MEP CHECKLIST 213087 OFFICE SPACE 1357 River Road Big River US Prepared for A1 Engineers 2468 Main Street Metrotown US Surveyor: Emily Bosch Date surveyed: February 22, 2021 Site Contact: Jeff Williams Phone: 888-250-1357 _____________ ___________________ _____________ RIGHT PEOPLE. 7704 Basswood Drive RIGHT TOOLS. Chattanooga, TN 37416 P: 423 296 9000 RIGHT RESULTS. Page 1 of 34 www.coast2coast.net

Building Information Building Info Split Stand Alone Number of floors in surveyed space?: 1 Building type: Multi -Tenant Building Info Not Multi-Tenant Tenant to the right name: FALSE Left: N/A Traffic and Weather Network Total # of Floors in Building: 4 Floor # target space is located: 4th Notes: No Notes Building Construction N/A Demising wall(s) fire taped to deck?: FALSE No Back wall above ceiling: Drywall Front wall above ceiling: Drywall Above Ceiling Insulated?: No Deck Construction: Other Concrete Deck height(s)?: 11'-9\"-12'-5\" Deck slopes up and down throughout space Notes: No Notes Page 2 of 34

Electrical Information Main Electrical Service Voltage: 480/277 Amps: 800 Phase: 3 Wires: 4 Notes: No Notes Electric Meter Electric Meter location: Local Distance to space: Electrical Communication Room Photo Numbers: 136-137 Meter Number: 63230-508-105 Notes: No Notes Main Disconnect Switch No Main Disconnect Disconnect Manufacturer: Eaton FALSE Model #: BDP5103S004 Type : Breaker Voltage: 600 VAC Amps: 800 Location: Electrical Communications Room Photo Numbers: 133-135 Notes: No Notes Additional Disconnect Switch N/A Switch name from drawing: TRUE Photo Numbers: Disconnect Manufacturer: Model #: Switch controls: Voltage: Phase: Amps: Wires: Conduit size to disconnect: Conduit size to Equipment: Notes: No Notes Page 3 of 34

Electrical Information Transformer No Transformers Transformer Manufacturer: Eaton FALSE Model #: N48M28T22EE KVA: 225 Phase: 3 High Volt: 120 Low Volt: 480 Location and Mount: Electrical Communications room on slab Photo Numbers: 145-147 Notes: No Notes Additional Transformer N/A Transformer Manufacturer: Eaton FALSE Model #: N48M28T75EE KVA: 75 Phase: 3 High Volt: 480 Low Volt: 120 Location and Mount: Generator Equipement Room on floor Photo Numbers: 260-261 Notes: No Notes Time Switches TRUE No Time Switches Time Switch Manufacturer Model #: Switch Controls: Photo Numbers: Amps: Number of Poles: Voltage: Notes: No Notes Time Switch Manufacturer Model #: Switch Controls: Voltage: Amps: Photo Numbers: Notes: No Notes Number of Poles: Page 4 of 34

Electrical Panel Information Panel name or #: X1N241 Photo Numbers: 183-191 Manufacturer: Eaton Catalog Number: PRL1A Voltage: 208Y/120 Amps: 225 Phase: 3 Wires: 4 Main Breaker Amperage: N/A Total number of poles: 42 Number of Poles in use: 8 Notes: Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 20 1 1 Not Labeled N-Light Panel 4th Flr. 2 1 20 30 1 3 Not Labeled 4 1 20 20 1 5 Not Labeled Not Labeled 6 1 20 30 1 7 Not Labeled Not Labeled 8 1 20 30 1 9 Not Labeled Not Labeled 10 1 20 20 1 11 Not Labeled 12 1 20 20 1 13 3rd FL FAP NAC Not Labeled 14 1 20 20 1 15 3rd Floor Fire Alarm Not Labeled 16 1 20 20 1 17 Not Labeled 18 1 1 19 4th FL FAP NAC Open Slot 20 1 1 21 LCP N4E Open Slot 22 1 1 23 Open Slot Open Slot 24 1 1 25 Open Slot Open Slot 26 1 1 27 Open Slot Open Slot 28 1 1 29 Open Slot Open Slot 30 1 1 31 Open Slot Open Slot 32 1 1 33 Open Slot Open Slot 34 1 1 35 Open Slot Open Slot 36 1 1 37 Open Slot Open Slot 38 3 60 1 39 Open Slot Elev Mech Rm Panel 40 3 x 1 41 Open Slot Not Labeled 42 3 x 43 Open Slot Not Labeled 44 45 Open Slot 46 47 48 49 50 51 52 Page 5 of 34

Electrical Panel Information Panel name or #: EU2 Photo Numbers: 220-229 Manufacturer: Eaton Catalog Number: PRL1A Voltage: 208Y/120 Amps: 125 Phase: 3 Wires: 4 Main Breaker Amperage: N/A Total number of poles: 42 Number of Poles in use: 37 Notes: No notes Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 20 1 1 Quad Radio Console 440 Quad Radio Console 462 2 1 20 20 1 3 Quad Radio Console 441 Quad Radio Console 461 4 1 20 20 1 5 Quad Radio Console 442 Quad Radio Console 459 6 1 20 20 1 7 Quad Radio Console 443 Quad Radio Console 458 8 1 20 20 1 9 Quad Radio Console 446 Quad Radio Console 456 10 1 20 20 1 11 Quad Radio Console 447 Quad Radio Console 455 12 1 20 20 1 13 Quad Radio Console 448 14 3 20 20 1 15 Quad Radio Console 458 Gen Use Rec 477 16 3 x 20 1 17 Quad Radio Console 452 Gen Use Rec 477 18 3 x 20 1 19 Quad Radio Console 460 Gen Use Rec 477 20 1 20 20 1 21 Quad Radio Console 444 Gen Use Rec 477 22 2 20 20 1 23 Quad Radio Console 445 Gen Use Rec 474 24 2 x 20 1 25 Quad Radio Console 449 Spare to J-Box 474 26 1 20 20 1 27 Quad Radio Console 450 28 1 20 20 1 29 Quad Radio Console 451 Not Labeled 30 1 20 20 1 31 Quad Radio Console 454 Not Labeled 32 1 20 20 1 33 Not Labeled 34 1 20 20 1 35 Not Labeled Not Labeled 36 1 20 20 1 37 Not Labeled Not Labeled 38 1 20 20 1 39 Not Labeled Not Labeled 40 1 20 20 1 41 Not Labeled Not Labeled 42 1 20 43 Not Labeled Not Labeled 44 45 Not Labeled 46 47 48 49 50 51 52 Page 6 of 34

