL PUMP SOLENOID SCREW J7 J8 TERMINAL BOX 12 12 R BK CONTACTOR CONTACTOR CONTACTOR CONTACTORTHIS UNIT MUST CURTAIN CURTAIN POWER SUPPLY 1 W COMPRESSORBE GROUNDED. SWITCH 1 SWITCH 2 REMOTE COMPRESSOR SEE NAMEPLATE FOR CONDENSER PROPER VOLTAGE REQUIREMENTS MORETHAN ONE DISCONNECT MEANS MAY BE AND MAXIMUM FUSE SIZE FAN REQUIREDTO DISCONNECT ALL POWERTOTHIS UNIT. REMOTE CONDENSER FANC1448R-63 230/380-420/50/3C1448R-63 230/380-420/50/3 D Series January 2015 Page 89
Wiring DiagramsC0630R-6, C0830R-6, C1030R-6C0630R-6, C0830R-6, C1030R-6 D Series January 2015 Page 90
Wiring Diagrams17-3360-01 (AIR COOLED ONLY) (WHEN 2ND USE COPPER CONDUCTORS ONLY 1 DASHED LINES INDICATE FIELD WIRING WHICH MUST BE MOT MOT FAN IS PRESENT) INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL WATER FAN FAN CODE AND ALL STATE AND LOCAL CODES. SOLENOID MOT W HOT GAS BN/W HARV ASSIST CAUTION: PTCRWILL BE HOT. PUMP BN SOLENOID W SOLENOID COMPRESSOR MAY NOT START IF PTCR IS NOT ALLOWEDTO COOL BU BN/W FUSE (3A) L2 BN W DUMP W W BK 10 LOAD L1 .33 VALVE 6 79 12V LINE uF R/W HARVEST ASSIST W TRANSFORMER 230V SOLENOID 1 5 42 1 LINE O TRANSFORMER BK RW W 12V BK BK HOT GAS VALVE FUSEFAN CYCLING PRESSURE V L1 T1 (3A) WATER VALVE CONTROL SWITCH CONTACTOR (AIR COOLED ONLY) L2 T2 CONTACTOR COIL BN W WATER R W RUN ELECTRONIC CONTROL LEVEL BK CAP SENSOR GN/YICE BKTHICKNESSPROBE J10 W/R 12 3 Y W/Y W/R J9 WATER SUMP LEVEL TEMP. SENSOR CURTAIN 1234 ICE SWITCH 1 J1 DISCHARGE THICKNESS TEMP. PROBE CURTAINSUMP TEMP. PTCRSENSOR ELECTRONIC GN/Y EARTH GROUND SWITCH 2 DISCHARGE CONTROL (2 PLATE UNITS ONLY) TEMP. CONTACTOR T1 SENSOR 1234 BK Y DUMP J6 R VALVE FAN J2 BN MOTOR BN PROTECTOR TERMINAL BOX (AC ONLY) FAN CYCLING 12345678 INTERNAL R PRESSURE SWITCH J7 J8 JUNCTION GROUND BK C1 S2 WATER FAN (A/C ONLY) 12 12 BOX SCREW R3 PUMP MOTOR (WHEN APPLICABLE) (AC ONLY) 1 EARTH GROUND 1 CURTAIN SWITCH CAUTION: SEE NAMEPLATE FOR POWER SUPPLY W PTCR PROPER VOLTAGE REQUIREMENTS COMPRESSOR RUN THIS UNIT MUST CAP. BE GROUNDED. AND MAXIMUM FUSE SIZEC0530 50 Hz C Series MORETHAN ONE DISCONNECT MEANS MAY BE REQUIREDTO DISCONNECT ALL POWERTOTHIS UNIT. COMPRESSORC0530 50 Hz D Series January 2015 Page 91
Repair SectionInlet Water Solenoid Valve1 Disconnect electrical power Electrical Shock Hazard Disconnect electrical power before beginning2 Shut off the water supply.3 Remove front and left side panels.4 Unplug wire from coil.5 Disconnect water supply tube from theinlet of the valve.6 Disconnect the water outlet tube.7 Remove the two mounting screws holding the valve to the back panel.8 Pull the valve forward and out of the machine.Fan Blade or Motor1 Push and release the Off button2 Disconnect electrical power.3 Remove front panel, sound shield and left side panel.4 Unplug fan motor wire leads.5 Remove fan motor mounting brackets from shroud. Note: Fastener size is 3/8” hex6 Carefully remove fan motor and blade assembly from machine cabinet.7 Loosen set screw, pull fan blade from motor shaft.8 If the blade is the only part being changed, reverse to reassemble. Note: blade mountspurge to end of motor shaft.9 If the motor will be changed, remove mounting brackets from fan motor. Note: Fastenersize is ¼” hex.10 Reverse to reassemble. January 2015 Page 92
