Manufacturers of Fire Detection EquipmentGFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentGFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentGFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection Equipment PANELSGFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection Equipment EN54-2 and EN54-4 CERTIFIED 1328-CPR-0160JUNO NETNetworkable Fire Detection SystemJUNO NET is a powerful Analogue Addressable Fire Alarm Control System with networking capabilities that facilitatethe configuration of complex Wide Area Fire Detection Systems. Modular construction and distributed intelligenceallow systems of up to 96 Loops to be constructed. With a high level of built-in redundancy and emergency back-upfeatures, the JUNO NET is fully equipped to control the most complex installations.Using its wide array of interfacing capabilities the JUNO NET is ideally placed to provide an efficient and effectivesolution to the logistics of protecting large institutions. JUNO NET is available as a standalone system of up to 13Loops in a single cabinet and can be expanded to up to 96 Loops via a networked array of sub-panels which can besupplied in a blank box version or combined with a repeater to allow remote display and control of the system.Networking is done by a monitored, redundant, double RS422/RS485,Fibre optic loop or TCP/IP network.The JUNO NET networking capabilities are further enhanced by a wide range of programming options which providethe capability to customise the system according to the needs of the customer. Flexible cause and effectprogramming of I/O devices and warning devices ensure that Fire or Fault warnings trigger the appropriate response.An interactive graphic representation of the system can be displayed on the users' computer via the ODYSSEYgraphical software (optional). All the devices on the system can be displayed on a building plan showing their statusin real time. In the event of fire or fault the customer can control the system and access all the necessary informationwith a few mouse-clicks.Automatic device detection at start up reduces time spent at the commissioning stage. In Installation mode theJUNO NET detects and recognises addressed and connected devices with the system being fully operational in lessthan two minutes. The default programming ensures that the system is ready to detect Fire/Fault alerts from themoment that power is applied.Additional programming, to customise the system can be implemented via the onboard keypad, IR programmer,PS/2 keyboard or with a laptop PC running the GFE Connector software which is available free of charge on theGlobal Fire website.GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentJUNO NETKey Features Fully expandable system from 1-96 Loops with distributed intelligence for added security 125 Device addresses per loop Up to 96 Loop sounders with 32 individually programmable addresses per Loop 96 VULCAN 2 (addressable) ultra low current sounders or beacons per Loop. Only 64 of these units should be installed per loop when combined sounder beacons are being used. This number includes addressable, shadow, auxiliary and detector-sounder/beacon versions of these units Compatible with major analogue addressable communications protocols 2 Fire output changeover relays and 1 Fault output relay (NC) Open collector outputs for Fire, Fault and pre-alarm remote indication 2 Fully monitored conventional sounder outputs on main panel and each sub panel Repeaters with optional integrated Sub-Panels (J-NET-REP + Loop Card) 384 Programmable zones 512 Fully programmable sounder and I/O groups Event Log 2000 entries FIFO Backlit LCD display 4 row x 40 characters Programming options: onboard keypad, Remote IR (optional), PS2 Keyboard and GFE Connector Software PC Graphics package ODYSSEY for alarm management and reporting (optional) Multiple Language support (menu selectable) MODBUS (ASCII & RTU) and BMS support TECHNICAL SPECIFICATIONS 1 - 4 LOOPS 4 - 13 LOOPS LOOPS 1 to 4 loops - Max 275 mA per loop 4 to 13 loops - Max 275 mA per loop 2 at 28 V DC / 500 mA each 4/6/8 24 V DC / 500 mA each SOUNDER OUTPUTS 2 rated 50 VAC / DC 1A resistive 2 rated 50 VAC / DC 1A resistive 1 rated 50 VAC / DC 1A resistive 1 rated 50 VAC / DC 1A resistive AUX. RELAYS FIRE 28 V DC; 2x230 mA 28 V DC; 2x230 mA Multiplexed up to 384 Zones Multiplexed up to 384 Zones AUX. RELAY FAULT 230 +10% -15% V AC 230 +10% -15% V AC 28 V DC Nominal 28 V DC Nominal AUX SUPPLY OUTPUT 65 W (1-3 Loop) - 150 W (4 Loop) 150 W (4-6 Loop) - 200 W (7-13 Loop) 130 mA (1-3 Loop) - 180 mA (4 Loop) 130 mA + 90 mA / sub-panel ADDITIONAL OUTPUTS 2 x 12 V 12 AH 2 x 12 V 12 AH -10ºC to 50ºC -10ºC to 50ºC PRIMARY SUPPLY -10ºC to 50ºC -10ºC to 50ºC Max 95% no condensation Max 95% no condensation SECONDARY SUPPLY IP21 IP21 375 (L) x 345 (W) x 139 (H) mm 420 (L) x 550 (W) x 127 (H) mm POWER SUPPLY RATING 5,1 Kg (no batteries) 8,1 Kg (no batteries) White or Red White or Red QUIESCENT CURRENT (NO DEVICES) 1 LOOP - PSU 2.4A LARGE BOX - 4 LOOPS - PSU 5A BATTERIES (INTERNAL) 2 LOOPS - PSU 2.4A LARGE BOX - 5 LOOPS - PSU 5A 3 LOOPS - PSU 2.4A LARGE BOX - 6 LOOPS - PSU 5A OPERATING TEMPERATURE 4 LOOPS - PSU 5A LARGE BOX - 7 LOOPS - PSU 7.5A LARGE BOX - 8 LOOPS - PSU 7.5A STORAGE TEMPERATURE LARGE BOX - 9 LOOPS - PSU 7.5A LARGE BOX - 10 LOOPS - PSU 7.5A HUMIDITY LARGE BOX - 11 LOOPS - PSU 7.5A LARGE BOX - 12 LOOPS - PSU 7.5A PROTECTION LARGE BOX - 13 LOOPS - PSU 7.5A DIMENSIONS WEIGHT COLOUR ORDER CODE J-NET-EN54-SC-001 1328-CPR-0160 J-NET-EN54-SC-002 1328-CPR-0160 J-NET-EN54-SC-003 1328-CPR-0160 J-NET-EN54-SC-004 J-NET-EN54-SC-004-L J-NET-EN54-SC-005 J-NET-EN54-SC-006 J-NET-EN54-SC-007 J-NET-EN54-SC-008 J-NET-EN54-SC-009 J-NET-EN54-SC-010 J-NET-EN54-SC-011 J-NET-EN54-SC-012 J-NET-EN54-SC-013GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentJ-NET-CON-SP1Juno Net Main Connector Board inc. 1 Loop Expansion Sub-PanelThe introduction of the J-NET-CON-SP1, brings in a new level of flexibility and competitiveness to our customers.By including a single loop sub-panel in the J-NET-CON board, we were able to pack 4 loops into our standard box. Thenew range of self contained JUNO NET panels covers all variants in steps of 1 from 1 to 13 loops. Using this new boardthe JUNO NET panel can be provided in the standard box from 1 to 4 loops and on the larger enclosure from 4 to 13 loops.The J-NET-CON-SP1 is compatible with all models of interface cards used either when interfacing the JUNO NET MainPanel to other Sub-Panels and/or Repeaters or when connecting JUNO NET Systems to GFE’s graphical softwareODYSSEY, BMS or MODBUS. TECHNICAL SPECIFICATIONS 1 loop - Max 275 mA per loop 2 rated at 28 V DC 500 mA each LOOPS 2 - Changeover C-NO-NC rated @ 50 VAC / DC 1A resistive SOUNDER OUTPUTS 1 - Normally Closed rated @ 50 VAC / DC 1A resistive AUX. RELAYS FIRE 2 rated @ 28 V DC 300 mA / output AUX. RELAY FAULT Multiplexed up to 384 Zones AUX POWER OUTPUT 80 mA ADDITIONAL OUTPUTS 120 (L) x163 (W) x 27 (H) mm QUIESCENT CURRENT (NO DEVICES) 240 g DIMENSIONS -10ºC to 50ºC WEIGHT -10ºC to 50ºC OPERATING TEMPERATURE STORAGE TEMPERATURE JUNO NET MAIN CONNECTOR BOARD INC. 1 LOOP EXP. SUB-PANEL ORDER CODE globalfire.pt J-NET-CON-SP1GFE - 02.2018

Manufacturers of Fire Detection EquipmentNODEExpansion boardThe NODE allows expansion of the system in groups of either 1, 2 or 3 loops. When supplied in an enclosed cabinetwith independent primary and secondary power supplies up to 9 Loops may be installed in each cabinet which alsocontains a 2.4 A PSU/ Charger unit and space for standby rechargeable batteries. One RS422/RS485, Fibre Optic orTCP/IP interface is required per cabinet to enable networking with the rest of the system.Each NODE board controls up to 3 Analogue Addressable Detection Loops via its own independent processor. In theevent of communication failure with the main control unit, the sub panel is capable of operating independently,detecting Fire/ Fault events and activating its own sounders and relays. TECHNICAL SPECIFICATIONS NODE STAND ALONE NODE (BOXED) 1, 2 or 3 loops - Max. 275 mA/ Loop 1, 2 or 3 loops - Max. 275 mA/ Loop LOOPS 2 at 28 V DC / 500 mA each 2 at 28 V DC / 500 mA each SOUNDER OUTPUTS / sub-panel 2 rated 50 VAC / DC 1A resistive 2 rated 50 VAC / DC 1A resistive AUX. RELAYS FIRE / sub-panel 1 rated 50 VAC / DC 1A resistive 1 rated 50 VAC / DC 1A resistive AUX. RELAY FAULT / sub-panel 28 V DC 400 mA 28 V DC 400 mA AUX POWER OUTPUT N/A 85-265 V AC, 50/60 Hz PRIMARY SUPPLY 28 V DC Nominal 28 V DC Nominal SECONDARY SUPPLY N/A 64.8 W POWER SUPPLY RATING 80 mA 80 mA QUIESCENT CURRENT (NO DEVICES) N/A 2 x 12 V 12 AH BATTERIES (INTERNAL) 0ºC to 40ºC 0ºC to 40ºC OPERATING TEMPERATURE -10ºC to 50ºC -10ºC to 50ºC STORAGE TEMPERATURE N/A Max 85% No condensation / IP21 HUMIDITY / PROTECTION 113 (L) x 180 (W) x 26 (H) mm 375 (L) x 345 (W) x 139 (H) mm DIMENSIONS 0,3 Kg 4,5 Kg WEIGHT (NO BATTERIES) NODE MOTHERBOARD 1 LOOP - 2.4 A PSU ORDER CODE NODE W/ 1 LOOP 2 LOOP - 2.4 A PSU NODE-MB NODE W/ 2 LOOPS 3 LOOPS - 2.4 A PSU NODE-1L NODE W/ 3 LOOPS 4 LOOPS - 2.4 A PSU NODE-2L 5 LOOPS - 2.4 A PSU NODE-3L globalfire.pt 6 LOOPS - 2.4 A PSU J-NET-SPX-001-NODE 7 LOOPS - 2.4 A PSU J-NET-SPX-002-NODE 8 LOOPS - 2.4 A PSU J-NET-SPX-003-NODE 9 LOOPS - 2.4 A PSU J-NET-SPX-004-NODE J-NET-SPX-005-NODE J-NET-SPX-006-NODE J-NET-SPX-007-NODE J-NET-SPX-008-NODE J-NET-SPX-009-NODEGFE - 02.2018