Electrical Panel Information Panel name or #: EU3 Photo Numbers: 230-238 Manufacturer: Eaton Catalog Number: PRL1A Voltage: 208Y/120 Amps: 125 Phase: 3 Wires: 4 Main Breaker Amperage: N/A Total number of poles: 42 Number of Poles in use: 11 Notes: No notes Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 20 3 1 Studio On-Air Lights Gen Use Rec 464 2 3 20 x33 Studio Track Ltg 458,459,461,462 Gen Use Rec 469 43x x35 Studio Track Ltg451,454,456 Gen Use Rec 469 63x 20 3 7 Studio On-Air Lights Not Labeled 8 1 20 x39 Studio Track Ltg 440,443 Not Labeled 10 1 20 x 3 11 Studio Track Ltg 447,452 Not Labeled 12 1 20 20 1 13 Not Labeled 14 1 20 20 1 15 Not Labeled Not Labeled 16 1 20 20 1 17 Not Labeled Not Labeled 18 1 20 20 1 19 Not Labeled Not Labeled 20 1 20 20 1 21 Not Labeled Not Labeled 22 1 20 20 1 23 Not Labeled Not Labeled 24 1 20 20 1 25 Not Labeled Not Labeled 26 1 20 20 1 27 Not Labeled Not Labeled 28 1 20 20 1 29 Not Labeled Not Labeled 30 1 20 20 1 31 Not Labeled Not Labeled 32 1 20 20 1 33 Not Labeled Not Labeled 34 1 20 20 1 35 Not Labeled Not Labeled 36 1 20 20 1 37 Door Security Not Labeled 38 1 20 20 1 39 Sever Rock Pwr Not Labeled 40 1 20 20 1 41 Not Labeled Not Labeled 42 1 20 43 Not Labeled 44 45 46 47 48 49 50 51 52 Page 7 of 34

Electrical Panel Information Panel name or #: EUD Photo Numbers: 202-210 Manufacturer: Eaton Catalog Number: PRL1A Voltage: 208Y/120 Amps: 300 Phase: 3 Wires: 4 Main Breaker Amperage: UTD Total number of poles: 24 Number of Poles in use: 9 Notes: Main Breaker not labeled with amperage Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 125 3 1 Panel EU1 Panel EU2 2 3 125 x33 Panel EU1 Panel EU2 43x x35 Panel EU1 Panel EU2 63x 125 3 7 Panel EU3 Open slot 81 x39 Panel EU3 Open slot 10 1 x 3 11 Panel EU3 Open slot 12 1 Open slot Open slot 14 1 1 13 Open slot Open slot 16 1 1 15 Open slot Open slot 18 1 1 17 Open slot Open slot 20 1 1 19 Open slot Open slot 22 1 1 21 Open slot Open slot 24 1 1 23 26 28 25 30 27 32 29 34 31 36 33 38 35 40 37 42 39 44 41 46 43 48 45 50 47 52 49 51 Page 8 of 34

Electrical Panel Information Panel name or #: EGP1 Photo Numbers: 262-270 Manufacturer: Eaton Catalog Number: PRL1A Voltage: 208/120V Amps: 200 Phase: 3 Wires: 4 Main Breaker Amperage: 200 Total number of poles: 42 Number of Poles in use: 42 Notes: No notes Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 20 3 1 Gen Use Rec 440,441,442,443 Gen Use Rec 458,459,461,462 2 3 20 x33 Gen Use Rec 443,445,446,447 43x x35 Rec Clock& Beta Bright 63x 20 1 7 Rec Clock & Beta Bright Gen Use Rec 454,455,456 8 3 20 20 1 9 Gen Use Rec 448,449,450,451,453 10 3 x 20 3 11 System Furn 463 12 3 x x 3 13 Gen Use Rec 452 System Furn 463 14 1 20 x 3 15 Rec Reel Lights 474 Spare To J-Box 464 16 2 20 20 3 17 Rec Wiremold 3000 474 FA Preaction Compressor 18 2 x x 3 19 Rec Wiremold 3000 474 System Furn 463 20 2 30 x 3 21 Gen Use Rec 410 System Furn 463 22 2 x 20 1 23 DSC-1 Outdoor DSS-1 Indoor 24 2 30 20 3 25 Rec Roof Service DSC-1 Outdoor DSS-1 Indoor 26 2 x x 3 27 Gen Use Rec 474 DSC-2 Outdoor DSS-2 Indoor 28 2 30 x 3 29 Spare To J-Box Above Preaction FA DSC-2 Outdoor DSS-2 Indoor 30 2 x 20 3 31 Gen Use Rec 477 DSC-3 Outdoor DSS-3 Indoor 32 2 30 x 3 33 Gen Use Rec 477 DSC-3 Outdoor DSS-3 Indoor 34 2 x x 3 35 Security System Panel 477 DSC-4 Outdoor DSS-4 Indoor 36 2 30 20 1 37 Telephone System Panel 477 DSC-4 Outdoor DSS-4 Indoor 38 2 x 20 1 39 Gen Use Rec 477 DSC-5 Outdoor DSS-5 Indoor 40 2 30 20 1 41 Rec Reel Lights 447 DSC-5 Outdoor DSS-5 Indoor 42 2 x 43 Generator Bat. Charger DSC-6 Outdoor DSS-6 Indoor 44 45 Generator Block Heater DSC-6 Outdoor DSS-6 Indoor 46 47 Generator Gen GFCI/Remote Fuel 48 49 50 51 52 Page 9 of 34