Repair SectionHarvest Assist Solenoid / Mechanism1 Remove front panel.2 Push and release Manual Harvest button3 Disconnect electrical supplyElectrical Shock HazardDisconnect electricalpower before beginning4 Remove sound shield (when used). Original Harvest Assist Solenoid5 Unplug wires from solenoid or mechanism.6 Remove screws and solenoid or mechanism fromcabinet7 Reverse to reassemble.Note: Solenoid replaced by mechanism beginning in2013. Solenoid prior to 2010 may be eligible for recall.See www.scotsman-ice.com for details 2010 and later Harvest Assist Solenoid Harvest Assist Mechanism, use began 2013 January 2015 Page 93
Repair SectionIce thickness sensor1. Push and release the Off switch.2. Remove front and top panels.3. Push and release the Harvest switch4. Remove the evaporator cover.5. Remove the sound shield (when used).6. Disconnect electrical power. Electrical Shock Hazard Disconnect electrical power before beginning7. Open the control box.8. Remove curtain.9. Locate sensor, squeeze mounting legs together to release it from the mounting bracket.10. Remove sensor, follow wire back to control box.11. Disconnect from controller connection J10.12. Remove sensor from machine.13. Reverse to reassemble.14. Set initial probe-to-evaporator-surface gap using a 7/32” drill bit as a gauge. January 2015 Page 94
Repair SectionCapacitor (run)1. Disconnect electrical power.2. Remove front panel.3. Open control box cover.4. Remove right side of control box.5. Remove metal barrier from control box6. Remove screw holding strap to back of the control box.7. Remove wires from capacitor8. Connect wires to new capacitor, refer to wiring diagram as needed.9. Reverse to reassemble.Contactor1. Disconnect electrical power.2. Remove front panel.3. Open control box cover.4. Remove right side of control box.5. Remove metal barrier from control box6. Remove mounting screws holding contactor to control box.7. Exchange wires from old controller to new. Refer to wiring diagram as needed.8. Reverse to reassemble. January 2015 Page 95
Repair SectionController1. Disconnect electrical power. Electrical Shock Hazard Disconnect electrical power before beginning2. Remove front panel.3. Open control box door.4. Unplug all wires from controller.5. Remove screws holding controller to door6. Push controller snaps down and pull controller from mounting bracket.7. Before touching new controller, discharge any static electricity by touching the metal surface of the ice machine cabinet.8. Rotate selector switch to the proper model number for the machine the controller is being installed on.9. Install new controller on mounting bracket, secure with original screws.10. Attach all wires removed.11. Shut control box cover.12. Switch on the electrical power. Controller’s Model Selector Switch January 2015 Page 96
Repair SectionCurtain• Push and hold the Off button to shut the machine off.• Remove front panel.• Remove evaporator cover.• Push inside tab in to release front curtain pin from holder.• Pull curtain from machine.• Reverse to reassemble.Note: Two plate machines must place curtain on correct evaporator. Exception is the articulatedcurtain, which has magnets on both ends.• Push and release the ON button to restart the machine.Curtain switch1. Push and hold the Off button to shut the machine off.2. Disconnect electrical power Electrical Shock Hazard Disconnect electrical power before beginning3. Remove front panel.4. Remove evaporator cover.5. Remove sound shield (when used)6. Open control box.7. Locate curtain switch on evaporator mounting bracket. Pull switch from its snaps or remove 2 screws.8. Dismount wires from sump cover and remove from J7 or J8 connector on control board.9. Reverse to reassemble. Be sure wires are re-mounted to sump cover edge. January 2015 Page 97