Manufacturers of Fire Detection EquipmentJ-NET-EN54-REPJuno Net RepeaterThe Juno Net Repeater Panel, J-NET-EN54-REP, fully replicates the control panel information and control facilitiesallowing multiple operating points within the system. The J-NET-EN54-REP communicates with the Master ControlPanel via an RS422/RS485, Fibre Optic or TCP/IP network. Sub-Panels can be integrated into the repeater panel toallow the connection of up to 3 additional detection loops, per sub-panel, to the system.J-NET-EN54-REP is ideal for multiple building complexes where display and control of the system is required invarious locations. Depending on control panel loading, power for the J-NET-EN54-REP can be supplied from thecontrol panel’s auxiliary power output, an external 24 Volt power supply or an optional complete built-in 24 V, 2,4 A or5 A power supply unit. If a sub-panel is installed in the repeater housing, then a 5 A power supply unit is required. TECHNICAL SPECIFICATIONS NO LOOP CARD WITH LOOP CARD LOOPS N/A 1, 2 or 3 loops - Max. 275 mA per loop SOUNDER OUTPUTS 2 at 28 V DC / 500 mA each 2 - 28 V DC / 500 mA each AUX. RELAYS FIRE 2 rated 50 VAC / DC 1 A resistive 2 rated 50 VAC / DC 1A resistive AUX. RELAY FAULT 1 rated 50 VAC / DC 1 A resistive 1 rated 50 VAC / DC 1A resistive AUX SUPPLY OUTPUT 28 V DC, 2x230 mA 28 V DC, 2x230 mA ADDITIONAL OUTPUTS Multiplexed up to 384 Zones Multiplexed up to 384 Zones PRIMARY SUPPLY N/A 230 +10% -15% V AC SECONDARY SUPPLY 28 V DC Nominal 28 V DC Nominal POWER SUPPLY RATING N/A 65 W QUIESCENT CURRENT (NO DEVICES) 110 mA 130 mA no loop devices fitted BATTERIES (INTERNAL) 2 x 12 V 12 AH 2 x 12 V 12 AH OPERATING TEMPERATURE -10ºC to 50ºC -10ºC to 50ºC STORAGE TEMPERATURE -10ºC to 50ºC -10ºC to 50ºC HUMIDITY Max 95% no condensation Max 95% no condensation PROTECTION IP21 IP21 COLOUR White or Red White or Red DIMENSIONS 375 (L) x 345 (W) x 139 (H) mm 375 (L) x 345 (W) x 139 (H) mm WEIGHT (NO BATTERIES) 4,5 Kg (no batteries) 5,1 Kg (no batteries) ORDER CODE JUNO NET EN54 REPEATER J-NET-EN54-REPGFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection Equipment EN54-2 and EN54-4 CERTIFIED 1328-CPR-0179JUNIOR V4Single Loop Analogue AddressableControl Panel Expandable to 2 LoopsThe Global Fire JUNIOR V4 is a single loop Analogue addressable control panel which can be expanded to 2loops. It provides a cost effective solution for small to medium sized installations. The JUNIOR V4 can supportup to 125 addressable devices on each loop which are compatible with major analogue addressablecommunications protocols.Using Global Fire’s advanced communications mechanism, up to 32 individually addressed Loop sounders canbe connected to each of the JUNIOR V4 detection Loops. The JUNIOR V4 also supports Shadow and AuxiliarySounder/ Beacons together with GFE’s new VULCAN 2 addressable Sounder-Beacon-Isolator along with allother GFE Interface devices.The panel is equipped with a backlit LCD display of 4 rows each with 40 characters to give clear textualindications of Fire/ Fault occurrences to the end user. There are also 16 Zone Fire LED indicators.Junior Repeaters and Mini-Repeaters can be connected via an RS422/RS485, Fibre Optic or TCP/IP interface tofacilitate remote display and control of the system.An interactive graphic representation of the system can be displayed on the users' computer via the ODYSSEYgraphical software (optional). All the devices on the system can be displayed on a building plan showing theirstatus in real time. In the event of fire or fault the customer can control the system and access all the necessaryinformation with a few mouse-clicks.Automatic Device Detection at start up reduces time spent at the commissioning stage. In Installation mode theJUNIOR V4 detects and recognises addressed and connected devices with the system being fully operational inless than 2 minutes.The default programming ensures that the system is ready to detect Fire/ Fault alerts from the moment thatpower is applied. Additional programming, to customise the system can be implemented using a laptop PCrunning the GFE Connector software which is available free of charge on GFE’s website.GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentJUNIOR V4Key Features Single loop panel - Expandable to two Loops using JNR-V4-Card Supports connection to Mini-repeaters via RS422/RS485, Fibre Optic or TCP/IP interfaces 125 Device addresses per loop 32 Individually programmable sounder addresses per Loop 96 VULCAN 2 (addressable) ultra low current sounders or beacons per Loop. Only 64 of these units should be installed per loop when combined sounder beacons are being used. This number includes addressable, shadow, auxiliary and detector-sounder/ beacon versions of these units 2 Fire output relays (change-over) and 1 Fault relay (normally closed) 2 Conventional alarm outputs (individually programmable) 384 Fully programmable zones 512 Fully programmable sounder groups together with 512 Input/Output groups Event log (rolling, 2000 entries) Compatible with GFE’s range of Analogue Addressable Devices Backlit LCD display with 4 rows of 40 characters PC Programming using Upload/Download GFE Connector Software PC Graphics package ODYSSEY for alarm management and reporting (optional) Multiple language support (menu selectable) Integrated 16 zone LED fire zone indication TECHNICAL SPECIFICATIONS PRIMARY SUPPLY VOLTAGE - INPUT 230 +10% -15% V AC 28.5 V DC nominal PRIMARY SUPPLY VOLTAGE - OUTPUT 2.4 A @ 28.5 V DC nominal (max.) 21.0 Min. - 27.2 Max.V DC -BAT charger o/p 28 V DC PRIMARY SUPPLY CURRENT - OUTPUT 1.6 Amp Maximum @ 200C 2 x 12 V 7Ah Sealed VRLA Lead Acid Batteries SECONDARY SUPPLY VOLTAGE 275 mA/Loop 2 Fire (COM-NC-NO) - 1 Fault (COM-NC) non-supervised SECONDARY SUPPLY CURRENT OUTPUT 2 - 400 mA Max. current drive per circuit - Fully monitored Max 95% RH Non-Condensing INTERNAL BATTERY CAPACITY - MAXIMUM IP30 -10ºC to 50ºC LOOP CURRENT DRIVE 2.0 Kg - 7 Kg (inc. 2 x 7 AH 12 V bat.) 273 (L) x 107 (W) x 404 (H) mm AUXILIARY RELAY OUTPUTS White or Red CONVENTIONAL SOUNDER CIRCUITS JUNIOR V4, 1 LOOP EXPANDABLE TO 2 LOOPS, PSU 2.4 A JUNIOR V4, 2 LOOPS, PSU 2.4 A HUMIDITY JUNIOR V4 LOOP CARD EXPANSION FROM 1 TO 2 LOOP PROTECTION OPERATING TEMPERATURE WEIGHT DIMENSIONS COLOUR ORDER CODE JNR-V4-1 1328-CPR-0179 JNR-V4-2 1328-CPR-0179 JNR-V4-CARDGFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentJUNIOR REPJunior Repeater PanelThe JUNIOR REP will provide remote control, system status display and monitoring functions for any of GFE’sAnalogue Addressable Fire Detection Panels. All Fire, Fault, Test and Disabled conditions are displayed. User isable to control all functions at access Level’s 1, 2 (authorized user level) and 3 (installer/programming level).Compliant with EN54-2. Display and Control Functions are replicated and shown in the same manner as on any ofGFE’s Analogue Addressable Fire Detection Panel. Access to Levels 2 and 3 is via the same code as programmedfor the associated panel.This unit uses the same plastic enclosure as the JUNIOR V4 panel and is available in 2 colours: white and red.It includes as standard an RS485 interface.This unit is also compatible with all of GFE’s standard data loopinterfaces allowing the JUNIOR REP panel to be interfaced to both JUNIOR and JUNO NET addressable panelsusing RS485, Fibre Optic or TCP/IP.A maximum of 4 JUNIOR REP panels can be connected to a single Addressable Panel if powered directly from theControl Panel’s Auxiliary Supply Output. This number is always dependent on maximum current. TECHNICAL SPECIFICATIONS 28 V DC nominal derived from panel’s Aux. Supply O/P 80 mA SUPPLY VOLTAGE +Supply, -Supply plus interface connections SUPPLY CURRENT RS485, Fibre Optics, TCP/IP CONNECTIONS 4 units max. when powered from aux. supply o/p from panel REPEATER NETWORK Max 95% RH Non-Condensing NOTE -10ºC to 50ºC HUMIDITY 273 (L) x 107 (W) x 404 (H) mm OPERATING TEMPERATURE 1.6 Kg DIMENSIONS White or Red WEIGHT COLOUR JUNIOR REPEATER PANEL - NO LOOPS - INCLUDES 1 X RS485 INTERFACE ORDER CODE globalfire.pt JUNIOR REPGFE - 02.2018

Manufacturers of Fire Detection EquipmentJUNIOR MINI-REPJunior Mini-Repeater PanelThe JUNIOR MINI-REP will provide remote control, system status display and monitoring functions for any ofGFE’s Analogue Addressable Fire Detection Panels. All Fire, Fault, Test and Disabled conditions are displayed. Useris able to control all functions at access Level’s 1, 2 (authorized user level) and 3 (installer/programming level).Compliant with EN54-2. Display and Control Functions are replicated and shown in the same manner as on any ofGFE’s Analogue Addressable Fire Detection Panel. Access to Levels 2 and 3 is via the same code as programmedfor the associated panel. This unit is available in 2 colours: white and red.It includes as standard an RS485 interface. This unit is also compatible with all of GFE’s standard data loopinterfaces allowing the JUNIOR MINI-REP panel to be interfaced to both JUNIOR and JUNO NET addressablepanels using RS485, Fibre Optic or TCP/IP.A maximum of 4 JUNIOR MINI-REP panels can be connected to a single Addressable Panel if powered directly fromthe Control Panel’s Auxiliary Supply Output. This number is always dependent on maximum current. TECHNICAL SPECIFICATIONS 28 V DC nominal derived from panel’s Aux. Supply O/P 80 mA SUPPLY VOLTAGE +Supply, -Supply plus interface connections SUPPLY CURRENT RS485, Fibre Optics, TCP/IP CONNECTIONS 4 units max. when powered from aux. supply o/p from panel REPEATER NETWORK Max 95% RH Non-Condensing -10ºC to 50ºC HUMIDITY 194 (L) x 256 (W) x 75 (H) mm OPERATING TEMPERATURE 1.5 Kg DIMENSIONS White or Red WEIGHT COLOUR JUNIOR MINI REPEATER PANEL - NO LOOPS INCLUDES 1 X RS485 INTERFACE ORDER CODE globalfire.pt JUNIOR-MINI-REPGFE - 02.2018