Electrical Panel Information Panel name or #: EU1 Photo Numbers: 211-219 Manufacturer: Eaton Catalog Number: PRL1A Voltage: 208Y/120 Amps: 125 Phase: 3 Wires: 4 Main Breaker Amperage: N/A Total number of poles: 42 Number of Poles in use: 37 Notes: No notes Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 20 1 1 1 20 20 1 3 Data/Network Rack Plug Strips Rack 39 Data/Network Rack Plug Strips Rack 20 2 1 20 20 1 5 1 20 20 1 7 Data/Network Rack Plug Strips Rack 38 Data/Network Rack Plug Strips Rack 19 4 1 20 20 1 9 1 20 20 1 11 Data/Network Rack Plug Strips Rack 37 Data/Network Rack Plug Strips Rack 18 6 1 20 20 1 13 1 20 20 1 15 Data/Network Rack Plug Strips Rack 36 Data/Network Rack Plug Strips Rack 11 8 1 20 20 1 17 1 20 20 1 19 Data/Network Rack Plug Strips Rack 35 Data/Network Rack Plug Strips Rack 10 10 1 20 20 1 21 1 20 20 1 23 Data/Network Rack Plug Strips Rack 34 Data/Network Rack Plug Strips Rack 9 12 1 20 20 1 25 1 20 20 1 27 Data/Network Rack Plug Strips Rack 28 Data/Network Rack Plug Strips Rack 8 14 1 20 20 1 29 1 20 20 1 31 Data/Network Rack Plug Strips Rack 27 Data/Network Rack Plug Strips Rack 7 16 1 20 20 1 33 1 20 20 1 35 Data/Network Rack Plug Strips Rack 26 Data/Network Rack Plug Strips Rack 6 18 1 20 20 1 37 1 20 20 1 39 Data/Network Rack Plug Strips Rack 25 Data/Network Rack Plug Strips Rack 5 20 1 20 20 1 41 1 20 43 Data/Network Rack Plug Strips Rack 24 Data/Network Rack Plug Strips Rack 4 22 45 47 Data/Network Rack Plug Strips Rack 23 Data/Network Rack Plug Strips Rack 3 24 49 51 Data/Network Rack Plug Strips Rack 33 Data/Network Rack Plug Strips Rack 2 26 Data/Network Rack Plug Strips Rack 32 Data/Network Rack Plug Strips Rack 1 28 Data/Network Rack Plug Strips Rack 31 Data/Network Rack Plug Strips Rack 15 30 Data/Network Rack Plug Strips Rack 30 Data/Network Rack Plug Strips Rack 14 32 Data/Network Rack Plug Strips Rack 29 Data/Network Rack Plug Strips Rack 13 34 Data/Network Rack Plug Strips Rack 22 Data/Network Rack Plug Strips Rack 12 36 Data/Network Rack Plug Strips Rack 21 Not Labeled 38 Not Labeled Not Labeled 40 Not Labeled Not Labeled 42 44 46 48 50 52 Page 10 of 34

Electrical Panel Information Panel name or #: X1N441 Photo Numbers: 174-182 Manufacturer: Eaton Catalog Number: PRL2A Voltage: 480Y/277 Amps: 225 Phase: 3 Wires: 4 Main Breaker Amperage: N/A Total number of poles: 42 Number of Poles in use: 4 Notes: No notes Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 20 1 1 Level 3 Shell Space Not Labeled 2 1 20 20 1 3 Not Labeled 4 1 20 20 1 5 Level 3 Egress Not Labeled 6 1 20 20 1 7 Level 4 Shell Space Open Slot 81 19 Open Slot 10 1 1 11 Level 4 Egress Not Labeled 12 1 20 1 13 Open Slot Not Labeled 14 1 20 1 15 Open Slot Not Labeled 16 1 20 1 17 Open Slot Open Slot 18 1 1 19 Open Slot Open Slot 20 1 1 21 Open Slot Open Slot 22 1 1 23 Open Slot Open Slot 24 1 1 25 Open Slot Open Slot 26 1 1 27 Open Slot Open Slot 28 1 1 29 Open Slot Open Slot 30 1 1 31 Open Slot Open Slot 32 1 1 33 Open Slot Open Slot 34 1 1 35 Open Slot Open Slot 36 1 1 37 Open Slot Open Slot 38 1 1 39 Open Slot MTRS 40 1 50 1 41 Open Slot MTRS 42 1 X 43 Open Slot 44 45 Open Slot 46 47 48 49 50 51 52 Page 11 of 34