Repair SectionPurge valve1. Push and hold the Off button to shut the machine off.2. Disconnect electrical power. Electrical Shock Hazard Disconnect electrical power before beginning3. Remove front panel.4. Remove left side panel.5. Unplug wires from valve coil.Note: The coil can be removed from the valve body by rotating it 1/8turn CW. After removal of the coil the spring and plunger can be takenout.6. Remove screws holding valve to mounting bracket.7. Remove inlet and outlet hoses8. Remove valve from cabinet.9. Reverse to reassemble10. Push and release the On button to restart the machineWater level sensor1. Push and hold the Off button until the machine shuts off.2. Remove the front panel.3. Remove the sound shield.4. Locate water level sensor.5. Squeeze the locking tabs together and pull the sensor up and out of the sump.6. Unplug the electrical connection from the sensor.7. Reverse to reassemble January 2015 Page 98
Repair SectionWater pump1 Push and hold the Off button until the machine shuts off. Electrical Shock Hazard Disconnect electrical power before beginning2 Remove the front panel.3 Remove the sound shield.4 Unplug the water pump5 Rotate the pump CCW about 1/8 turn to release it.6 Lift pump up and remove hose7 Attach hose to new pump8 Install in pump bracket.9 Rotate CW about 1/8 turn to lock it in place.10 Plug pump into harness11 Return panels to their original positions and securewith the original screws.12 Push and release the ON button to restart themachine. January 2015 Page 99
Refrigeration Removal and ReplacementEvaporator1. Remove panels as needed for evaporator access.2. Remove evaporator cover.3. If the machine was in operation, push and release the Harvest button to warm up the evaporator.4. Disconnect electrical power. Electrical Shock Hazard Disconnect electrical power before beginning5. Remove harvest assist6. Recover refrigerant.7. Remove curtain8. Remove water distributor9. Release ice thickness sensor10. Remove water distributor bracket from the top of the evaporator11. Connect nitrogen bottle to discharge access port. Open both access valves.12. Open nitrogen valve13. Unsweat the inlet and outlet refrigerant tubes. Use caution when heating the tubing, do not damage the freezing compartment walls.14. Shut nitrogen valve.15. Gain access to the right side of the unit. Remove mounting screws holding the evaporator to the freezing compartment wall. Note: fastener size is 5/16” hex.16. Remove the evaporator from the ice machine.17. Attach new evaporator to freezing compartment wall, but do not secure tightly at this time.18. Install the harvest assist. Be sure pin moves freely thru ejection hole.19. Open nitrogen valve20. Reconnect inlet and outlet tubes by brazing the copper tubes together.21. Replace filter drier.22. Shut access valves, remove nitrogen bottle.23. Evacuate to at least 300 microns.24. Weigh in the nameplate charge. Check for leaks.25. Return ice thickness sensor bracket, ice thickness sensor, water distributor, curtain and evaporator cover to their original positions.26. Reconnect electrical power.27. Return panels to their original positions. January 2015 Page 100
Search
Read the Text Version
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- 41
- 42
- 43
- 44
- 45
- 46
- 47
- 48
- 49
- 50
- 51
- 52
- 53
- 54
- 55
- 56
- 57
- 58
- 59
- 60
- 61
- 62
- 63
- 64
- 65
- 66
- 67
- 68
- 69
- 70
- 71
- 72
- 73
- 74
- 75
- 76
- 77
- 78
- 79
- 80
- 81
- 82
- 83
- 84
- 85
- 86
- 87
- 88
- 89
- 90
- 91
- 92
- 93
- 94
- 95
- 96
- 97
- 98
- 99
- 100
- 101
- 102
- 103
- 104