Manufacturers of Fire Detection EquipmentORION-PLUSExpandable Conventional Fire Detection PanelThe ORION-PLUS range of expandable conventional control panels offers an aesthetically pleasing and functionalcabinet design for larger projects demanding ease of installation and commissioning, as well as simple operation,typical of conventional installations.The unit can be expanded easily from 8 to 16 zones in regular box and 20 to 32 in large box version. Expansion is made byinstalling additional modules with 4 zones. The range also includes two types of repeater.The outstanding programming features included in this panel range exceed the possibilities of standard conventionalpanels, using a graphic LCD display and real time clock which permits the recording of events in a time stamped log.Operation is intuitive, offering simple control and one-button disablement facilities, as well as a one man test routine,which provides a highly effective way to perform regular testing of the fire alarm system.Advanced configuration interfacing includes RS232, RS422/485, Fibre Optic, GSM-GPRS and TCP/IP. All of the abovemaking use of our own proprietary interfaces.These allow for connection to up to 4 remote repeater panels, extinguishing interface modules and multiplexed outputrelays, giving one of the highest levels of system integration possible in conventional systems.GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentORION-PLUSKey Features 8 Zone expandable control panels with a maximum of 16 zones 20 Zone expandable control panels with a maximum of 32 zones (Large Box version) Up to 32 conventional smoke and/or heat detectors per zone Zone expansion via 4 zone expansion module (GFE-EXP-MOD) Active or Resistive End of Line monitoring Programmable non-latching zones Programmable on/off delay timer per zone Programmable coincidence for adjacent zones One man test Supervised auxiliary 24 volt output 2 Supervised/ monitored sounder circuits 3 Programmable remote inputs. 2 Relay outputs 1 fire and 1 fault Fully EN54-2 and EN54-4 compliant Repeater output using RS232, RS485, Fibre Optic and TCP/IP TECHNICAL SPECIFICATIONS 90 to 265 V AC 28.5 V DC nominal SUPPLY SPECIFICATION 1.7 A @ 28.5 V DC nominal (max.) PRIMARY SUPPLY VOLTAGE - IN 21.0 min. - 27.2 max. V DC - BAT charger o/p 28 V DC PRIMARY SUPPLY VOLTAGE - OUT 1.1 Amp Maximum @ 200C PRIMARY SUPPLY CURRENT - OUT 2 x 12 V x 7 Ah Sealed VRLA Lead Acid Batteries SECONDARY SUPPLY VOLTAGE 4 A -250 V Slow Blow - 20 mm SECONDARY SUPPLY CURRENT OUTPUT 1.6 Amp - Resettable INTERNAL BATTERY CAPACITY - MAXIMUM MAINS FUSE 16 Max. BATTERY FUSE 4 mA / 60 mA - Maximum DETECTION CIRCUIT SPECIFICATION 40 Ohms / 0.470 uF NUMBER OF CIRCUITS Active EOL - 10uF/50V Bipolar Electrolytic Aluminium Capacitor ZONE CURRENT - QUIESCENT / ALARM YES (provided diodes are fitted to detector base) MAX. CABLE RESISTANCE / CAPACITANCE 32 Maximum - EN54 pt.2 END OF LINE MONITORING 270 - 1000 Ohms BS-5839 DETECTOR REMOVAL COMPLIANT DEVICES PER ZONE 2 outputs w/ 500 mA max. current drive per circuit - fully monitored ALARM RESISTANCE VALUE 27.5 V DC Nominal / 10 K Ohms - 1/4 Watt SOUNDER CIRCUIT SPECIFICATION CURRENT OUTPUT 1 Fire (COM-NC-NO) - 1 Fault (COM-NC) non-supervised ALARM VOLTAGE / END OF LINE RESISTOR 50 V DC - 1 Amp resistive loads AUXILIARY OUTPUTS SPECIFICATION AUXILIARY RELAY OUTPUT Non-Latching - Voltage free contact RELAY CONTACT RATING Non-Latching - Voltage free contact REMOTE INPUT SPECIFICATION PROGRAMMABLE INPUT 1 Max 95% RH Non-Condensing PROGRAMMABLE INPUT 2 -10ºC to 50ºC MECHANICAL & OPERATING SPEC. 2 Kg without batteries, 7 Kg with batteries (2 x 12 V x 7Ah) HUMIDITY 2 Kg without batteries, 7 Kg with batteries (2 x 12 V x 7Ah) OPERATING TEMPERATURE 273 (L) x 107 (W) x 404 (H) mm WEIGHT (ORION-PLUS) 375 (L) x 345 (W) x 139 (H) mm WEIGHT (ORION-PLUS-L) White or Red DIMENSIONS (ORION-PLUS) DIMENSIONS (ORION-PLUS-L) 8 ZONE EXPANDABLE TO 16 ZONE CONVENTIONAL FACP / REGULAR BOX COLOUR 12 ZONE EXPANDABLE TO 16 ZONE CONVENTIONAL FACP / REGULAR BOX 16 ZONE CONVENTIONAL FACP / REGULAR BOX ORDER CODE 20 ZONE EXPANDABLE TO 32 FACP / LARGE BOX ORION-PLUS 8 24 ZONE EXPANDABLE TO 32 FACP / LARGE BOX ORION-PLUS 12 28 ZONE EXPANDABLE TO 32 FACP / LARGE BOX ORION-PLUS 16 32 ZONE CONVENTIONAL FACP / LARGE BOX ORION-PLUS 20L GFE-EXP-MOD: 4 ZONE ORION-PLUS EXPANSION MODULE ORION-PLUS 24L ORION-PLUS 28L ORION-PLUS 32L GFE-EXP-MODGFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection Equipment EN54-2 and EN54-4 CERTIFIED 1328-CPR-0224ORIONConventional Fire Detection PanelThe ORION conventional control panel range offers a creatively designed and visually pleasing solution forsmaller cost-conscious projects demanding simplicity of operation. Versions available include 2, 4 and 8 zonepanels and two styles of repeater.The outstanding programmable features included in this panel range contradict the facilities commonly availablein this type of panel and include: programmable time delay by zone, Day/Night mode, selectable non-latchingzones and coincidence detection.Operation is extremely intuitive, offering simple control and one-button disablement facilities, as well as the oneman test mode which provides simple and efficient testing of the system.Advanced configuration solutions include the following: a dedicated RS232 communication interface allowingconnection of up to 4 remote repeater panels, addressable loop interface modules and multiplexed zonal outputrelays; giving one of the most highly advanced levels of system integration and compatibility existing on themarket at this level.GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentORIONKey Features 2, 4 and 8 Zone non-expandable control panels Up to 32 conventional smoke and/or heat detectors per Zone Active End of Line monitoring Programmable non-latching Zones Delay timer programmable on/off per Zone Coincidence programmable for adjacent Zones One man test Supervised auxiliary 24 volt output 2 Supervised/ monitored sounder circuits 3 Remote inputs used for activation of Class Change, Day/Night mode, and Reset 2 Relay outputs fire and fault Fully EN54 part 2 and 4 compliant Repeater output Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL) Multiplexed output for sounders per zone (GFE-MPX-SNDR) Addressable Loop Interface card (GFE-ADLI) TECHNICAL SPECIFICATIONS SUPPLY SPECIFICATION PRIMARY SUPPLY VOLTAGE - IN 230 +10% -15% V AC 28.5 V DC nominal PRIMARY SUPPLY VOLTAGE - OUT 1.7 A @ 28.5 V DC nominal (max.) 21.0 min. - 27.2 max. V DC - BAT charger o/p 28 V DC PRIMARY SUPPLY CURRENT - OUT 1.1 Amp Maximum @ 200C 2 x 12V x 7Ah Sealed VRLA Lead Acid Batteries SECONDARY SUPPLY VOLTAGE 4 A -250 V Slow Blow - 20 mm 1.6 Amp - Resettable SECONDARY SUPPLY CURRENT OUTPUT 2,4 or 8 INTERNAL BATTERY CAPACITY - MAXIMUM 4 mA / 60 mA - Maximum 40 Ohms / 0.470 uF MAINS FUSE Active EOL - 10uF/50V Bipolar Electrolytic Aluminium Capacitor YES provided diodes are fitted to detector base BATTERY FUSE 32 Maximum - EN54 pt.2 270 - 1000 Ohms DETECTION CIRCUIT SPECIFICATION 2 outputs w/ 500mA max. current drive per circuit - fully monitored NUMBER OF CIRCUITS 27.5 V DC Nominal / 10 K Ohms - 1/4 Watt ZONE CURRENT - QUIESCENT / ALARM 1 Fire (COM-NC-NO) - 1 Fault (COM-NC) non-supervised 50 V DC - 1 Amp resistive loads MAX. CABLE RESISTANCE / CAPACITANCE Non-Latching - Voltage free contact END OF LINE MONITORING Non-Latching - Voltage free contact BS-5839 DETECTOR REMOVAL COMPLIANT Max 95% RH Non-Condensing IP30 DEVICES PER ZONE -10ºC to 50ºC 1.7 Kg - 7 Kg (inc. 2 x 7 AH 12 V bat.) ALARM RESISTANCE VALUE 273 (L) x 107 (W) x 404 (H) mm White or Red SOUNDER CIRCUIT SPECIFICATION 2 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL CURRENT OUTPUT 4 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL 8 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL ALARM VOLTAGE / END OF LINE RESISTOR AUXILIARY OUTPUTS SPECIFICATION AUXILIARY RELAY OUTPUT RELAY CONTACT RATING REMOTE INPUT SPECIFICATION EVACUATION (CC) - DAY/ NIGHT MODE RESET MECHANICAL & OPERATING SPEC. HUMIDITY PROTECTION OPERATING TEMPERATURE WEIGHT DIMENSIONS COLOUR ORDER CODE ORION 2 1328-CPR-0224 ORION 4 1328-CPR-0224 ORION 8 1328-CPR-0224GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentORION MINI1 & 2 Zone Conventional Fire Detection Panel - Low ProfileThe ORION MINI 1 & 2 zones conventional control panel, offers a creatively designed and aesthetically pleasingsolution for smaller cost-conscious projects demanding simplicity of operation. The programmable featuresincluded in this panel are: programmable time delay and Day/Night mode.Operation is extremely intuitive, offering simple control and one-button disablement facilities, as well as the oneman test mode which provides simple and efficient testing of the system.Key Features Up to 32 conventional smoke and/or heat detectors per Zone Active End of Line monitoring Delay timer programmable ON/OFF and Day/Night mode One man test 1 Supervised/ monitored sounder circuit Fully EN54 -2 and EN54-4 compliant Addressable Loop Interface card-GFE-ADLI (optional) TECHNICAL SPECIFICATIONS 230 +10% -15% V AC 0.5 A @ 28.5 V DC nominal (max.) PRIMARY SUPPLY VOLTAGE- IN 21.0 min. - 27.2 max.V DC - BAT charger o/p 28 V DC PRIMARY SUPPLY VOLTAGE/ CURRENT- OUT 2 x 12 V x 1.2 Ah Sealed VRLA Lead Acid Batteries SECONDARY SUPPLY VOLTAGE 1 A -250 V Slow Blow - 20 mm/ 1.0 Amp - Resettable INTERNAL BATTERY CAPACITY - MAXIMUM 4 mA / 65 mA MAINS FUSE/ BATTERY FUSE 40 Ohms / 0.470 uF ZONE CURRENT - QUIESCENT/ ALARM Active EOL - 10uF/50V Bipolar Electrolytic Aluminium Capacitor MAX. CABLE RESISTANCE/ CAPACITANCE YES provided diodes are fitted to detector base END OF LINE MONITORING 32 Maximum - EN 54-2 BS5839 DETECTOR REMOVAL COMPLIANT 270 - 1000 Ohms DEVICES PER ZONE 1 output w/ 300 mA max. current drive - fully monitored ALARM RESISTANCE VALUE 27.5 V DC Nominal / 10 K Ohms - 1/4 Watt E.O.L. SOUNDER CIRCUIT SPECIFICATION -10ºC to 50ºC / 95% RH Non-Condensing ALARM VOLTAGE/ END OF LINE RESISTOR 1.1 Kg - 2.3 Kg (inc. 2 x 1.2 AH 12 V bat.) OPERATING TEMPERATURE / MAX. HUMIDITY 194 (L) x 256 (W) x 86 (H) mm WEIGHT White or Red DIMENSIONS COLOUR ONE ZONE CONVENTIONAL FIRE DETECTION CONTROL PANEL - LOW PROFILE TWO ZONE CONVENTIONAL FIRE DETECTION CONTROL PANEL - LOW PROFILE ORDER CODE ORION MINI 1 globalfire.pt ORION MINI 2GFE - 02.2018