Electrical Panel Information Panel name or #: LLP4A SEC 2 Photo Numbers: 165-173 Manufacturer: Eaton Catalog Number: PRL4A Voltage: 208Y/120 Amps: 225 Phase: 3 Wires: 4 Main Breaker Amperage: N/A Total number of poles: 42 Number of Poles in use: 30 Notes: Description matching printed schedule, not hand-written numbers on panel Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 20 3 1 Gen Use Rec 473 Gen Use Rec 421,422,424 2 3 20 x33 Gen Use Rec 421,422,424 43x x35 Rec Coffee Timer 473 63x 20 3 7 Gen Use Rec 473 Gen Use Rec 420,421 8 3 20 x39 System Furn 423 10 3 x x 3 11 Gen Use Rec 432,433 System Furn 423 12 3 x 20 3 13 Flat Panel Monitors 426,427,432 System Furn 423 14 2 20 x 3 15 System Furn 423 16 2 x x 3 17 Ceiling Rec Subwoofer 473 System Furn 423 18 1 20 20 3 19 Gen Use Rec 473 20 3 20 x 3 21 Gen Use Rec 473 Rec Ceiling 456,458,459,461,462 22 3 x x 3 23 Exhaust Fan 473 Gen Use Rec 440,441,442,443 24 3 x 20 2 25 Rec Ceiling 440,441,442,443 26 2 20 x 2 27 Gen Use rec 468,470,471 Gen Use Rec 443,444,445,446 28 2 x 20 2 29 Gen Use Rec,Coffee timer 470,471 30 1 20 x 2 31 Rec Ceiling 445,446,447,448,449 32 1 20 20 3 33 Rec Copier 472 Rec Ceiling 450,451,452,453,454 34 1 20 x 3 35 Flat Panel Monitors 443,469 36 1 20 x 3 37 Flat Panel Monitors 436,463 Not Labeled 38 1 20 20 2 39 Flat Panel Monitors 437,438 Not Labeled 40 1 20 x 2 41 Not Labeled 42 1 20 43 Track Lights 429 Not Labeled 44 45 Not Labeled Not Labeled 46 47 Not Labeled Not Labeled 48 49 Not Labeled Not Labeled 50 51 Not Labeled 52 Not Labeled Page 12 of 34

Electrical Panel Information Panel name or #: LLP4A SEC 1 Photo Numbers: 156-164 Manufacturer: Eaton Catalog Number: PRL4A Voltage: 120/208Y Amps: 225 Phase: 3 Wires: 4 Main Breaker Amperage: N/A Total number of poles: 42 Number of Poles in use: 35 Notes: No Notes Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 20 3 1 Gen Use Rec 473 Gen Use Rec 421,422,424 2 3 20 x33 Gen Use Rec 473 Gen Use Rec 421,422,424 43x x35 Gen Use Rec 473 63x 20 3 7 Gen Use Rec 474 Gen Use Rec 420,421 8 3 20 x39 System Furn 474 System Furn 423 10 3 x x 3 11 System Furn 474 System Furn 423 12 3 x 20 3 13 System Furn 423 14 2 20 x 3 15 Gen Use Rec 432,433,434 System Furn 423 16 2 x x 3 17 Gen Use Rec 428,430,431 System Furn 423 18 1 20 20 3 19 Gen Use Rec 428,430,431 20 3 20 x 3 21 Gen Use Rec 436,437,438 Rec Ceiling 456,458,459,461,462 22 3 x x 3 23 Gen Use Rec 434,435,436 Gen Use Rec 440,441,442,443 24 3 x 20 2 25 Gen Use Rec 433,434,435 Rec Ceiling 440,441,442,443 26 2 20 x 2 27 Gen Use Rec 425,426,427 Gen Use Rec 443,444,445,446 28 2 x 20 2 29 Gen Use Rec 425,426,427 30 1 20 x 2 31 Rec Ceiling 445,446,447,448,449 32 1 20 20 3 33 Rec Copier 439 Rec Ceiling 450,451,452,453,454 34 1 20 x 3 35 System Furn 439 36 1 20 x 3 37 System Furn 439 Not Labeled 38 1 20 20 2 39 System Furn 439 Not Labeled 40 1 20 x 2 41 Gen Use Rec 437,439 Not Labeled 42 1 20 43 Rec Whirlwind 473 Not Labeled 44 45 Rec Whirlwind 473 Not Labeled 46 47 Not Labeled 48 49 Not Labeled 50 51 52 Page 13 of 34

Electrical Panel Information Panel name or #: N1N241 Photo Numbers: 148-155 Manufacturer: Eaton Catalog Number: PRL4B Voltage: 120/208Y Amps: 800 Phase: 3 Wires: 4 Main Breaker Amperage: 400 Total number of poles: 36 Number of Poles in use: 25 Notes: No Notes Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 20 1 1 Rec Restrooms Equip LCP N4N 2 1 20 20 1 3 Not Labeled Not Labeled 4 1 20 20 1 5 Rec Roof Not Labeled 6 1 20 20 1 7 Rec Roof 8 1 20 20 2 9 Rec Roof HVAC EF-1 Smoke Damper Roof 10 1 x 2 11 Rec Open Slot 12 1 20 1 13 Open Slot 14 1 20 1 15 HVAC Fire Smoke Dampers Open Slot 16 1 20 20 1 17 Not Labeled 18 1 1 19 Not Labeled Rec Elevator Lobby 20 3 225 1 21 Open Slot Open Slot 22 3 x 1 23 Open Slot 24 3 x 1 25 Open Slot Panel LPP4B 26 3 225 20 1 27 Open Slot Panel LPP4B 28 3 x 1 29 Security Panel Panel LPP4B 30 3 x 1 31 Open Slot Panel LPP4A 32 3 225 1 33 Open Slot Panel LPP4A 34 3 x 20 1 35 Open Slot Panel LPP4A 36 3 x 37 Panel LPP4A2 38 3 400 39 Electrical Room Fan Panel LPP4A2 40 3 x 41 Panel LPP4A2 42 3 x 43 Not Labeled 44 45 Not Labeled 46 47 Not Labeled 48 49 50 51 52 Page 14 of 34

Electrical Panel Information Panel name or #: LPH4 Photo Numbers: 280-287 Manufacturer: Eaton Catalog Number: PRL2A Voltage: 480/277V Amps: 225 Phase: 3 Wires: 4 Main Breaker Amperage: N/A Total number of poles: 30 Number of Poles in use: 16 Notes: No notes Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 20 1 1 LTG 440,441,442,443,444,445,44L6tg 439,458,459,461,462,464,465,468,469,470,4721 1 20 20 1 3 Ltg Open Office Area 423 Open Slot 41 15 Open Slot Ltg 473 6 1 20 20 1 7 Ltg 447,448,449,450,451,452,453,454,455 Open Slot 81 20 1 9 Ltg Corr, 403,429,472,476 Open Slot 10 1 1 11 Open Slot Ltg 400,401,402,474,475,478,479 12 1 20 1 13 Open Slot Open Slot 14 1 50 1 15 Tankless Water Heater 473 Not Labeled 16 1 20 1 17 Open Slot Not Labeled 18 1 60 20 1 19 Not Labeled Not Labeled 20 1 20 20 1 21 Not Labeled Not Labeled 22 1 20 20 1 23 Not Labeled Not Labeled 24 1 20 20 1 25 Not Labeled Not Labeled 26 1 20 20 1 27 Not Labeled Not Labeled 28 1 20 20 1 29 Not Labeled Not Labeled 30 1 20 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 Page 15 of 34

Electrical Panel Information Panel name or #: LPP4B Photo Numbers: 271-279 Manufacturer: Eaton Catalog Number: PRL1A Voltage: 208/120V Amps: 225 Phase: 3 Wires: 4 Main Breaker Amperage: N/A Total number of poles: 42 Number of Poles in use: 40 Notes: No notes Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 20 3 1 Gen Use Rec 403,404 System Furn 416 2 3 20 x33 System Furn 418 43x x35 System Furn 404 System Furn 416 63x 20 3 7 Rec Copier 404 8 3 20 x39 Gen Use Rec 404,405,406 Gen Use Rec 414,415 10 3 x x 3 11 Gen Use Rec 405,406 Gen Use Rec 414,415,417 12 3 x 20 3 13 System Furn 404 14 2 20 x 3 15 Gen Use Rec 410,412 Gen Use Rec 417,418 16 2 x x 3 17 Gen Use Rec 408,410 Gen Use Rec 412,413 18 1 20 20 3 19 System Furn 407 Rec Flat Panel Monitor 413 20 3 20 x 3 21 Rec Dishwasher 418 Rec Hot Water Tank 418 22 3 x x 3 23 Rec Coffee Timer 418 24 3 x 20 3 25 Rec Microwave 418 System Furn 404 26 3 20 x 3 27 Rec Vending Mach 418 Rec Copier 416 28 3 x x 3 29 Rec Vending Mach 418 Rec Flat Panel Monitor 401 30 3 x 20 3 31 Rec Refrigerator 418 Gen Use Rec 400,401 32 3 20 x 3 33 Gen Use Rec 474,475,478 Gen Use Rec 401,402,403 34 3 x x 3 35 Gen Use Rec 400,475,478 Rec Coffee Timer 409 36 3 x 20 3 37 Gen Use Rec 479 Spare In J-Box 416 38 1 20 x 3 39 Rec Copier 475 System Furn 416 40 1 20 x 3 41 Rec Plotter 475 Rec Copier 416 42 1 43 Rec Copier 478 Gen Use Rec 475 44 45 46 47 Not Labeled 48 49 Open Slot 50 51 52 Page 16 of 34

Electrical Panel Information Panel name or #: EGD1 Photo Numbers: 253-259 Manufacturer: Eaton Catalog Number: PRL4 Voltage: 480Y/227 Amps: 225 Phase: 3 Wires: 4 Main Breaker Amperage: 250 Total number of poles: 42 Number of Poles in use: 22 Notes: No notes Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 125 3 1 Transformer & Panel EGP1 UPS & Panel EUD 2 3 125 x33 Transformer & Panel EGP1 UPS & Panel EUD 43x x35 Transformer & Panel EGP1 UPS & Panel EUD 63x 20 3 7 VAV6 8 3 20 x39 VAV2 VAV7 10 3 x x 3 11 VAV3 VAV8 12 3 x 35 1 13 VAV4 VAV15 14 3 20 40 1 15 VAV1 VAV16 16 3 x 35 1 17 VAV5 VAV17 18 3 x 60 1 19 VAV12 Ltg 477 20 1 20 20 1 21 VAV9 Not Labeled 22 1 20 20 1 23 VAV10 Not Labeled 24 1 20 20 1 25 VAV43 Not Labeled 26 1 60 20 1 27 Not Labeled Not Labeled 28 1 20 20 1 29 Not Labeled Not Labeled 30 1 60 20 1 31 Not Labeled Not Labeled 32 1 20 20 1 33 Not Labeled Not Labeled 34 1 20 20 1 35 Not Labeled Not Labeled 36 1 20 20 1 37 Not Labeled Not Labeled 38 1 20 20 1 39 Not Labeled Not Labeled 40 1 20 20 1 41 Not Labeled Not Labeled 42 1 20 Not Labeled 44 43 46 45 48 47 50 49 52 51 Page 17 of 34