Manufacturers of Fire Detection EquipmentORION MINI-REPOrion Mini-Repeater PanelThe ORION MINI-REP will provide remote control, system status display and monitoring functions. All Fire,Fault, Test and Disabled conditions are displayed. User is able to control all functions at access Level’s 1 and 2.Compliant with EN54-2. Display and Control Functions are replicated and shown in the same manner as on theORION Fire Detection Panel. Access to Level 2 is via a four digit code (same code as used on the ORIONConventional Panel).It includes as standard an RS232 interface. This unit is also compatible with all of GFE’s standard data loopinterfaces, allowing the ORION MINI-REP panel to be interfaced to an ORION Conventional Panel using 4different interfacing technologies: RS232 RS485 Fibre Optics TCP/IP (specific for ORION Conventional Systems)A maximum of 4 ORION MINI-REP panels can be connected to a single ORION Conventional Fire DetectionPanel. When using data loop interfaces, only one repeater panel will offer both control and display of the system.The remainder of the repeater panels will only offer system status display. This unit is available in both whiteand red colours. TECHNICAL SPECIFICATIONS 28 V DC nominal derived from Orion Aux. Supply O/P 40 mA SUPPLY VOLTAGE +Supply, -Supply, TX and RX SUPPLY CURRENT RS232, RS485, FO or TCP/IP - 1 Display & Control 3 Display Only CONNECTIONS 95% RH Non-Condensing REPEATER NETWORK -10ºC to 50ºC MAX. HUMIDITY 1.4 Kg OPERATING TEMPERATURE 194 (L) x 256 (W) x 75 (H) mm WEIGHT White or Red DIMENSIONS COLOUR CONVENTIONAL MINI-REPEATER PANEL - INCLUDES 1 X RS232 INTERFACE ORDER CODE globalfire.pt ORION MINI-REPGFE - 02.2018

Manufacturers of Fire Detection EquipmentORION EXConventional Fire Detection & Extinguishing PanelThe ORION EX Conventional Fire Detection and Extinguishing Panel offers a creatively designed and aestheticallypleasing solution to satisfy the growing world demand for dependable Fire Suppression Systems.The ORION EX is designed and manufactured to comply with EN54-2, EN54-4 and EN12094-1. The outstandingprogrammable features included in this panel are best suited to be installed in expensive housing areas and ingeneral in all areas where loss of equipment can partially or totally disrupt the proper functioning of a business.Operation is extremely intuitive, offering simple control and one-button disablement facilities, as well as the oneman test mode which provides simple and efficient testing of the system.Advanced configuration solutions include the following: programmable pre-release and extinguishing times,electrovalve and flow switch status indications, manual and abort remote activation. There are 3 normal firedetection zones. All inputs are fully monitored for both Fire, Activation and Fault Conditions.Plans are under way to further complement this new range of extinguishing devices. Devices such as repeaterpanels, addressable system interfaces, I/O expansion boards as well as manual/abort call buttons for remoteconnection are just some of the additions to this range.GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentORION EXKey Features 3 Fire Detection Zones, with Zones 1 and 2 linked with extinguishing cycle Up to 32 conventional smoke and/or heat detectors per Zone Active End of Line monitoring (10uF/50V bipolar capacitor) for Zones Programmable Pre-Release and Extinguishing times Remote Manual Activation and Remote Abort Input Electro valve and Pressure Switch Status Indication One man test Supervised auxiliary 24 volt supply output 2 Supervised/monitored output circuits 2 Remote inputs used for activation of Evacuation and Reset 2 Relay outputs fire and fault with status indication Fully EN 54-2, EN54-4 and EN 12094-1 compliant TECHNICAL SPECIFICATIONS 230 +10% -15% V AC 28.5 V DC nominal SUPPLY SPECIFICATION 1.7 A @ 28.5 V DC nominal (max.) PRIMARY SUPPLY VOLTAGE- IN 21.0 min. - 27.2 max. V DC - BAT charger o/p 28 V DC PRIMARY SUPPLY VOLTAGE- OUT 1.85 Amp Maximum @ 200C PRIMARY SUPPLY CURRENT-OUT 2 x 12V x 7Ah Sealed VRLA Lead Acid Batteries SECONDARY SUPPLY VOLTAGE 4 A -250 V Slow Blow - 20 mm SECONDARY SUPPLY CURRENT OUTPUT 1.85 Amp - Resettable INTERNAL BATTERY CAPACITY - MAXIMUM MAINS FUSE 3 BATTERY FUSE 4 mA / 60 mA - Maximum DETECTION CIRCUIT SPECIFICATION 40 Ohms / 0.470 uF NUMBER OF DETECTION ZONES Active EOL - 10uF/50V Bipolar Electrolytic Aluminium Capacitor ZONE CURRENT - QUIESCENT / ALARM YES provided diodes are fitted to detector base MAX. CABLE RESISTANCE / CAPACITANCE 32 Maximum - EN54 pt.2 END OF LINE MONITORING 270 - 1000 Ohms BS5839 DETECTOR REMOVAL COMPLIANT DEVICES PER ZONE 1000 mA combined maximum current drive for both circuits ALARM RESISTANCE VALUE 27.5 V DC Nominal SOUNDER/OUTPUT CIRCUIT SPECIFICATION 10 K Ohms - 1/4 Watt CURRENT OUTPUT VOLTAGE OUTPUT 1 Fire (COM-NC-NO) - 1 Fault (COM-NC) non-supervised END OF LINE RESISTOR 30 V DC - 2 Amp resistive loads AUXILIARY OUTPUTS SPECIFICATION AUXILIARY RELAY OUTPUT Remote Activation, Remote Abort, Electrovalve Status, Flow/Pressure Switch Status RELAY CONTACT RATING Non-Latching - Voltage free contact REMOTE INPUT SPECIFICATION FULLY MONITORED INPUTS 95% RH Non-Condensing EVACUATION AND RESET IP30 MECHANICAL & OPERATING SPEC. -10ºC to 50ºC MAX. HUMIDITY 1.7 Kg - 7 Kg (inc. 2 x 7 AH 12 V bat.) PROTECTION 273 (L) x 107 (W) x 404 (H) mm OPERATING TEMPERATURE White or Red WEIGHT DIMENSIONS CONVENTIONAL FIRE DETECTION & EXTINGUISHING PANEL COLOUR globalfire.pt ORDER CODE ORION EXGFE - 02.2018

Manufacturers of Fire Detection EquipmentORION EX MINI-REPOrion Mini-Repeater PanelThe ORION EX MINI-REP will provide remote control, system status display and monitoring functions for theORION EX Extinguishing Panel. All Fire, Fault, Test and Disabled conditions are displayed. User is able to controlall functions at access Level’s 1 and 2. Compliant with EN54-2. Display and Control Functions are replicated andshown in the same manner as on the ORION EX Fire Detection and Extinguishing Panel. Access to Level 2 is via afour digit code (same code as used on the ORION EX Panel).It includes as standard an RS232 interface. This unit is also compatible with all of GFE’s standard data loopinterfaces, allowing the ORION MINI-REP panel to be interfaced to an ORION EX Panel using 4 differentinterfacing technologies: RS232 RS485 Fibre Optics TCP/IP (specific for ORION EX systems)A maximum of 4 ORION EX MINI-REP panels can be connected to a single ORION EX Panel. When using data loopinterfaces, only one repeater panel will offer both control and display of the system. The remainder of the repeaterpanels will only offer system status display. This unit is available in both white and red colours. TECHNICAL SPECIFICATIONS 28 V DC nominal derived from Orion Aux. Supply O/P 40 mA SUPPLY VOLTAGE +Supply, -Supply, TX and RX SUPPLY CURRENT RS232, RS485, FO or TCP/IP - 1 Display & Control 3 Display Only CONNECTIONS Max 95% RH Non-Condensing REPEATER NETWORK -10ºC to 50ºC HUMIDITY 1.4 Kg OPERATING TEMPERATURE 194 (L) x 256 (W) x 75 (H) mm WEIGHT White or Red DIMENSIONS COLOUR CONVENTIONAL MINI-REPEATER PANEL FOR ORION EX - INCLUDES 1 X RS232 INTERFACE ORDER CODE globalfire.pt ORION EX MINI-REPGFE - 02.2018

Manufacturers of Fire Detection Equipment DETECTORSGFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentZEOS-ADAnalogue Addressable Fire DetectorsThe ZEOS-AD series of Analogue Addressable Detectors have been designed to be fully compatible with the GlobalFire Equipment range of intelligent control panels, JUNIOR and JUNO NET.The ZEOS detector range, in conjunction with JUNIOR and JUNO NET panels, can accommodate several Alarmthresholds and timed options in combined smoke and heat detectors variants.Certified to EN54-5 and EN54-7 the ZEOS-AD series detectors are available in optical, heat and combined smoke/heatdetector versions. Optionally they can be fitted with a short-circuit loop isolator.Key Features Dual LEDs for 360º visibility Advanced detection and communication protocols Easy installation and maintenance Sleek low-profile housing Durable sensor head, no need for replacement SMD circuit board design. High quality and reliability guaranteed TECHNICAL SPECIFICATIONS SUPPLY VOLTAGE Loop Powered 17-30 V DC 450 uA max. CURRENT - QUIESCENT / SURGE 4 mA - Alarm LED illuminated According to EN54-5 and EN54-7 CURRENT - DEVICE IN ALARM 0.5-2.5 mm² 20 seconds max. SENSITIVITY Low / Normal (default) / High 55 C / 65 C (default) / 75 C / 85 C CABLE SIZE Heat / Smoke / Combined (default) White / ABS RESET/START-UP TIMES 0ºC to 50ºC / -10ºC to 85ºC 95% RH Non-Condensing SMOKE SENSITIVITY SETTINGS 100 (D) x 50 (H) mm inc. base 92 g (without base) & 144 g (inc. base) HEAT ALARM SETPOINTS ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR MULTISENSOR MODES ANALOGUE ADDRESSABLE TEMPERATURE/HEAT DETECTOR ANALOGUE ADDRESSABLE COMBINED SMOKE & HEAT DETECTOR COLOUR / CASE MATERIAL ANALOGUE ADDRESSABLE PHOTOELECTRIC TEMPERATURE/HEAT DETECTOR WITH ISOLATOR ANALOGUE ADDRESSABLE TEMPERATURE/HEAT DETECTOR WITH ISOLATOR NORMAL / TRANSIENT OPERATION TEMPERATURE ANALOGUE ADDRESSABLE COMBINED SMOKE & HEAT DETECTOR WITH ISOLATOR MAX. HUMIDITY DIMENSIONS WEIGHT ORDER CODE ZEOS-AD-S 1328-CPR-0521 ZEOS-AD-H 1328-CPR-0520 ZEOS-AD-SH 1328-CPR-0519 ZEOS-AD-SI 1328-CPR-0607 ZEOS-AD-HI 1328-CPR-0610 ZEOS-AD-SHI 1328-CPR-0492GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentZEOS-ASAnalogue Addressable Fire Detectors with Smart AddressingThe ZEOS-AS series of Analogue Addressable Detectors have been designed to be fully compatible with Global FireEquipment’s range of intelligent control panels, JUNIOR and JUNO NET.The ZEOS detector range, in conjunction with JUNIOR and JUNO NET panels, can accommodate several Alarmthresholds and timed options in combined smoke and heat detectors variants.The ZEOS-AS series is certified to EN54-5 and EN54-7 and consists of combined photoelectric smoke and heatdetectors. Optionally they can be fitted with a short-circuit loop isolator.The ZEOS-AS range of fire detectors is not addressed using a D.I.L. switch, it uses instead GFE’s proprietary SmartAddressing Mechanism (SAM). The address can be set either by using GFE’s analogue device programmer oralternatively, when used in conjunction with GFE’s range of Intelligent Analogue Addressable Fire Detection Panels,GFE’s automatic address setting mode ASET.Key Features Dual LEDs for 360º visibility Advanced detection and communication protocols Easy installation and maintenance Sleek low-profile housing Durable sensor head, no need for replacement SMD circuit board design. High quality and reliability guaranteed TECHNICAL SPECIFICATIONS SUPPLY VOLTAGE Loop Powered 17-30 V DC 450 uA max. CURRENT - QUIESCENT / SURGE 4 mA - Alarm LED illuminated According to EN54-5 or/and EN54-7, EN54-17 CURRENT - DEVICE IN ALARM 0.5-2.5 mm² 20 seconds max. SENSITIVITY Low / Normal (default) / High 55 C / 65 C (default) / 75 C / 85 C CABLE SIZE Heat / Smoke / Combined (default) White / ABS RESET/START-UP TIMES 0ºC to 50ºC / -10ºC to 85ºC 95% RH Non-Condensing SMOKE SENSITIVITY SETTINGS 100 (D) x 50 (H) mm inc. base / 92 g (without base) & 144 g (inc. base) HEAT ALARM SETPOINTS ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR WITH SMART ADDRESSING ANALOGUE ADDRESSABLE TEMPERATURE/HEAT DETECTOR WITH SMART ADDRESSING MULTISENSOR MODES ANALOGUE ADDRESSABLE COMBINED SMOKE & HEAT DETECTOR WITH SMART ADDRESSING ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR W/ ISOLATOR & SMART ADDRESSING COLOUR / CASE MATERIAL ANALOGUE ADDRESSABLE TEMPERATURE/HEAT DETECTOR W/ ISOLATOR & SMART ADDRESSING ANALOGUE ADDR. COMBINED SMOKE & HEAT DETECTOR W/ ISOLATOR & SMART ADDRESSING NORMAL / TRANSIENT OPERATION TEMPERATURE MAX. HUMIDITY DIMENSIONS / WEIGHT ORDER CODE ZEOS-AS-S 1328-CPR-0526 ZEOS-AS-H 1328-CPR-0527 ZEOS-AS-SH 1328-CPR-0525 ZEOS-AS-SI 1328-CPR-0609 ZEOS-AS-HI 1328-CPR-0608 ZEOS-AS-SHI 1328-CPR-0524GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentGFE-C2 wire conventional detectors with remote LED outputThe GFE-C series of conventional detectors have been designed to be fully compatible with the Global FireEquipment’s range of conventional control panels.Certified to EN54-5 and EN54-7, these detectors are available in optical, heat and combined smoke/heat detectorversions.Key Features Dual LEDs for 360º visibility Advanced detection and communication protocols Easy installation and maintenance Sleek low-profile housing Durable sensor head, no need for replacement SMD circuit board design. High quality and reliability guaranteed Sensor Base Option: Regular GFE Detector Base or Deep Base TECHNICAL SPECIFICATIONS GFE-SH-2L GFE-H-2L GFE-S-2L 2 2 2 MODEL 10.8 V to 33 V DC 10.8 V to 33 V DC 10.8 V to 33 V DC 2/4 WIRE 80 µA 40 µA 80 µA SUPPLY VOLTAGE 22/55 mA 20/55 mA 22/55 mA STANDBY CURRENT 160 µA 100 µA 160 µA ALARM CURRENT (12/24V) 57ºC 57ºC - SURGE CURRENT (MAX.) 80 mA 80 mA 80 mA ALARM TEMPERATURE 1-3 Seconds 1-3 Seconds 1-3 Seconds PERMISSIBLE CURRENT (MAX.) EN54-5 & EN54-7 EN54-5 EN54-7 FREQUENCY CERTIFICATION 2 WIRE PHOTOELECTRIC SMOKE AND HEAT DETECTOR WITH REMOTE LED OUTPUT 2 WIRE HEAT DETECTOR WITH REMOTE LED OUTPUT ORDER CODE 2 WIRE PHOTOELECTRIC SMOKE DETECTOR WITH REMOTE LED OUTPUT GFE-SH-2L GFE-H-2L globalfire.pt GFE-S-2LGFE - 02.2018

Manufacturers of Fire Detection EquipmentZEOS BASEStandard Detector BaseZEOS-BASE design and materials guarantees a proper electrical contact with detector head which is key to ensure astable system. Mounting Zeos Base to uneven ceilings has been made easier because of narrow contact points.Deep Detector BaseThis mounting option enables external wiring conduits in locations like car parking's, warehouses, etc. TECHNICAL SPECIFICATIONS Standard: 100 (D) x 10 (H) mm / Deep: 100 (D) x 30 (H) mm White / ABS DIMENSIONS STANDARD DETECTOR BASE COLOUR / CASE MATERIAL DEEP DETECTOR BASE ORDER CODE globalfire.pt ZEOS-BASE ZEOS-DEEP-BASEGFE - 02.2018

Manufacturers of Fire Detection EquipmentGFE-BASEZEOS detector base w/ buzzer or relayAccommodated inside our deep base, GFE-BASE-BUZ has a built-in piezo buzzer and it’s an option for localalarm signalling in places like offices, hotel rooms and class rooms at a lower cost than a VULCAN 2 basesounder. GFE-BASE-REL has a relay which is a very practical solution for ventilation damper activation togetherwith our detector housing.Both options are loop powered making them a viable and low cost solution for localized audible notification andexternal activation. TECHNICAL SPECIFICATIONS Loop powered 21 mA SUPPLY 30 V DC/ 2A CURRENT 75 dB RELAY RATING 100 (D) x 30 (H) mm BUZZER OUTPUT White / ABS DIMENSIONS COLOUR / CASE MATERIAL ZEOS DETECTOR BASE W/ BUZZER ZEOS DETECTOR BASE W/ RELAY ORDER CODE GFE-BASE-BUZ globalfire.pt GFE-BASE-RELGFE - 02.2018

Manufacturers of Fire Detection EquipmentGFE-ZEOS-PROGRAMMERPortable ProgrammerThis equipment enables manual address assignment to all self-programmable devices. It should be used duringmaintenance and installation as an alternative to GFE’s addressable panels ASET mode. Additionally it also allowsinstaller to read address of the device and read its analogue value.A larger battery life is obtained with use of lithium batteries, which can be recharged through available USB port.LED StatusGreen – Programmer is working correctly.Green Flashing – Battery is chargingYellow – Selected function in progress.Red – Internal fault.Red Flashing – Low battery.Keypad Operation Power ON Power OFF OK -> Increase Address OK (2 seconds) -> Decrease Address Program Address UP -> Read Analogue Value DOWN -> Read Address Back OK -> UP & OK -> UP & DOWN -> DOWN -> TECHNICAL SPECIFICATIONS 3.3 V (DC) 100 mA max. OPERATING VOLTAGE 5 V DC (Mini USB) CHARGE CURRENT 2 hours (max.) CHARGE VOLTAGE After 2 minutes CHARGE DURATION +500 operations AUTO POWER OFF 95% RH Non-Condensing AUTONOMY 0ºC to 40ºC MAX. HUMIDITY 86 (D) x 25 (H) mm OPERATING TEMPERATURE 172 g DIMENSIONS WEIGHT PORTABLE PROGRAMMER ORDER CODE globalfire.pt GFE-ZEOS-PROGRAMMERGFE - 02.2018

Manufacturers of Fire Detection EquipmentGFE-REM-IND-AAddressable Flashing Remote IndicatorThe GFE-REM-IND-A is designed to provide discreet remote indication and is controlled by the addressable controlpanel, whilst providing the ability to monitor multiple sensors within a zone thereby minimising wiringrequirements. The GFE-REM-IND-A is compatible with any of GFE’s analogue addressable panels.The unit can be activated either by any of GFE’s analogue addressable fire detectors sharing the same loop addressor alternatively by the panel’s cause and effect programming and in this particular mode of operation, multipledetectors can be used to activate the device.The GFE-REM-IND-A is supplied complete with a back box, enabling the device to be surface mounted. It will also fiton to a standard single gang box. TECHNICAL SPECIFICATIONS Loop Powered - 20 V to 30 V DC 0.12 mA (Quiescent) - 2.5 mA (LED ON) SUPPLY VOLTAGE 0.625 mA (Quiescent) - 2.5 mA (LED ON) LOOP CURRENT - Remote Indicator 2.5 mm² LOOP CURRENT - IO 95% RH Non-Condensing MAX. CABLE SIZE -10ºC to 50ºC MAX. HUMIDITY 86 (L) x 86 (W) x 25 (H) mm OPERATING TEMPERATURE 60 g Boxed DIMENSIONS WEIGHT ADDRESSABLE FLASHING REMOTE INDICATOR ORDER CODE globalfire.pt GFE-REM-IND-AGFE - 02.2018

Manufacturers of Fire Detection EquipmentGFE-REM-IND-CConventional Flashing Remote IndicatorThis remote indicator can be used with any fire alarm detector, be it of the conventional types, to indicate remotelythe activation of the relevant detection device.Its main characteristics are the high visibility due to the flashing of 2 high efficiency LEDs and the wide operatingvoltage range (3.3 V to 10 V DC) with a maximum 7 mA current consumption. The connections of this device arenon-polarised. TECHNICAL SPECIFICATIONS 3.3 V to 10 V DC 7 mA max. SUPPLY VOLTAGE 2.5 mm² SUPPLY CURRENT 95% RH Non-Condensing MAX. CABLE SIZE -10ºC to 50ºC MAX. HUMIDITY 86 (L) x 86 (W) x 25 (H) mm OPERATING TEMPERATURE 50.1 g = module 4,8 g + box 45,3 g DIMENSIONS WEIGHT CONVENTIONAL FLASHING REMOTE INDICATOR ORDER CODE globalfire.pt GFE-REM-IND-CGFE - 02.2018