Electrical Panel Information Panel name or #: N1N441 Photo Numbers: 138-144 Manufacturer: Eaton Catalog Number: PRL4B Voltage: 480Y/227V Amps: 800 Phase: 3 Wires: 4 Main Breaker Amperage: 400 Total number of poles: 42 Number of Poles in use: 42 Notes: No Notes Amp Pole Slot Circuit Description Circuit Description Slot Pole Amp 20 3 1 Panel EGD1 Meter Panel LPH4 2 3 225 x33 Panel EGD1 Meter Panel LPH4 43x x35 Panel EGD1 Meter Panel LPH4 63x 225 3 7 8 1 20 x39 Panel EGD1 Level 4 Lobby&Restrooms 10 1 20 70 3 11 Panel EGD1 Not Labeled 12 3 20 x 3 13 Panel EDG1 14 3 x x 3 15 VAV'S 31,32 HVAC Elevator Mach Rm A/C Unit 16 3 x 70 3 17 VAV'S 31,32 HVAC Elevator Mach Rm A/C Unit 18 1 20 x 3 19 VAV'S 31,32 HVAC Elevator Mach Rm A/C Unit 20 3 20 x 3 21 VAV'S 38,40 22 3 x x 3 23 VAV'S 38,40 Equip HWT-4 24 3 x 70 3 25 VAV'S 38,40 Equip Motors EF-Rooftop 26 3 70 x 3 27 VAV'S 24, 19 Equip Motors EF-Rooftop 28 3 x x 3 29 VAV'S 24,23 Equip Motors EF-Rooftop 30 3 x 70 3 31 VAV'S 24,29 32 3 70 x 3 33 VAV'S 33,41 VAV'S 11,14,22 34 3 x x 3 35 VAV'S 13,18 36 3 x 70 3 37 VAV'S 25 VAV'S 20,21 38 3 70 x 3 39 VAV'S 30,34 40 3 x x 3 41 VAV'S Future SE corner 42 3 x 400 3 43 VAV'S 35 VAV'S Future SE corner 44 3 40 x 3 45 VAV'S 36,39 VAV'S Future SE corner 46 3 x x 3 47 VAV'S 37,42 48 3 x 49 Panel N1N421 VAV'S 26,27,28 50 51 Panel N1N421 VAV'S 26,27,28 52 Panel N1N421 VAV'S 26,27,28 Panel N1N421 Panel N1N421 Panel N1N421 Page 18 of 34

HVAC Information HVAC System, Cooling & Heating Cooling Type: V.A.V. Heating Type: Combined R.T.U Heating supplied by landlord? UTD Type of heating supplied? Electric Notes: No Notes Cooling System Cooling Unit #: RTU 1 Photo Numbers: 002-004 Unit Manufacturer: Mitsubishi Electric Model Number: MUY-D30NA Serial #: 8000834 T Capacity in Tons: 2.5 MFG Date: UTD, 2008 Voltage: 208/230 Phase: 1 Amps: 25 If combined with heating and unit is electric what is the kilowatt capacity?: UTD If combined with heating and Gas: Input BTU N/A Output BTU N/A Disconnect located on R.T.U?: Yes Voltage: 240 Amps: 30 Phase: UTD Notes: Phase not labeled on Disconnect Heating System Heating System is combined with Cooling Heating Unit #: TRUE Unit Manufacturer: Photo Numbers: Serial #: Model Number: Kilowatt capacity if electric: Capacity if gas: Input BTUs: MFG Date: Notes: No Notes Output BTUs: Page 19 of 34

HVAC Information Cooling System Photo Numbers: 005-007 Cooling Unit #: RTU 2 Model Number: MUY-D30NA-1 Unit Manufacturer: Mitsubishi Electric Serial #: 0000424 T Capacity in Tons: 2.5 MFG Date: UTD, 2008 Voltage: 208/230 Phase: 1 Amps: 25 If combined with heating and electric what is the kilowatt capacity?: UTD If combined with heating and Gas: Input BTU N/A Output BTU N/A Disconnect located on R.T.U?: Yes Voltage: 240 Amps: 30 Phase: UTD Notes: Phase not labeled on Disconnect Cooling System N/A Cooling Unit #: RTU 3 FALSE Photo Numbers: 008-010 Unit Manufacturer: Mitsubishi Electric Model Number: MUY-D30NA-1 Serial #: 0000584 T Capacity in Tons: 2.5 MFG Date: UTD, 2008 Voltage: 208/230 Phase: 1 Amps: 25 If combined with heating and electric what is the kilowatt capacity?: UTD If combined with heating and Gas: Input BTU N/A Output BTU N/A Disconnect located on R.T.U?: Yes Voltage: 240 Amps: 30 Phase: UTD Notes: Phase not labeled on Disconnect Page 20 of 34

HVAC Information Heating System Heating System is combined with Cooling Heating Unit #: TRUE Unit Manufacturer: Photo Numbers: Serial #: Model Number: Kilowatt capacity if electric: Capacity if gas: Input BTUs: MFG Date: Notes: No Notes Output BTUs: Heating System Heating Unit #: TRUE N/A Photo Numbers: Unit Manufacturer: Model Number: Serial #: MFG Date: Kilowatt capacity if electric: Capacity if gas: Input BTUs: Output BTUs: Notes: No Notes Page 21 of 34

HVAC Information Cooling System Photo Numbers: 011-013 Cooling Unit #: RTU 4 Model Number: MUY-D30NA Unit Manufacturer: Mitsubishi Electric Serial #: 8000621 T Capacity in Tons: 2.5 MFG Date: UTD, 2008 Voltage: 208/230 Phase: 1 Amps: 25 If combined with heating and electric what is the kilowatt capacity?: UTD If combined with heating and Gas: Input BTU N/A Output BTU N/A Disconnect located on R.T.U?: Yes Voltage: 240 Amps: 30 Phase: UTD Notes: Phase not labeled on Disconnect Cooling System N/A Cooling Unit #: RTU 5 FALSE Photo Numbers: 014-016 Unit Manufacturer: Mitsubishi Electric Model Number: MUY-D30NA-1 Serial #: 0000587 T Capacity in Tons: 2.5 MFG Date: UTD, 2008 Voltage: 208/230 Phase: 1 Amps: 25 If combined with heating and electric what is the kilowatt capacity?: UTD If combined with heating and Gas: Input BTU N/A Output BTU N/A Disconnect located on R.T.U?: Yes Voltage: 240 Amps: 30 Phase: UTD Notes: Phase not labeled on Disconnect Page 22 of 34

HVAC Information Heating System Heating System is combined with Cooling Heating Unit #: TRUE Unit Manufacturer: Photo Numbers: Serial #: Model Number: Kilowatt capacity if electric: Capacity if gas: Input BTUs: MFG Date: Notes: No Notes Output BTUs: Heating System Heating Unit #: TRUE N/A Photo Numbers: Unit Manufacturer: Model Number: Serial #: MFG Date: Kilowatt capacity if electric: Capacity if gas: Input BTUs: Output BTUs: Notes: No Notes Page 23 of 34

HVAC Information Cooling System Photo Numbers: 017-019 Cooling Unit #: RTU 6 Model Number: MUY-D30NA-1 Unit Manufacturer: Mitsubishi Electric Serial #: 0000590 T Capacity in Tons: 2.5 MFG Date: UTD, 2008 Voltage: 208/230 Phase: 1 Amps: 25 If combined with heating and electric what is the kilowatt capacity?: UTD If combined with heating and Gas: Input BTU N/A Output BTU N/A Disconnect located on R.T.U?: Yes Voltage: 240 Amps: 30 Phase: UTD Notes: Phase not labeled on Disconnect Cooling System N/A Cooling Unit #: FL-1 FALSE Photo Numbers: 020-022 Unit Manufacturer: Mitsubishi Electric Model Number: MUY-GE12NA Serial #: 0001756 T Capacity in Tons: 1 MFG Date: UTD, 2008 Voltage: 208/230 Phase: 1 Amps: 25 If combined with heating and electric what is the kilowatt capacity?: UTD If combined with heating and Gas: Input BTU N/A Output BTU N/A Disconnect located on R.T.U?: Yes Voltage: 240 Amps: 30 Phase: UTD Notes: Phase not labeled on Disconnect; supplies Server Room Page 24 of 34

HVAC Information Heating System Heating System is combined with Cooling Heating Unit #: TRUE Unit Manufacturer: Photo Numbers: Serial #: Model Number: Kilowatt capacity if electric: Capacity if gas: Input BTUs: MFG Date: Notes: No Notes Output BTUs: Heating System Heating Unit #: TRUE N/A Photo Numbers: Unit Manufacturer: Model Number: Serial #: MFG Date: Kilowatt capacity if electric: Capacity if gas: Input BTUs: Output BTUs: Notes: No Notes Page 25 of 34

HVAC Information Cooling System Photo Numbers: 023-028 Cooling Unit #: FL-2 Model Number: 24ACC660A300 Unit Manufacturer: Carrier Serial #: 1416E14967 Capacity in Tons: 5 MFG Date: Mar, 2016 Voltage: 208/230 Phase: 1 Amps: 40 If combined with heating and electric what is the kilowatt capacity?: UTD If combined with heating and Gas: Input BTU N/A Output BTU N/A Disconnect located on R.T.U?: Yes Voltage: 240 Amps: 60 Phase: UTD Notes: Phase not labeled on Disconnect Cooling System N/A Cooling Unit #: TRUE Photo Numbers: Unit Manufacturer: Model Number: Serial #: Capacity in Tons: MFG Date: Voltage: Phase: Amps: If combined with heating and electric what is the kilowatt capacity?: If combined with heating and Gas: Input BTU Output BTU Disconnect located on R.T.U?: Voltage: Amps: Phase: Notes: N/A Page 26 of 34

HVAC Information Heating System Heating System is combined with Cooling Heating Unit #: TRUE Unit Manufacturer: Photo Numbers: Serial #: Model Number: Kilowatt capacity if electric: Capacity if gas: Input BTUs: MFG Date: Notes: No Notes Output BTUs: Heating System Heating Unit #: TRUE N/A Photo Numbers: Unit Manufacturer: Model Number: Serial #: MFG Date: Kilowatt capacity if electric: Capacity if gas: Input BTUs: Output BTUs: Notes: No Notes Page 27 of 34

HVAC Information Thermostats Manufacturer: Alerton Photo Numbers: 299 Quantity: 10 Notes: No Notes FALSE Only 1 Thermostat Type Photo Numbers: 300 Manufacturer: UTD Quantity: 1 Notes: No Notes Natural Gas TRUE No Natural Gas Meter Number: Photo Numbers: Location: Gas Line Diameter(s) Into Meter: Into Space: Notes: No Notes Duct Info FALSE No Duct Work Supply air is: Ducted Return air is: Ducted Supply Duct is: Rigid & Flex Return Duct is: Rigid & Flex Duct insulated?: Yes Notes: No Notes Duct Heater No Duct Heater Manufacturer: TRUE Photo Numbers: Model Number: Voltage: Phase: Watts: Notes: No Notes V.A.V. No V.A.V Manufacturer: Nailor FALSE Photo Numbers: 056-060 Model Number: D35SEST Voltage: 480 Phase: 3 Watts: 850 Notes: No Notes Page 28 of 34