Manufacturers of Fire Detection EquipmentUG-4Duct Smoke Sampling SystemUG-4 duct housing is a simple and effective solution to monitor smoke presence in ventilation ducts or otherHVAC conducts.Based in Venturi effect, air sampling it's naturally aspirated because of aerodynamic shape of sampling tube. Theventuri tube conducts the air from the duct to the detector housing, which is fitted to the outside of the duct, wherea smoke detector detects potential fire particles in the air.UG-4 should be installed according to air flow direction in the duct but it can be installed on any side of the duct.We recommend that the UG-4 is mounted at an equal distance from heating, cooling or humidity devices. Adistance of 3 times the duct diameter should be left before a damper, filter or change of the duct direction and 5times the diameter after these devices to assure the presence of laminar flow.For detailed information about installation, download manual available in our website. TECHNICAL SPECIFICATIONS ABS / Aluminum 708 g MATERIAL 0.6 m - 377 g / 1,5 m - 950 g / 2,8 m - 1760 g WEIGHT: HOUSING 180 (W) x 235 (H) x 183 (D) mm WEIGHT: VENTURI PIPE 23 (W) x 35 (D) mm ?DIMENSIONS: HOUSING DIMENSIONS: VENTURI PIPE DUCT SMOKE SAMPLING SYSTEM VENTURI PIPE 0.6 METER FOR UG-4 ORDER CODE VENTURI PIPE 1.5 METER FOR UG-4 DUCT HOUSING VENTURI PIPE 2.8 METER FOR UG-4 VR-0.6M VR-1.5M globalfire.pt VR-2.8MGFE - 02.2018

Manufacturers of Fire Detection EquipmentFIRE BEAMReflective Optical Beam Smoke DetectorFIRE BEAM is the optimal solution to protect large areas with ceiling height greater than 4 meters. A motorizedbeam head will self-align itself to the centre of the reflector when commissioning and will automatically keepalignment when building movement occurs which will prevent unwanted false alarms. Additionally, the groundlevel controller facilitates any change or adjustment. Its low current consumption enables seamless integrationwith addressable systems via an Input or ZMU modules. Another relevant feature is related with its environmentalprotection that makes FIRE BEAM a suitable solution for harsh industrial applications, in situations wherecondensation may occur, filters with special coating widens the scope of usage.Key Features Dual LEDs for 360º visibility Low power IP65 environmental protection Ground level commissioning Multi language interface Motorized beam head 1500 m² maximum coverage TECHNICAL SPECIFICATIONS 10.2 to 40V DC 3 mA (quiescent; alarm; fault) ELECTRICAL SUPPLY VOLTAGE Green LED’s Flashing / Controller Message SUPPLY CURRENT Yellow LED’s Flashing / Change over relay (2A@30VDC)/ Controller Message STATUS INDICATORS Red LED’s Flashing / Change over relay (2A@30VDC)/ Controller Message NORMAL FAULT -10°C to +55°C ALARM 10 to 95% RH Non-condensing ENVIRONMENTAL IP65 when suitably mounted and terminated TEMPERATURE HUMIDITY 180 (H) x 155 (W) x 137 (D) mm / Weight 1.1 Kg IP RATING 185 (H) x 120 (W) x 62 (D) mm / Weight 0.55 Kg MECHANICAL 293 (H) x 293 (W) x 5 (D) mm / Weight 0.8 Kg BEAM HEAD 394 (H) x 394 (W) x 5 (D) mm / Weight 1.8 Kg CONTROLLER 270 (H) x 250 (W) x 5 (D) mm / Weight 0.6 Kg (mounts the Beam Head onto unistrut) 40KIT80 MID-RANGE REFLECTOR 80KIT100 LONG RANGE REFLECTOR BASIC FIRE BEAM INCL. CONTROLLER + 1 REFLECTOR COVERS DISTANCE OF 5-40 METERS ADAPTER MID RANGE EXTENSION KIT 40-80 M LONG RANGE EXTENSION KIT 80-100 M ORDER CODE HEAD INTERFACE ADAPTER TO MOUNT TO UNISTRUT FIRE BEAM ANTI FOG FIRE BEAM 40KIT80 ANTI FOG MID RANGE EXTENSION KIT 40-80 M 80KIT100 ANTI FOG LONG RANGE EXTENSION KIT 80-100 M ADAPTER ANTI FOG WINDOW ANTI-FOG FIRE BEAM SINGLE ANTI FOG REFLECTOR 40KIT80-AF ANTI FOG WINDOW FOR HEAD AND SINGLE ANTI FOG REFLECTOR 80KIT100-AF WINDOW-AF REF-AF FOGKITGFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection Equipment Flame Detector Flame Detector Flame Detector GFE-SWR-UV GFE-SWR-UVIR GFE-SWR-IR3 globalfire.pt globalfire.pt globalfire.ptGFE-SWRFlame DetectorsGFE-SWR flame detector range utilizes a microprocessor for sophisticated electronic signal analysis. Its advanceddiscrimination technology and rugged construction makes it suitable for almost all installations scenarios as it'spresented in application table below.GFE-SWR-UV flame detector is suitable for indoor applications, such as fume hoods and hydrogen storages. Becauseof its non-corrosive housing it is suitable for indoor industrial areas where corrosion may occur. UV light is emitted inpractically every fire, both hydrocarbon and non-hydrocarbon fires.GFE-SWR-UVIR flame detector is a combination of UV and IR detections, it uses an additional alarm criterion: theanalysis of the flame flicker frequency. The UV and IR sensor must both exceed their alarm threshold to initiate a firealarm. The GFE-SWR-UVIR flame detector has a good false alarms immunity since the UV and IR sensor do not sharefalse alarm sources.GFE-SWR-IR3 flame detector must exceed its alarm threshold to initiate a fire alarm. The GFE-SWR-IR3 flamedetector also use additional alarm criterion: the analysis of the flame flicker-frequency. This version also exhibitsgood false alarm rejection capabilities. APPLICATION UV UVIR IR3 aaa Aircraft hangars r Atriums r aaa Bio gas setups and stables r aaa Car, bus, tram and train parkings r aaa Chemical storages, fuel and solvent storage indoors aaaa Chemical storages, fuels, paint and solvent storage outdoors r r a Cold Storages aaaar Electric power transformers r aa Diesel engine rooms r aaaa Gas engine rooms aaaaa Fuel service stations and plug-in hybrid charging stations r aaa Fume hoods aaa r Heating Rooms for chemicals aaa r Hydrocarbons storage and processing indoors aaaaa Hydrogen storage and processing indoors aaar Hydrogen storage and processing outdoors r r r Isolators for antennas aaar Laboratories aaaa Monitoring of machinery a aaa Oil and Gas pipe line and pumping stations r aaa Paint spray booths r r aa Radio amplifier rooms aaa r Recycling and waste processing plants r r aa aaaModest suitabity: Good suitability:GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentGFE-SWRKey Features Suitable for heavy and light Hydrocarbons such as Gasoline, Diesel, Methanol and Ethanol Resistant to artificial and sunlight Suitable for indoor and outdoor applications GRP IP65 housing Relay output for Alarm and Fault conditions CPR/EN54-10 certified ATEX zone 2/22 certified FM3260 & 3611 Approvals Rugged sensors make the detector suitable for virtually all fire types Sophisticated software enhances the reliability and availability of the detector Design of the housing and the swivel mount avoid mounting errors with regards to grounding Automatic Sensor Test (Built-in Self-Test) enhances the reliability and availability of the flame detector Pressure Compensating Element avoids additional cost of maintenance caused by moisture build up and increases the life time. TECHNICAL SPECIFICATIONS 12-24 Vdc (10-28 Vdc) 25 mA at 24 Vdc POWER +/- 75 mA at 24 Vdc CURRENT NORMAL <10 sec CURRENT IN ALARM (24 Vdc) Selectable LEDs and relays latching/non latching, factory setting: latching STARTUP TIME De-energized during normal operation, no alarm, SPDT, 30 Vdc – 2 A, 60 W max. ALARM OUTPUT SETTING Energized during normal operation, no fault, SPDT, 30 Vdc – 2 A, 60 W max. RELAY OUTPUTS / ALARM RELAY Standard available 0-20 mA (stepped, sinking, non-isolated) RELAY OUTPUTS / FAULT RELAY < 8 sec. CURRENT OUTPUT 90º minimum ALARM RESPONSE TIME Glass Reinforced Polyester (GRP), Lid screw tightening torque 2 nm minimum CONE OF VISION IP65 HOUSING -40ºC to 70ºC INGRESS PROTECTION ATEX and FM class 3611: -25ºC to 70ºC OPERATING TEMPERATURE Automatic Sensor Test (Built in Self-Test) and manual self-test AMBIENT TEMPERATURE GFE-SWR-UV & GFE-SWR-UVIR: 17 m (n-heptane; 33x33 cm); 25m (alcohol; 50x50 cm) AUTOMATIC AND MANUAL SELF-TEST GFE-SWR-IR3: 35 m (n-heptane; 33x33 cm); 35 m (alcohol; 50x50 cm) DETECTION RANGE 125 x 80 x 57 mm 465 g DIMENSIONS Red & White WEIGHT M20 (cable conduit diameter 5.5-13 mm, two steps 5.5-8 mm and 8-13 mm) COLOR PCE (Pressure Compensating Element) avoids moisture build up in the detector housing, CABLE GLAND caused by pressure differences as a consequence of temperature fluctuations PRESSURE COMPENSATING ELEMENT Suitable for massive cores 0.5 to 1.5 mm² (24 to 16 AWG), tightening torque 0.4 Nm minimum PA66, 316SS nuts and bolts TERMINALS 280 g (OPTIONAL) GFE-SWR-BKT MATERIAL (OPTIONAL) GFE-SWR-BKT WEIGHT ULTRAVIOLET FLAME DETECTOR ULTRAVIOLET/INFRARED FLAME DETECTOR ORDER CODE TRIPLE INFRARED FLAME DETECTOR SWIVEL MOUNTING BRACKET WITH ANGULAR MARKINGS GFE-SWR-UV GFE-SWR-UVIR globalfire.pt GFE-SWR-IR3 GFE-SWR-BKTGFE - 02.2018

Manufacturers of Fire Detection EquipmentGFE-SWR-LMPTest Lamp for GFE-SWR Flame DetectorsThe non Ex GFE-SWR-LMP(TC-169/1) flame detector test lamp activates GFE-SWR series flame detectors namely:GFE-SWR-UVIR(UV/IR-210/1), GFE-SWR-UV(UV-185/5) and GFE-SWR-IR3(IR3-109/1). For all models the testing range is 4meters. The GFE-SWR-LMP(TC-169/1) test lamp is non Ex, suitable for use in safe areas only.TECHNICAL SPECIFICATIONS 100-240 V AC, 500 mA Sealed Lead Acid battery, 12 Vdc / 2.7 AhBATTERY CHARGER 10-15 minutes under optimal conditions and continuous useBATTERY H3, 12 Vdc / 100 WBATTERY AUTONOMY IP30LAMP 4ºC to 40ºCPROTECTION Black / ABSOPERATING TEMPERATURE 440 (L) x 340 (W) x 280 (H) mmCOLOUR / MATERIAL 5 kgDIMENSIONS (BOX)WEIGHT TEST LAMP FOR GFE-SWR FLAME DETECTORS NON-ExORDER CODEGFE-SWR-LMPGFE-SWR-BKTSwivel mounting bracketwith angular markingsThe swivel mount GFE-SWR-BKT(SM21) is a convenient mounting device for GFE-SWR flame detector models. Theswivel mount enables you to thoroughly align the detectors to the fire risks. The swivel mount GFE-SWR-BKT(SM21)is suitable for hazardous areas applications. TECHNICAL SPECIFICATIONS Pa66 / 316 SS 50 (L) x 78 (W) mm MATERIAL 280 g DIMENSIONS WEIGHT SWIVEL MOUNTING BRACKET WITH ANGULAR MARKINGS ORDER CODE globalfire.pt GFE-SWR-BKTGFE - 02.2018