HVAC Information V.A.V. No V.A.V Manufacturer: Nailor FALSE Model Number: D37SE Photo Numbers: 061-064 Voltage: 277 Phase: 1 Watts: 700 Phase: Notes: No Notes Phase: Phase: V.A.V. Phase: No V.A.V Manufacturer: Nailor FALSE Photo Numbers: 065-068 Model Number: D35SEST Voltage: 480 3 Watts: 850 Notes: No Notes V.A.V. No V.A.V Manufacturer: Nailor FALSE Photo Numbers: 069-072 Model Number: D37SEST Voltage: 277 1 Watts: 840 Notes: No Notes V.A.V. No V.A.V Manufacturer: Nailor FALSE Photo Numbers: 073-077 Model Number: D37SEST Voltage: 277 1 Watts: 380 Notes: No Notes V.A.V. No V.A.V Manufacturer: Nailor FALSE Model Number: D35SEST Photo Numbers: 78-82 Voltage: 480 3 Watts: 850 Notes: No Notes Page 29 of 34

HVAC Information V.A.V. No V.A.V Manufacturer: Nailor FALSE Model Number: D37SE Photo Numbers: 083-087 Voltage: 277 Phase: 1 Watts: 700 Phase: Notes: No Notes Phase: Phase: V.A.V. Phase: No V.A.V Manufacturer: Nailor FALSE Photo Numbers: 088-092 Model Number: D35SEST Voltage: 480 3 Watts: 850 Notes: No Notes V.A.V. No V.A.V Manufacturer: Nailor FALSE Photo Numbers: 093-097 Model Number: D37SEST Voltage: 277 1 Watts: 380 Notes: No Notes V.A.V. No V.A.V Manufacturer: Nailor FALSE Photo Numbers: 098-101 Model Number: D37SEST Voltage: 277 1 Watts: 380 Notes: No Notes V.A.V. No V.A.V Manufacturer: Nailor FALSE Model Number: D35SEST Photo Numbers: 102-105 Voltage: 480 3 Watts: 850 Notes: No Notes Page 30 of 34

HVAC Information V.A.V. No V.A.V Manufacturer: Nailor FALSE Model Number: D37SEST Photo Numbers: 106-110 Voltage: 277 Phase: 1 Watts: 380 Phase: Notes: No Notes Phase: Phase: V.A.V. Phase: No V.A.V Manufacturer: Nailor FALSE Photo Numbers: 111-114 Model Number: D37SE Voltage: 277 1 Watts: 700 Notes: No Notes V.A.V. No V.A.V Manufacturer: TRUE Photo Numbers: Model Number: Watts: Voltage: Notes: No Notes V.A.V. No V.A.V Manufacturer: TRUE Photo Numbers: Model Number: Watts: Voltage: Notes: No Notes V.A.V. No V.A.V Manufacturer: TRUE Photo Numbers: Model Number: Watts: Voltage: Notes: No Notes Page 31 of 34

Plumbing Information Water Fountain No Water Fountain Drinking fountain Manufacturer: TRUE Model #: Quantity: Mount: Photo Numbers: Notes: No Notes Mop Sink TRUE No Mop Sink Location: Photo Numbers: Notes: No Notes Water Heater FALSE No Water Heater Water Heater Manufacturer: Bosch Model #: ES 4-1M WIR Capacity in Gallons: 4 Type: Electric Photo Numbers: 294-295 Location: Under sink in kitchen area Operating: Yes On base or platform: No Watts: 1440 Volts: 120 Phase: 1 If gas BTU's/hour: N/A Notes: No Notes Water Meter: No Water Meter Meter#: UTD FALSE Location: Locked in room in parking ramp Does meter serve only surveyed space: UTD Diameter of pipe going into space: UTD Photo Numbers: Notes: Meter not accessible, in locked room on parking deck Page 32 of 34

Plumbing Information Water Fountain No Water Fountain Drinking fountain Manufacturer: TRUE Model #: Quantity: Mount: Photo Numbers: Notes: No Notes Mop Sink TRUE No Mop Sink Location: Photo Numbers: Notes: No Notes Water Heater No Water Heater Water Heater Manufacturer: Eemax FALSE Model #: HA018240 Capacity in Gallons: Tankless Type: Electric Photo Numbers: 296-297 Location: Under sink, east side of building Operating: Yes On base or platform: No Watts: UTD Volts: 240 Phase: 1 If gas BTU's/hour: NA Notes: No Notes Water Meter: No Water Meter Meter#: TRUE Location: Does meter serve only surveyed space: Diameter of pipe going into space: Photo Numbers: Notes: No Notes Page 33 of 34

Emergency Systems Information Sprinkler System FALSE No Sprinkler System Sprinkler riser in space: No Sprinkler Head Type: Concealed Photo numbers of sprinkler main: 288-293 Notes: Sprinkler heads exposed in open ceiling areas. Riser in stairwell near elevators. Smoke Detectors & Alarms Ceiling mounted Smoke Detectors: No If Yes Photo numbers: N/A N/A Smoke evacuation system: No If Yes Photo numbers: N/A Central station monitor: No If Yes Photo numbers: 298 N/A Fire Alarm system: Yes Manufacturer: Prime Electrio 301 Fire Alarm model: UTD Photo Numbers: Emergency Lighting: No If Yes, functional? No Photo Numbers: Exit Lights: Yes If Yes, functional? Yes Photo Numbers: Notes: No Notes Smoke Detectors (Above Ceiling) TRUE No Above Ceiling Smoke Detectors Smoke Detectors above ceiling: If Yes Photo numbers: Duct mounted Smoke Detectors: If Yes Photo numbers: Smoke Detectors above ceiling Hard Wired: Notes: No Notes Page 34 of 34