Manufacturers of Fire Detection Equipment MANUAL CALL POINTSGFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentGFE-MCPE-AAddressable Manual Call PointThe GFE-MCPE-A is an Analogue Addressable Manual Call Point, designed and manufactured to comply with EN54-11, compatible with all GFE Addressable Control panels. With its enhanced communications mechanism the typicalresponse time, when in alarm, is approximately one second, depending on the number of call points connected tothe device loop. There is also a version incorporating a Loop Isolator.A bi-colour LED flashes Green when the unit is interrogated by the control panel and is illuminated Red when inAlarm. The command to illuminate the Red LED is emitted by the control panel in response to activation of theindividual call point thus confirming that the Alarm signal has been received at the control panel. The individualaddress, up to 125, of each call point is set via an eight way DIL switch.The unit is supplied complete with a hinged flap which protects the trigger element from accidental activation andreduces malicious activations as two actions are required in order to activate the device. This unit can be bothsurface and flush mounted and it can be easily reset using the supplied key after activation. TECHNICAL SPECIFICATIONS SUPPLY VOLTAGE Loop Powered 20-30 V DC 500 uA - 650 uA for GFE-MCPE-AI CURRENT - QUIESCENT 3.1mA - Yellow LED ON only applies to GFE-MCPE-AI 0.5-2.5 mm² CURRENT - DEVICE IN ALARM 30 GFE-MCPE-A or 6 GFE-MCPE-AI Red / ABS & Clear/ PC - Flame Retardant 94 V0 CABLE SIZE IP24D -10ºC to 55ºC MAX. RECOMMENDED PER LOOP 95% RH Non-Condensing 92.6 (W) x 92.6 (H) x 60.1 (D) mm COLOUR / CASE MATERIAL 152 g PROTECTION ADDRESSABLE MANUAL CALL POINT ADDRESSABLE MANUAL CALL POINT WITH LOOP ISOLATOR OPERATING TEMPERATURE MAX. HUMIDITY DIMENSIONS WEIGHT ORDER CODE GFE-MCPE-A 1328-CPR-0374 GFE-MCPE-AI 1328-CPR-0375GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentGFE-MCPE-CConventional Manual Call PointThe GFE-MCPE-C is a Conventional Manual Call Point, designed and manufactured to comply with EN54-11,compatible with all GFE Conventional Control panels. A bi-colour LED flashes Green when the unit is connected to acontrol panel and is illuminated Red when in Alarm.The unit is supplied complete with a hinged flap which protects the trigger element from accidental activation andreduces malicious activations as two actions are required in order to activate the device. This unit can be bothsurface and flush mounted and it can be easily reset using the supplied key after activation. TECHNICAL SPECIFICATIONS SUPPLY VOLTAGE 20-30 V DC 200 uA CURRENT - QUIESCENT 50 mA @ 24 V DC - Alarm Resistance 470 Ohms Max. 0.5-2.5 mm² CURRENT - DEVICE IN ALARM Red / ABS & Clear/ PC - Flame Retardant 94 V0 IP24D CABLE SIZE -10ºC to 55ºC 95% RH Non-Condensing COLOUR / CASE MATERIAL 92.6 (W) x 92.6 (H) x 60.1 (D) mm 152 g PROTECTION CONVENTIONAL MANUAL CALL POINT OPER. TEMPERATURE BLUE CONVENTIONAL MANUAL CALL POINT GREEN CONVENTIONAL MANUAL CALL POINT MAX. HUMIDITY YELLOW CONVENTIONAL MANUAL CALL POINT WHITE CONVENTIONAL MANUAL CALL POINT DIMENSIONS WEIGHT ORDER CODE GFE-MCPE-C 1328-CPR-0377 GFE-MCPE-C-BLUE 1328-CPR-0377 GFE-MCPE-C-GREEN 1328-CPR-0377 GFE-MCPE-C-YELLOW 1328-CPR-0377 GFE-MCPE-C-WHITE 1328-CPR-0377GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentGFE-MCPE-AI-IP67Addressable Manual Call Point Outdoor Use-IP67The GFE-MCPE-AI-IP67 is an Analogue Addressable Manual Call Point, designed and manufactured to complywith EN54-11, compatible with all GFE Addressable Control panels specially recommended for outdoor use.With its enhanced communications mechanism, the typical response time, when in alarm, is approximately onesecond, depending on the number of call points connected to the device loop. The individual address, up to 125, ofeach call point is set via an eight way DIL switch. Each unit is supplied, as standard, with a loop short circuitisolator. A bi-colour LED flashes Green when the unit is interrogated by the control panel and is illuminated Redwhen in alarm.The GFE-MCPE-AI-IP67 has been designed to deal with today’s difficult and harsh environments. It is a unique firealarm manual call point that mimics the feel of breaking glass whilst offering the user the benefits and safetyadvantages of a glass-free resettable operating element. Once activated a warning flag drops in to view easilyidentifying the call point that has been operated. A key can then reset the unit.The GFE-MCPE-AI-IP67 provides an ideal solution for GFE’s addressable fire alarm systems. Ideal for all outdoorapplications such as oil rigs, ships, factories as well as wash down areas that are sensitive to broken glass. TECHNICAL SPECIFICATIONS SUPPLY VOLTAGE Loop Powered 20-30 V DC 500 uA CURRENT - QUIESCENT 3.5 mA - Alarm LED illuminated 0.5-2.5 mm² CURRENT - DEVICE IN ALARM 30 Red / ABS & Clear/ Polycarbonate - Flame Retardant 94 V0 MAX. CABLE SIZE IP67 -10ºC to 50ºC / 95% RH Non-Condensing MAX. RECOMMENDED PER LOOP 111.9 (H) x 111.9 (W) x 81.3 (D) mm COLOUR / CASE MATERIAL IP67 RATED ADDRESSABLE CALL POINT PROTECTION OPER. TEMPERATURE / MAX. HUMIDITY DIMENSIONS ORDER CODE GFE-MCPE-AI-IP67 1328-CPR-0376GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentGFE-MCPE-C-IP67Conventional Manual Call Point Outdoor Use-IP67The GFE-MCPE-C-IP67 is a Conventional Manual Call Point, designed and manufactured to comply with EN54-11,compatible with all GFE Conventional Control panels specially recommended for outdoor use.The unit is supplied complete with a hinged flap which protects the trigger element from accidental activation andreduces malicious activations as 2 actions are required in order to activate the device.A bi-colour LED flashes Green when the unit is connected to a control panel and is illuminated Red when in Alarm.The GFE-MCPE-C-IP67 has been designed to deal with today’s difficult and harsh environments. It is a unique firealarm manual call point that mimics the feel of breaking glass whilst offering the user the benefits and safetyadvantages of a glass-free resettable operating element. Once activated a warning flag drops in to view easilyidentifying the call point that has been operated. A key can then reset the unit.The GFE-MCPE-C-IP67 provides an ideal solution for most conventional fire alarm systems. Ideal for all outsideapplications such as oil rigs, ships, factories as well as wash down areas that are sensitive to broken glass. TECHNICAL SPECIFICATIONS SUPPLY VOLTAGE 20-30 V DC 200 uA CURRENT - QUIESCENT 50 mA - Alarm LED illuminated 0.5-2.5 mm² CURRENT - DEVICE IN ALARM Red / ABS & Clear - Polycarbonate - Flame Retardant 94 V0 IP67 MAX. CABLE SIZE -10ºC to 50ºC / 95% RH Non-Condensing 111.9 (H) x 111.9 (W) x 81.3 (D) mm COLOUR / CASE MATERIAL IP67 RATED CONVENTIONAL CALL POINT PROTECTION OPER. TEMPERATURE / MAX. HUMIDITY DIMENSIONS ORDER CODE GFE-MCPE-C-IP67 1328-CPR-0373GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection Equipment SOUNDERS & BEACONSGFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection Equipment EN54-3 Type A CERTIFIED 1328-CPR-0286VALKYRIE ASAddressable Wall Mount Sounder/ BeaconThe VALKYRIE AS is a Wall Mounted Addressable Sounder/ Beacon with low power consumption. Up to 32individually addressed sounders can be installed per loop occupying address 94 to 125. The address is set usingswitches 1 to 5 of the 8 way DIL switch. Four different tones are available and selected using DIL switches 6 and 7.When individual address reporting is not required, VALKYRIE AS can be configured as a Shadow Sounder. In this casesounders do not occupy an address in the loop thus freeing up addresses for more detection devices. Shadowsounders do not report back to the control panel so their presence on the loop is not monitored. Shadow soundersdraw current from the loop (10 mA in alarm) and must be included in loop load calculations. TECHNICAL SPECIFICATIONS SUPPLY VOLTAGE Loop: 20 V to 30 V DC 0.5 mA LOOP CURRENT - QUIESCENT 10 mA - 280 mW @ 30 V DC inc. isolator 100 dB (@ 1 meter - 30 V DC) LOOP CURRENT - SOUNDER/ BEACON ACTIVE 2.5 mm² -10ºC to 55ºC MAXIMUM SOUNDER OUTPUT 95% RH Non-Condensing Red or White / ABS and PC MAX. CABLE SIZE IP21C - Type A - Indoor use 110 (D) x 85 (H) mm inc. base OPERATING TEMPERATURE 254 g - inc. mounting base MAX. HUMIDITY ADDRESSABLE WALL SOUNDER ADDRESSABLE WALL SOUNDER/ BEACON COLOUR / CASE MATERIAL ADDRESSABLE WALL SOUNDER WITH ISOLATOR ADDRESSABLE WALL SOUNDER/ BEACON WITH ISOLATOR PROTECTION CATEGORY DIMENSIONS WEIGHT ORDER CODE VALKYRIE AS 1328-CPR-0286 VALKYRIE ASB 1328-CPR-0286 VALKYRIE ASI 1328-CPR-0286 VALKYRIE ASBI 1328-CPR-0286GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection Equipment EN54-3 Type A CERTIFIED 1328-CPR-0287VALKYRIE CSConventional Wall Mount Sounder/ BeaconThe VALKYRIE CS is a wall mounted Conventional Sounder/ Beacon with low power consumption. Four differenttones are available and selected using DIL switches 1 and 2.Both continuous and pulsing outputs are provided via separate negative supply connections allowing for thepresence of differentiated evacuation and alert sounds. TECHNICAL SPECIFICATIONS SUPPLY VOLTAGE 20 V to 30 V DC 10 mA - 280 mW @ 30 V DC CURRENT - SOUNDER/ BEACON ACTIVE 97 dB (@ 1 meter - 30 V DC) 2.5 mm² MAXIMUM SOUNDER OUTPUT -10ºC to 55ºC 95% RH Non-Condensing MAX. CABLE SIZE Red or White / ABS and PC IP21C - Type A - Indoor use OPERATING TEMPERATURE 110 (D) x 85 (H) mm inc. base 254 g - inc. mounting base MAX. HUMIDITY CONVENTIONAL WALL SOUNDER COLOUR / CASE MATERIAL CONVENTIONAL WALL SOUNDER/ BEACON PROTECTION CATEGORY DIMENSIONS WEIGHT ORDER CODE VALKYRIE CS 1328-CPR-0287 VALKYRIE CSB 1328-CPR-0287GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection Equipment EN54-3 Type B CERTIFIED 1328-CPR-0299VALKYRIE AS IP65Addressable Wall Mount Sounder/ Beacon Outdoor Use-IP65The VALKYRIE AS IP65 is a Wall Mounted Addressable Sounder/ Beacon with low power consumption. It isspecifically designed to be used outdoors. Up to 32 individually addressed sounders can be installed per loopoccupying address 94 to 125. The address is set using switches 1 to 5 of the 8 way DIL switch. Four different tonesare available and selected using DIL switches 6 and 7.When individual address reporting is not required, VALKYRIE AS IP65 can be configured as a Shadow Sounder. Inthis case sounders do not occupy an address in the loop thus freeing up addresses for more detection devices.Shadow sounders do not report back to the control panel so their presence on the loop is not monitored. Shadowsounders draw current from the loop (10 mA in alarm) and must be included in loop load calculations. TECHNICAL SPECIFICATIONS SUPPLY VOLTAGE Loop: 20 V to 30 V DC 0.5 mA LOOP CURRENT - QUIESCENT 10 mA - 280 mW @ 30 V DC inc. isolator 108 dB (@ 1 meter - 30 V DC) LOOP CURRENT - SOUNDER/ BEACON ACTIVE 2.5 mm² -25ºC to 70ºC MAXIMUM SOUNDER OUTPUT 95% RH Non-Condensing Red / ABS and PC MAX. CABLE SIZE IP65 - Type B - Outdoor use 112 (D) x 110 (H) mm inc. base OPERATING TEMPERATURE 315 g / 350 g - including packaging MAX. HUMIDITY ADDRESSABLE WALL SOUNDER WITH ISOLATOR - IP65 RATED ADDRESSABLE WALL SOUNDER/ BEACON WITH ISOLATOR - IP65 RATED COLOUR / CASE MATERIAL PROTECTION CATEGORY DIMENSIONS WEIGHT ORDER CODE VALKYRIE ASI IP65 1328-CPR-0299 VALKYRIE ASBI IP65 1328-CPR-0299GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection Equipment EN54-3 Type B CERTIFIED 1328-CPR-0300VALKYRIE CS IP65Conventional Wall Mount Sounder/ Beacon Outdoor Use-IP65The VALKYRIE CS IP65 is a wall mounted Conventional Sounder/ Beacon with low power consumption. It isspecifically designed to be used outdoors. Four different tones are available and selected using DIL switches 1 and 2.Both continuous and pulsing outputs are provided via separate negative supply connections allowing for thepresence of differentiated evacuation and alert sounds. TECHNICAL SPECIFICATIONS SUPPLY VOLTAGE 20 V to 30 V DC 10 mA - 280 mW @ 30 V DC CURRENT - SOUNDER/ BEACON ACTIVE 97 dB (@ 1 meter - 30 V DC) 2.5 mm² MAXIMUM SOUNDER OUTPUT -20ºC to 70ºC 95% RH Non-Condensing MAX. CABLE SIZE Red / ABS and PC IP65 - Type B - Outdoor use OPERATING TEMPERATURE 112 (D) x 110 (H) mm inc. base 315 g / 350 g - including packaging MAX. HUMIDITY CONVENTIONAL WALL SOUNDER - IP65 RATED COLOUR / CASE MATERIAL CONVENTIONAL WALL SOUNDER/ BEACON - IP65 RATED PROTECTION CATEGORY DIMENSIONS WEIGHT ORDER CODE VALKYRIE CS IP65 1328-CPR-0300 VALKYRIE CSB IP65 1328-CPR-0300GFE - 02.2018 globalfire.pt

Manufacturers of Fire Detection EquipmentVALKYRIE VOX AAddressable Voice SounderThe VALKYRIE VOX A is a wall mounted Addressable Voice Sounder which is available in either Red or Whitehousings. The VALKYRIE VOX A voice sounder is based on our successful Horn type sounder and sounder/ beacon.Up to 32 individually addressed sounders can be installed per loop occupying an address in the range 94 to 125, it canbe also configured the shadow mode. The address is set using switches 1 to 5 of the 8 way DIL switch.With message selection directly programmable via the standard sounder programming of the JUNIOR and JUNO NETPanels, the VALKYRIE VOX A, can broadcast up to 5 differentiated pre-loaded messages: Alert, Fire, Evacuation, Testand Silence Message. The desired messages can be downloaded from our own proprietary recording PC application,via a standard USB interface. This product is Loop Controlled and Loop Powered.Key Features Multi-Message. Follows Panel’s Sounder Programming Multi-Language 107 dBA maximum sounder output at 1 m Messages easily programmed via USB interface using dedicated software Synchronization for fast activation TECHNICAL SPECIFICATIONS Loop: 20 V to 30 V DC 0.7 mA (Quiescent) - 7.5 mA Max. (Sounder active or charging) SUPPLY VOLTAGE 1.4 mA LOOP CURRENT Tone 104 dBA - Voice Message 107 dBA LOOP CURRENT - ALARM BEACON 2.5 mm² SOUNDER OUTPUT @ 1 METER Red or White / ABS and PC MAX. CABLE SIZE -10ºC to 55ºC / 95% RH Non-Condensing COLOUR / CASE MATERIAL IP21C - Type A - Indoor use OPERATING TEMPERATURE / MAX. HUMIDITY 110 (D) x 83.6 (H) mm PROTECTION 270 g / 325 g - inc. mounting base DIMENSIONS WEIGHT ADDRESSABLE VOICE SOUNDER ADDRESSABLE VOICE SOUNDER WITH BEACON ORDER CODE VALKYRIE VOX A globalfire.pt VALKYRIE VOX ABGFE - 02.2018

Manufacturers of Fire Detection EquipmentVALKYRIE VOX CConventional Voice SounderThe VALKYRIE VOX C is a wall mounted Conventional Voice Sounder which is available in either Red or Whitehousings. The VALKYRIE VOX C voice sounder is based on our successful Horn type sounder and sounder/ beacon.The VALKYRIE VOX C, can broadcast up to 2 differentiated pre-loaded messages: Fire and Alert. The desiredmessages can be downloaded from our own proprietary recording PC application, via a standard USB interface.Key Features Multi-Message Multi-Language 106 dB maximum sounder output at 1 m Messages easily programmed via USB interface using dedicated software Synchronization for fast activation Compatible with most conventional fire panels TECHNICAL SPECIFICATIONS 20 V to 30 V DC 28 mA (Average) - 65 mA (Peak) @ 24 V DC SUPPLY VOLTAGE Tone 103 dBA - Voice Message 106 dBA LOOP CURRENT - SOUNDER ACTIVE 2.5 mm² SOUNDER OUTPUT @ 1 METER Red or White / ABS and PC MAX. CABLE SIZE -10ºC to 55ºC COLOUR / CASE MATERIAL 95% RH Non-Condensing OPERATING TEMPERATURE IP21C - Type A - Indoor use MAX. HUMIDITY 110 (D) x 83.6 (H) mm PROTECTION 265 g / 315 g - inc. packaging DIMENSIONS WEIGHT CONVENTIONAL VOICE SOUNDER CONVENTIONAL VOICE SOUNDER WITH BEACON ORDER CODE VALKYRIE VOX C globalfire.pt VALKYRIE VOX CBGFE - 02.2018

Manufacturers of Fire Detection EquipmentVALKYRIE VOX A IP65Addressable Voice Sounder/ Beacon Outdoor Use-IP65The VALKYRIE VOX A IP65 is a wall mounted Addressable Voice Sounder which is available in Red housings. It isspecifically designed to be used outdoors. Up to 32 individually addressed sounders can be installed per loopoccupying an address in the range 94 to 125, it can be also configured the shadow mode. The address is set usingswitches 1 to 5 of the 8 way DIL switch.With message selection directly programmable via the standard sounder programming of the JUNIOR and JUNO NETPanels, the VALKYRIE VOX A IP65, can broadcast up to 5 differentiated pre-loaded messages: Alert, Fire, Evacuation,Test and Silence Message. The desired messages can be downloaded from our own proprietary recording PCapplication, via a standard USB interface. This product is Loop Controlled and Loop Powered.Key Features Multi-Message. Follows Panel’s Sounder Programming Multi-Language 107 dBA maximum sounder output at 1 m Messages easily programmed via USB interface using dedicated software Synchronization for fast activation TECHNICAL SPECIFICATIONS Loop: 20 V to 30 V DC 0.7 mA (Quiescent) - 7.5 mA Max. (Sounder active or charging) SUPPLY VOLTAGE 1.4 mA LOOP CURRENT Tone 104 dBA - Voice Message 107 dBA LOOP CURRENT - ALARM BEACON 2.5 mm² SOUNDER OUTPUT @ 1 METER Red or White / ABS and PC MAX. CABLE SIZE -10ºC to 50ºC / 95% RH Non-Condensing COLOUR / CASE MATERIAL IP65 - Type B - Outdoor use OPERATING TEMPERATURE / MAX. HUMIDITY 110 (D) x 83.6 (H) mm PROTECTION 333 g / 400 g - inc. packaging DIMENSIONS WEIGHT ADDRESSABLE VOICE SOUNDER IP65 RATED ADDRESSABLE VOICE SOUNDER WITH BEACON IP65 RATED ORDER CODE VALKYRIE VOX AS IP65 globalfire.pt VALKYRIE VOX ASB IP65GFE - 02.2018

Manufacturers of Fire Detection EquipmentVALKYRIE VOX C IP65Conventional Voice Sounder/ Beacon Outdoor Use-IP65The VALKYRIE VOX C IP65 is a wall mounted Conventional Voice Sounder which is available in Red housings. It isspecifically designed to be used outdoors.The VALKYRIE VOX C IP65, can broadcast up to 2 differentiated pre-loaded messages: Fire and Alert. The desiredmessages can be downloaded from our own proprietary recording PC application, via a standard USB interface.Key Features Multi-Message Multi-Language 106 dB maximum sounder output at 1 m Messages easily programmed via USB interface using dedicated software Synchronization for fast activation Compatible with most conventional fire panels TECHNICAL SPECIFICATIONS 20 V to 30 V DC 28 mA (Average) - 65 mA (Peak) @ 24 V DC SUPPLY VOLTAGE Tone 103 dBA - Voice Message 106 dBA LOOP CURRENT - SOUNDER ACTIVE 2.5 mm² SOUNDER OUTPUT @ 1 METER Red / ABS and PC MAX. CABLE SIZE -10ºC to 50ºC / 95% RH Non-Condensing COLOUR / CASE MATERIAL IP65 - Type B - Outdoor use OPERATING TEMPERATURE / MAX. HUMIDITY 110 (D) x 83.6 (H) mm PROTECTION 323 g / 390 g - inc. packaging DIMENSIONS WEIGHT CONVENTIONAL VOICE SOUNDER IP65 RATED CONVENTIONAL VOICE SOUNDER WITH BEACON IP65 RATED ORDER CODE VALKYRIE VOX CS IP65 globalfire.pt VALKYRIE VOX CSB IP65GFE - 02.2018